Instruction Sheet

Thank you very much for purchasing DELTA CTA series. Please read this instruction sheet before using your CTA
series to ensure proper operation and please keep this instruction sheet handy for quick reference.

¾

DANGER! Caution! Electric Shock!

¾

When the power is on, DO NOT touch the AC terminals in case an electric shock may occur.

¾

Make sure the power is disconnected when you check the unit inside.

¾

CTA series is an OPEN-TYPE device. They are intended for installation completely within an overall panel and are for use
in counting or timing application. If it will cause serious injury to workers or damage on other equipments when used in a
dangerous environment, please make sure it is installed in an automatic safety protection device.

1.

Precaution

1. Always use recommended solder-less terminals: Fork terminal with isolation (M3 screw, width 7.0mm), hole (diameter

3.2mm). Screw size: M3x6.5 (with 6.8x6.8 square washer). Recommended tightening torque: 0.4 N.m (4kgf.cm).
Applicable wire: solid/twisted wire of 2mm

2

, 12AWG to 24 AWG. Please be sure to tighten them properly.

2. Prevent dust or metallic debris from falling into the device and cause malfunctions.
3. DO NOT modify or uninstall the device.
4. DO NOT use empty terminals.
5. Make sure the wires are correctly connected to proper terminals.
6. Keep away from high-voltage and high-frequency environment during installation in case of interference.
7. Prevent using the device in premises which contain:

Dust or corrosive gas

High humidity

High radiation

Vibration and shock

8. CTA series is an open-type device. Make sure to install it in an enclosure to prevent dust, humidity in case of an electric

shock.

9. Please make sure the power cables and signal device are installed correctly before switching on the power; otherwise

serious damage may occur.

10. DO NOT touch the terminals or repair the device when the power is on; otherwise an electric shock may occur.
11. Please wait for one minute after the power is switched off to allow the capacitor to discharge and DO NOT touch the

internal wiring within this period.

12. Use dry cloth to clean the device. DO NOT use acid or alkaline liquid to clean the device.

2.

Display, Indicators and Keys

Reset 2 ind icato r
Reset 1 ind icato r

Ke y p ro te ct 2 in dica tor

Ou tput 2 i nd icator

Ke y p ro te ct 1 in dica tor

Ou tput 1 i nd icator

Sp ecia l fun cti on ind icato r

Lo ck ke y

Reset key

Mode and nu mb er sh ift key

PV (Pr esen t Val ue) disp lay

SV (Se t Val ue) di sp la y

Timer functi on i ndi cator

Cou nter fu nctio n in di ca tor
Tacho meter fu nctio n in di ca tor

Up/Down ke y

™

LCD Display and indicators

RST 1/2

Light on when reset signal is detected

BATCH

“Batch Counting Mode” in Counter and Tachometer function

K/P 1/2

Light on when key-protected mode is enabled

SET 1 2

SV1, SV2 display

OUT 1/2

Light on when output is executing

TAC

Light on when Tachometer function is executing

H M S

Hour, minute, second, unit of timer, displayed
in Timer function

CNT

Light on when Counter function is executing

TOTAL

“Total Counting Mode” in Counter and
Tachometer function

TMR

Light on when Timer function is executing

™

Key Operation

Increase and decrease SV or change parameter settings.

Left move 1 digit of the selected digit. The indicator of the selected digit will flash.

MODE

Save the set parameters or switch among functions.

LOCK

Prevent settings from being changed. Key-protected mode still works after the power is switched off. Press

LOCK

to enter key-protected mode. In non-key-protected status, press

LOCK

to enter Lock 1. In Lock 1, press

LOCK

again to enter Lock 2. Press

MODE

and

at the same time to disable key-protected mode.

(Lock 1

)

disables the functions of all keys.

(Lock 2) allows users to change SV and functions of

RESET

remain.

LOCK

only functions in non-key-protected status.

RESET

Clear and reset PV.

