Page 2 - TABLE OF CONTENTS
1 • Control systems • Control systems TABLE OF CONTENTS CONTROL SYSTEMS 1 Survey control systems 2 2 Individual control systems 4 Wired / infrared remote control 4 Online controller 12 Siesta Sky Air 14 3 Centralised control systems 15 Centralised remote control / Unified ON/OFF control / Schedule t...
Page 5 - kWh indication; keeps; Save energy
A series of energy saving functions that can be individually selected › Temperature range limit › Setback function › Presence & floor sensor connection (available on new round flow cassette) › kWh indication › Set temperature auto reset › Off timer Temperature range limit avoids excessive heatin...
Page 7 - Specifications; Technical Specifications
6 • Control systems • Individual control systems • ARC*/BRC* Specifications Technical Specifications BRC1E52A* / BRC1E52B* Casing Colour Fresh White Button cover No Operation LED Colour Green Dimensions Unit HeightxWidthxDepth mm 120x120x19 Packed unit HeightxWidthxDepth mm 150x160x55 Weight Unit kg...
Page 8 - Dimensional drawing
7 • Control systems • Individual control systems • ARC*/BRC* BRC1E52A/B - Wired remote control Dimensional drawing Operation lamp 5x7 oblong hole 5x15 oblong hole Staple Left outlet Lower case portion Lower case portion Switch box for one switch ex. KJB111A (optional accessory) Switch box for two sw...
Page 9 - BRC1D52 - Wired remote control
8 • Control systems • Individual control systems • ARC*/BRC* BRC1D52 - Wired remote control Dimensional drawing BRC4C61,62,65 - Infrared remote control Dimensional drawing Cover closed Cover open 5 x 7 (Round end slit) 5 x 10 (Round end slit) 6,5 x 9 (Round end slit) Hole ø5 3D007898B Transmitting p...
Page 10 - BRC7E530W - Infrared remote control; BRC7E63W - Infrared remote control
9 • Control systems • Individual control systems • ARC*/BRC* BRC7E530W - Infrared remote control Dimensional drawing BRC7E63W - Infrared remote control Dimensional drawing Remote control dimensions Receiver installation procedure Transmitting part Drain piping side Refrigerant piping side Decoration...
Page 11 - BRC7E618 - Infrared remote control
10 • Control systems • Individual control systems • ARC*/BRC* BRC7E618 - Infrared remote control Dimensional drawing BRC7C(A)528W - Infrared remote control Dimensional drawing Remote control dimensions Transmitting part 157 62 17.5 Remote controller holder installation procedure (Installation to wal...
Page 12 - BRC3A61 - Simplified remote control for hotel applications; BRC2C51 - Simplified remote control
11 • Control systems • Individual control systems • ARC*/BRC* BRC3A61 - Simplified remote control for hotel applications Dimensional drawing BRC2C51 - Simplified remote control Dimensional drawing 2 - 5 x 9 Slot (Fixing hall) (Unit: mm) 3D013859A 3D050645
Page 13 - no matter where you are; Light commercial use:; Available software features
12 • Control systems • Individual control systems • Online controller • KKRP01A Always in control, no matter where you are Daikin provides a new control solution to monitor and control the main functions of the residential indoor units. The system is working in an end-user friendly way and can be us...
Page 14 - App; Online controller KKRP01A
13 • Control systems • Individual control systems • Online controller • KKRP01A App Daikin gives you a whole new way to control & monitor your residential indoor units. Ask your Daikin installer to equip your unit with an Online Controller (KKRP01A) and now you have the option to manage your uni...
Page 15 - Overview of available controllers for Siesta Sky Air
14 • Control systems • Individual control systems • Siesta Sky Air Siesta Sky Air indoor units Controllers ACQ*A cassette ACQ-B - Standard wireless remote controller in box of decoration panel ADP125A - Optional wired remote controller ARCWB AHQ*A ceiling suspended - Standard wireless remote control...
Page 16 - Centralised remote control
15 • Control systems • Centralised control systems • Centralised remote control/Unified ON/OFF / Schedule timer Centralised control of the VRV system can be achieved via 3 user friendly compact controls: centralised remote control, unified on/off control and schedule timer. These controls may be use...
Page 17 - DCS302C51 - Centralised remote control
16 • Control systems • Centralised control systems • Centralised remote control/Unified ON/OFF / Schedule timer DCS302C51 - Centralised remote control Dimensional drawing DCS301B51 - Unified on/off control Dimensional drawing Switch box Door open Door closed ø 5 hole Optional switch box 2 - 5 x 7 Ro...