™

Modes: Operation Mode and Configuration Mode

Operation When the power is on, the timer/counter/tachometer is in the operation mode. Press

to change SV, or

to make change on a desired digit. The indicator of the selected digit will flash. After the change is made,

press

MODE

to save the setting. If SV or parameters are not changed, press

MODE

once to switch between SET1 and

SET2.

Configuration Press

MODE

in operation mode

for more than 3 seconds to enter configuration mode. Press

MODE

once to switch

among parameters. To return to operation mode, press

MODE

for more than 3 seconds.

3.

Ordering Information

C TA

2

3

4

5

6

1

n

Product name

CTA: Delta Counter/Timer/Tachometer A series

q

Preset stage

0: 2 preset stage

o

Panel size

4: 48mm x 48mm 1/16DIN

r

Communication

0: none

p

Output 2

0: NPN; 1: Relay

s

Power supply

A:

AC

100~240V

4.

Specification

Power input AC 100~240V, 50/60Hz

Input voltage range 85% to 110%, rated voltage
Power consumption Less than 10VA

External power supply 12Vdc ±10%, 100mA

Display Double-line, 6-digit negative transmissive LCD display

Non-voltage input (NPN): ON impedance 1K ohm max. ON residual voltage: 2V max.

Input signal

Voltage input (PNP): High level: 4.5 to 30Vdc, Low level: 0 to 2Vdc
Relay: SPST max.250Vac, 5A (resistance load)

Output 1

Transistor: NPN open collector. When 100mA /30Vdc, residual voltage=1.5Vdc max.
Relay: SPDT max.250Vac, 5A (resistance load)

Output 2

Transistor: NPN open collector. When 100mA /30Vdc, residual voltage=1.5Vdc max.

Dielectric strength 2000Vac 50/60 Hz for 1 minute

Vibration resistance Without damage: 10~55Hz, amplitude=0.75mm, 3 axes for 2 hours

Shock resistance Without damage: drop 4 times, 300m/s

2

, 3 edges, 6 surfaces and 1 corner

Ambient temperature 0

o

C to +50

o

C

Storage temperature -20

o

C to +65

o

C

Altitude 2000m or less

Ambient humidity 35% to 85% RH (non-condensing)

Pollution degree Degree 2

5.

Parameters in Configuration Mode

™

Timer

Select a
function


MOD E

Setup Timer
function,
(counting up
or down)

MOD E

Select
output
mode of
Timer

MOD E

Setup the
displayed
unit of timer

MOD E

Setup the
pulse width
of output 1

MOD E

Reset min.
pulse width


MOD E

Select input
type (PNP
or NPN)

MOD E

Back to

“select a

function”

™

Counter

Select a
function

MOD E

Select
counting
modes

MOD E

Setup input
mode of
Counter

MOD E

Setup output
mode of
Counter (not
dual output)

MOD E

Setup dual
output counting
mode (dual
output)

MOD E

Setup counting
speed

MOD E

Setup the
pulse width of
output 1

MOD E

Back to

“select a

function”

Select input
type (PNP or
NPN)

MOD E

Reset min.
pulse width

MOD E

Save data or
not while
switching off
power

MOD E

Setup pre-scale
value

MOD E

Setup the
decimal point

MOD E

Setup the
pulse width of
output 2

MOD E

™

Tachometer

Select a function

MOD E

Setup output mode
of Tachometer

MOD E

Setup counting
speed

MOD E

Setup the decimal
point

MOD E

Setup pre-scale value

MOD E

Back to “select a

function”

Select input type
(PNP or NPN)

MOD E

Reset min. pulse
width

MOD E

!

Setup the average of

input data

MOD E

Setup the delay time
while switching on
power

MOD E

™

Timer + Counter Mixed

Select a
function



MOD E

Setup Timer
function,
(counting
up or down)

MOD E

Setup
output
mode of
timer

MOD E

Setup the
displayed
unit of
timer

MOD E

Setup
input
mode of
Counter

MOD E

Setup
output
mode of
Counter (not
dual output)

MOD E

Setup
counting
speed

MOD E

Setup the
pulse width
of output 1

MOD E

Back to

“select a

function”

Select
input type
(PNP or
NPN)

MOD E

Reset
min.
pulse
width

MOD E

Save data
or not
while
switching
off power

MOD E

Setup
pre-scale
value

MOD E

Setup
the
decimal
point

MOD E

Setup the
pulse
width of
output 2

MOD E

6.