Page 19 - Survey of various control systems
18 • Control systems • Centralised control systems • wiring details Survey of various control systems For more effective localized environmental control Daikin offers various control systems such as single or double remote control or centralized control. This enables the construction of a variety of...
Page 20 - Wiring example of centralised control systems; Pattern 1
19 • Control systems • Centralised control systems • wiring details Wiring example of centralised control systems • Be sure to connect the wiring of the central controller to (A) or (B). (Connect to (B), if it is possible.) • Be sure to limit the number of indoor units within the limitation for each...
Page 22 - Length of transmission wiring
21 • Control systems • Centralised control systems • wiring details Length of transmission wiring The super wiring system, that integrates the control wiring between indoor unit and outdoor unit and the transmission wiring to the central controllers into one common wiring, should satisfy the followi...
Page 25 - Number of connectable Units
24 • Control systems • Centralised control systems • wiring details Length of transmission wiring Number of connectable Units Central control equipment Indoor unit Outdoor unit Other adapters Target controller (max. number) • Centralised remote control (2 units) • Unified ON/OFF control (8 units) • ...
Page 26 - Flow chart to determine the number of units to be connected
25 • Control systems • Centralised control systems • wiring details Length of transmission wiring Flow chart to determine the number of units to be connected Notes 1 Condition (A) means: • Central control equipment + Indoor units + Outdoor units + other adapters £ 160 units • Conversion number of ce...
Page 27 - Main Functions; Basic solution; for control of Sky Air and VRV; Up to 4 units / 1 adapter
26 • Control systems • Centralised control systems • DTA113B51 BRC1D52 Features & Outline Basic solution for control and management of Sky Air and VRV systems Application area • Critical applications for centralized monitoring. System functions • Automates alarm (report messages) for any malfunc...
Page 28 - Electric wiring
27 • Control systems • Centralised control systems • DTA113B51 Electrical wiring Procured on-site sheathed vinyl cord( VCTF 0.2 mm2 or 0.3 mm2) Important • The A (+) and B (-) terminals have polarity which must not be mixed up.• Turn on SS1 (terminating resistance) for the DS-NET adapter.• Leave the...
Page 29 - easy monitoring; and operation of VRV systems; Features
28 • Control systems • Centralised control systems • DCS601C51 • Languages › English › French › German › Italian › Spanish › Dutch › Portuguese System layout › Up to 64 indoor units can be controlled › Touch panel (full colour LCD via icon display) Management › Easy management of electricity consump...
Page 30 - Web Application & Internet
29 • Control systems • Centralised control systems • DCS601C51 • Features Web Application & Internet
Page 31 - System overview
30 • Control systems • Centralised control systems • DCS601C51 • System overview This intelligent Touch Controller is capable of controlling/monitoring up to 64 groups of indoor units (hereafter “groups”). The main functions of the intelligent Touch Controller include:1 Set back function, enabling a...
Page 32 - Part Names - Connection; Back
31 • Control systems • Centralised control systems • DCS601C51 • Part Names - Connection Back Using DIII-NET Plus adapter being sold as an accessory, you can increase the number of indoor units to be controlled. RS232-C connector for DIII-NET Plus adapter When using Air Conditioning Network Service ...
Page 34 - Accessories
33 • Control systems • Centralised control systems • DCS601C51 • 3D047630 3D047631 Accessories DEC101A51 - Digital input Dimensional drawing External connection diagram Mounting hole (*1) (198) (309) 325 335 70 70 70 1 6 4.5 40 40 40 80 40 325 UP Spare hole (*1) Mounting hole (*1) Service entrance -...
Page 37 - Dimensions
36 • Control systems • Centralised control systems • DCS601C51 • Dimensions System wiring Connecting Unification adaptor allows using the contact for normal and abnormal operation signal and collective start/stop with a contact. For details, contact the vendor you purchased the product from. Also, b...
Page 38 - Power Proportional Distribution Card; Function and Outline
37 • Control systems • Centralised control systems • DCS601C51 • Power Proportional Distribution Card Function and Outline Power Proportional Distribution Card, in combination with an existing intelligent Touch Controller, enables to proportionally calculate and display electricity amount used by ai...
Page 39 - File Format
38 • Control systems • Centralised control systems • DCS601C51 • Power Proportional Distribution Card File Format When Power Proportional Distribution Report is saved, a zone information file, an electric power information file and detailed information file are created. Zone information file This co...
Page 40 - System overview and main features; Accessoires
39 • Control systems • Management control • TABLE OF CONTENTS iTM 1 System overview and main features 40 2 Functions & options 42 2.1. Functions 42 2.2. Options 43 3 Specifications 44 3.1. Intelligent Touch Manager 44 3.1.1. Main specifications 44 3.1.2. Location of terminals and switches 45 3.1...
Page 41 - Integration; with; intelligent control; System overview and main features
~ ~ DCM601A51 Integration with intelligent control solutions Fire alarm kWh meter Web Access Web Access Malfunction report by E-Mail Air Conditioning Network Service System DIII-NET line iTM plus adaptor line Di/Pi port Di/Pi line Max. 200m Internal modem (option) Max. 64 groups Max. 7 adapters LAN ...
Page 42 - Languages
User friendliness › Intuitive user interface › Visual lay out view and direct access to indoor unit main funtions › All functions direct accessible via touch screen or via web interface Flexibility › In size: modular design for use in small to large applications › In integration: from simple A/C con...
Page 46 - Understanding where terminals and switches are located; Rear face
45 • Control systems • intelligent Touch Manager • ED721208 Understanding where terminals and switches are located Understand the arrangement of terminals and the location of openings on the unit and plan how to route the cable and in which order to connect its wires to facilitate the installation p...
Page 47 - Front panel
46 • Control systems • intelligent Touch Manager • ED721208 Front panel Located below the monitor display on the front panel are four LEDs that indicate the operating status of the intelligent Touch Manager. Sliding the front slide cover down and then removing a screwed cover reveals terminals used ...
Page 48 - Side face
47 • Control systems • intelligent Touch Manager • ED721208 Side face On the left side face of the intelligent Touch Manager, a USB port cover is provided. You use this cover during setup after installation or during maintenance. You also see an attached label, bearing the model, weight, power ratin...
Page 51 - Requirements that must be met; Precautions for using multiple centralized controllers
50 • Control systems • intelligent Touch Manager • ED721208 NOTE • What’s a remote controller group? A single remote controller can simultaneously control a maximum of 16 indoor units. This capability is referred to as group control. A remote controller group is a group of indoor units controlled un...
Page 52 - Connecting a LAN cable
51 • Control systems • intelligent Touch Manager • ED721208 <DIII MASTER> To set the intelligent Touch Manager to SLAVE, use the DIII MASTER switch located under the front slide cover. Placing the DIII MASTER switch in the upper position (labeled as “SLAVE”) changes it to a SLAVE. To install m...
Page 53 - Terminals location and conceptual connection diagram
52 • Control systems • intelligent Touch Manager • ED721208 Terminals location and conceptual connection diagram Using a LAN cable, connect the LAN socket to the network hub. <Conceptual drawing of LAN connection> A Rear face of intelligent Touch Manager B LAN cable C Hub D PC Requirements tha...
Page 54 - Connecting I/O module
53 • Control systems • intelligent Touch Manager • ED721208 Connecting I/O module The intelligent Touch Manager can be used in conjunction with the I/O module. The I/O module provides a maximum of 960 I/O points for controlling non-DAIKIN peripheral equipment such as lighting equipment and security ...
Page 58 - iTM plus adaptor body; Front face of iTM plus adaptor
57 • Control systems • intelligent Touch Manager • ED721208 3.2.1.1 Dimensions iTM plus adaptor body 149mm 120mm 136mm 68.5mm 67.5mm 52.2mm 160mm 61.2mm 61.2mm 6.5mm 6.5mm 4mm 4mm 6mm 4mm 6mm 140mm 4mm 3.2.2 Location of terminals and switches Understand the arrangement of terminals and switches on t...
Page 60 - Determining installation place
59 • Control systems • intelligent Touch Manager • ED721208 The table below shows the status of the CPU ALIVE/ALARM LED when the iTM plus adaptor is operating normally or failed. NOTE [LED status and operation table] Operating condition CPU ALIVE ALARM Normal Blink Off Hardware failure Off On Addres...
Page 62 - Connecting intelligent Touch Manager
61 • Control systems • intelligent Touch Manager • ED721208 Connecting intelligent Touch Manager The iTM plus adaptor is a device that enables you to control more air conditioners with the intelligent Touch Manager. It needs to be connected to an intelligent Touch Manager to provide this capability....