Timer Function

There are counting up/down modes, several counting units and output modes to choose from in timer function.

Select counting up

or counting down

Setup the output time of timer, from 0 to 99.99 secs. 0= Hold output

Setup output modes

Setup the counting unit of the timer.

sec 0.01~9999.99

A unit = 10ms.

Max. counting = 9999.99 secs.

sec 0.1~99999.9

A unit = 0.1sec.

Max. counting = 99999.9 secs.

sec 1~999999

A unit = 1 sec.

Max. counting = 999999 secs.

min,sec 0.01~9959.99

A unit = 0.01 sec. Max. counting = 5999.99 secs.

min,sec 0.1~99959.9

A unit = 0.1 sec.

Max. counting = 59999.9 secs.

min 0.1~99999.9

A unit = 0.1 min.

Max. counting = 99999.9 mins.

min 1~999999

A unit = 1 min.

Max. counting = 999999 mins.

hr,min,sec 1~995959

A unit = 1 sec.

Max. counting = 359999 secs (100hr)

hr,min 1~999959

A unit = 1 min.

Max. counting = 35999999 secs (10000hr)

hr 1~999999

A unit = 1 hr.

Max. counting = 999999 hrs

Power signal

Start signal

Pause signal

Clear signal

U p

Down

0

0

S V

S V

S i g n a l O n D e l a y 1

t

t

Output signal

Power signal

S t a r t s i g n a l

Pause signal

Cle ar signa l

Output signal

Up

Down

0

0

SV

SV

S i g n a l O n D e l a y 2

t

t

P o w e r s i g n a l

Start signal

Pause signal

Clear signal

Output signal

SV

0

U p

Do wn

SV

0

Signal Off Delay

Power signal

Start signal

Paus e sign al

Clear signal

Output signal

SV

0

U p

Down

SV

0

S i g n a l O n

P o w e r s i g n a l

S t a r t s i g n a l

P a u s e s i g n a l

C l e a r s i g n a l

O u t p ut s ig na l

U p

Do wn

S V

S V

0

0

P o w e r O n D e l a y

t

t

t

Po wer signal

Start signal

Pa use signal

Clear signal

Output signal

Up

Down

SV

SV

0

0

Power On Delay Hold

t

t

t

t

Power signal

Start signal

Pause signal

Clear signal

O u t pu t s i g na l

Up

Down

S V

S V

Repeat Cycle

0

0

timer out put s et as 0

Power s ignal

Start signal

P a u s e s i g n a l

C l e a r s i g n a l

Output signal

Up

Down

SV

SV

R e p e a t C y c l e

t

t

t

t i m e r o u t p u t n o t s e t a s 0

Power signal

Start signal

Pause signal

Clear signal

Output signal

U p

Down

SV

SV

0

0

Repeat Cycle Hold

Timer output set as 0

Po we r sign al

St art signal

Pause signal

Clear signal

Output signal

Up

D o w n

SV

SV

0

0

R C Y H t i m e r o u t p u t n o t s e t a s 0

t

t

t

P o w e r s i g n a l

S t a r t s i g n a l

P a us e sig na l

Clear sig nal

O u t p u t s i g n a l

U p

D ow n

S V 1

S V 1

S V 2

S V 2

0

0

Repeat C ycl e 2

Power signal

Start signal

P a u s e s ig n a l

Clear signal

Output signal

Up

Down

0

SV

SV

0

S i g n a l C u m u l a t e

Po wer signal

S t a r t s i g n a l

Pause signal

Clear signal

Output signal

Up

Down

SV 1

SV 2

SV 1

0

0

SV 2

S i g n a l Tw i n O N - S t a r t

Power signal

Start signal

P a u s e s i g n a l

C l ea r s i g n a l

Output signal

Up

D o w n

S V 1

SV1

S V 2

SV2

0

0

Signal Twin OFF-Start