Page 70 - Installation place and mounting direction
69 • Control systems • intelligent Touch Manager • ED721208 Side face On the left side face of the iTM integrator, a USB port cover is provided. You use this cover during setup after installation or during maintenance. You also see an attached label, bearing the model, weight, power ratings and the ...
Page 72 - Removing terminal cover from rear face
71 • Control systems • intelligent Touch Manager • ED721208 3.3.4. Connections This chapter describes the procedure for connecting the iTM integrator with the intelligent Touch Manager. Required procedures • 2.3 Connecting power supply• 2.2 Connecting a LAN cable WARNING • Do not turn the power supp...
Page 75 - Function
74 • Control systems • intelligent Touch Manager • ED721208 4. Accessories 4.1. Di Unit <DEC101A51> Using this unit, connection of other facilities other than air conditioner is made possible, such as power supply facility, sanitary facility, anti-disaster facility, and crime prevention facili...
Page 76 - Part Names and Functions; Appearance
75 • Control systems • intelligent Touch Manager • ED721208 Part Names and Functions Appearance Di UnitDEC101A51 PCB in DEC101A51
Page 78 - Installation
77 • Control systems • intelligent Touch Manager • ED721208 Installation 325 Front panel screw (198) 70 (309) Mounting hole Unit (mm) Mounting hole 335 70 DEC101A51 UP (Installation Place)• Install the unit indoors where it is not exposed to water and dust or dirt.• Install the unit where both tempe...
Page 80 - Electric Wiring Work and Initial Setting; Electric wiring work
79 • Control systems • intelligent Touch Manager • ED721208 Electric Wiring Work and Initial Setting Electric wiring work × × 4 ON DS6 2 3 1 RS1 Low Group No. Set 0 DS1 High 2 4 1 3 DS3 5 DS2 8 ON 6 7 7 ON 2 DS5 3 DS4 4 6 5 8 1 M6 M3 M4 CA CM M5 A6 M2 M7 M8 A7 A4 A3 A8 M1 A5 A2 A1 TP1 2 H9P H8P H1P ...
Page 81 - Initial setting
80 • Control systems • intelligent Touch Manager • ED721208 Initial setting • DEC101A51 Switch Settings Name Operation OFF ON DS2 Abnormal input detection Open/Close (Concentrated address +4 to 7) Abnormal input detection method Open: Close (Normal) Æ Open (Abnormal)Close: Open (Normal) Æ Close (Abn...
Page 83 - Electric wiring connection; Power Supply & Earth Wiring; Wiring Procedure
82 • Control systems • intelligent Touch Manager • ED721208 Electric wiring connection Power Supply & Earth Wiring Fuse (10A) <F1/F2> wiring between this equipment and centralized control equipment is required. The connection to the facility equipment and setting of variousswitches are req...
Page 88 - The figure below shows the PC board built in this equipment.
87 • Control systems • intelligent Touch Manager • ED721208 The figure below shows the PC board built in this equipment. H4P H12P 3 ON 7 2 6 8 5 1 4 3 2 1 8 4 7 6 5 ON 1 4 2 3 ON DS6 DS2 DS3 DS4 DS5 Contact switch SS1 Con. Ins. Group No. Set DS1 High 0 RS1 Low D2 CD D3 D1 D4 CA A4 M1 A3 CM A2 A1 M4 ...
Page 92 - Electric Wiring Work
91 • Control systems • intelligent Touch Manager • ED721208 Electric Wiring Work and Initial Setting Electric Wiring Work 1 7 6 3 2 5 ON 4 8 1 7 6 3 2 5 4 1 3 2 4 8 ON ON DS6 Ins. SS1 Con. Contact switch DS5 DS4 RS1 Low DS1 High Group No. Set 0 DS2 DS3 D4 D2 D3 D1 CD Aiarm Monitor (RED)Operation Mon...
Page 93 - Factory preset before shipment
92 • Control systems • intelligent Touch Manager • ED721208 Factory preset before shipment C/C : Centralized control equipment C/D : Connectable Devices or Facility equipment Switch Condition Factory preset before shipment DS1 Range of address No. 1-00, 01, 02, 03 DS2 A1 - AM Abnormal in the open co...
Page 95 - Electric Wiring Connection
94 • Control systems • intelligent Touch Manager • ED721208 This indicates LED lighting. 1 2 3 4 DS3 DS3 DS3 DS3 Operation Monitor TP1 DS3 Setting Contents 1 Unit 2 Units 3 Units 4 Units 1 Unit 2 Units 3 Units 4 Units ON 1 2 3 4 ON 1 2 3 4 ON 1 2 3 4 ON Short circuit (with power "ON") This i...
Page 96 - Power proportional distribution; System Architecture; Confirmation of Watthour Meter; Confirm the following items for the construction process.
95 • Control systems • intelligent Touch Manager • ED721208 5. Power proportional distribution System Architecture Confirmation of Watthour Meter For distribution of electric energy, the integrating watthour meter with pulse transmitter is required.It is important to confirm that the specifications ...
Page 97 - Design Precautions; Calculation Condition; iTM
96 • Control systems • intelligent Touch Manager • ED721208 Design Precautions Calculation Condition 3 1 2 VRV Watthour meter (For VRV outdoor units) Watthour meter (For VRV indoor units) Group1 DIII-NET Remote controllergroup control iTM (1) Remote controller group ➀ Also in the indoor unit (sub-un...
Page 98 - Setting of Each Electric Power Group
97 • Control systems • intelligent Touch Manager • ED721208 Setting of Each Electric Power Group Watthour meters have to be installed for Heat Pump type VRV and Heat Recovery type VRV respectively as shown below figure and make power groups respectively. Group 1 VRVHeatPump Group 2 VRVHeatRecovery D...
Page 99 - The Reason why VRV Heat Recovery must not be Included; Not allowed with 1 unit !
98 • Control systems • intelligent Touch Manager • ED721208 The Reason why VRV Heat Recovery must not be Included For Heat Recovery outdoor units, the watthour meter must be independently installed. (1) For heat recovery, there is a case that the power consumption is less than VRV and VRV Plus.(2) H...
Page 100 - Explanations of Power Proportional Distribution; What is the Power Proportional Distribution (PPD)
99 • Control systems • intelligent Touch Manager • ED721208 Explanations of Power Proportional Distribution What is the Power Proportional Distribution (PPD) (System Ex. : Normal VRV ) Outdoor unit Power supply single phase Watthour meter with output Power supply3 phase Indoor units: a maximum of 64...
Page 102 - Count Accuracy
101 • Control systems • intelligent Touch Manager • ED721208 Count Accuracy (1) Cause of error (System example) Watthour meter (with output) Power supply 3 phase #1 #2 #3 #4 #5 #6 #: Indoor unit's address #7 #8 W2 W1 Outdoor unit Tenant A Tenant B Tenant C Legend : Read on wattmeter iTM <Case of ...
Page 104 - FXUQ
103 • Control systems • intelligent Touch Manager • ED721208 Notes • It is not possible to apportion power consumption for the VRV series indoor unit FXUQ (ceiling suspended cassette type). (Reason) VRV and SkyAir use different methods to calculate thermo step, which is a parameter necessary for pow...
Page 105 - Reference Material; Case Examples; Outdoor unit system 3
104 • Control systems • intelligent Touch Manager • ED721208 Reference Material Case Examples (1) A value on a wattmeter of each outdoor unit system does not correspond to PPD result. Electric power of wattmeter A is nearly the same as that of wattmeters B + C + D.However, the PPD result of outdoor ...
Page 106 - This setting can be configured in the field
105 • Control systems • intelligent Touch Manager • ED721208 (2) A group address is not set to a slave indoor unit with remote controller group. iTM cannot control slave indoor units (Indoor units B, D, G, and H in the following figure) in remote controller group. In general, the setting of a group ...
Page 107 - OFF OFF OFF OFF OFF OFF OFF; In the following case, power consumption of
106 • Control systems • intelligent Touch Manager • ED721208 (3) A PPD calculation result for a certain tenant is excessively large. iTM distributes electric power based on operation data from an indoor unit.If only one VRV indoor unit is in operation, electric power consumed by an outdoor unit incr...
Page 108 - Terminal Number; Just for operation with each remote controller; Detail of Outdoor Unit Terminal No.
107 • Control systems • intelligent Touch Manager • ED721208 6. Design of DIII-NET Features of DIII-NET What is DIII-NET? DIII-NET is a proprietary high-speed communication method developed by Daikin, with which huge amount of information can be transmit at high speed and various facilities of a bui...
Page 109 - Connection Method; Correct Wiring
108 • Control systems • intelligent Touch Manager • ED721208 Connection Method Correct Wiring • Series wiring method only should be used. [Example] Centralized Control Equipment VRV Outdoor unit VRV Indoor unit Connect the centralized control equipment to the outdoor-outdoor connection. Connect outd...
Page 110 - Wiring Example; Example of Control Wiring
109 • Control systems • intelligent Touch Manager • ED721208 Wiring Example Example of Control Wiring • Be sure to connect the wiring of the centralized control equipment to control wiring between outdoor units. When wiring connections are made between indoor and outdoor units, there may be cases wh...
Page 112 - Wiring Length
111 • Control systems • intelligent Touch Manager • ED721208 Wiring Length • Total length must be 2000m or less. ( The total wiring length is 1500m when shielded wire use.)• Max. length must be 1000m or less. [Example] 200m 100m Indoor unit 500m 10m 10m 200m Outdoor unit Max. length 200+10+10+500 =7...
Page 114 - Unit and Group
113 • Control systems • intelligent Touch Manager • ED721208 Unit and Group Indoor Unit and R/C No. of Group No. of Indoor Unit Indoor Unit R/C P1·P2 1 1 Indoor unit I/U I/U I/U R/C P1·P2 P1·P2 P1·P2 1 3 Outdoor Unit No. of Outdoor Unit 10HP I/U O/U I/U Refrigerant I/U F1·F2 1 18HP I/U O/U I/U Refri...
Page 115 - Number of Connectable Units
114 • Control systems • intelligent Touch Manager • ED721208 Number of Connectable Units Number of Units to be Connected [ VRV ] (Supplementary Explanation) • Up to 10 VRV outdoor units can be connected to DIII-NET. - In case of VRVII and VRVIII, an outdoor unit which consists of multiple modules is...
Page 116 - Connection of Devices other than VRV
115 • Control systems • intelligent Touch Manager • ED721208 Connection of Devices other than VRV • You can connect adaptors and other devices (SkyAir adaptor, RA adaptor, Di/Dio units, etc.), which are not VRV, to either indoor-outdoor connection or outdoor-outdoor connection. • You cannot connect ...
Page 117 - of; BMS or
116 • Control systems • Standard protocol interfaces • RTD - modbus interface Integration of RA, Sky Air, VRV, Daikin Altherma Flex and AHU in BMS or home automation systems RTD-NET › Modbus interface for monitoring and control of Sky Air, VRV, VAM and VKM RTD-10 › Advanced integration into BMS of S...
Page 118 - Overview functions
117 • Control systems • Standard protocol interfaces • RTD - modbus interface Main functions RTD-RA RTD-NET RTD-10 RTD-20 RTD-HO Dimensions H x W x D mm 80 x 80 x 37,5 100 x100 x 22 Key card + window contact Set back function Prohibit or restrict remote control functions (setpoint limitation, ...
Page 119 - of Split, Sky Air and VRV; Conc; KNX interface line-up; KNX interface for
KLIC-DD Size 90x60x35mm KLIC-DI Size 45x45x15mm Split Sky Air VRV BASIC CONTROLON/OFF Mode Auto, heat, dry, fan, cool Auto, heat, dry, fan, cool Auto, heat, dry, fan, cool Temperature Fan speed levels 3 or 5 + auto 2 or 3 2 or 3 Swing Stop or movement Stop or movement Swing or fixed posi...
Page 120 - Applied systems network; VRV network; Integrated control system for; seamless connection; between VRV, applied Systems, air handling units and BMS systems; Air handling unit network
119 • Control systems • Standard protocol interfaces • BACnet Interface Applied systems network › Interface for BMS system › Communication via BACnet protocol (connection via Ethernet) › Unlimited sitesize › Easy and fast installation › PPD data is available on BMS system (only for VRV ) BACNET / ET...
Page 121 - BACnet interface for VRV; Compatibility with leading BMS systems
120 • Control systems • Standard protocol interfaces • BACnet Interface BACnet interface for VRV Compatibility with leading BMS systems Manufacturer* Type Andover Controls Continuum ver. 1.6 1.6 Cinmetrics Sauter OPC Server Honeywell EBI V2.0 Iconix Sauter OPC Server Invensys(Sacthwell)Polar Soft Sy...
Page 123 - Communications Check Sheet; BACnet object list
122 • Control systems • Standard protocol interfaces • BACnet Interface Communications Check Sheet BACnet object list Memner number Name Object name (XXX: Air Con Logical Group Number) Object type Unit Inactive Active Text-1 Text-2 Text-3 Text-4 1 Start/stop (setting) (Note 2) Start stop command_XXX...
Page 124 - Outline of functions; Names and functions of each part
123 • Control systems • Standard protocol interfaces • BACnet Interface Function Outline of functions • This BACnet Interface enables interfacing between the VRV system and central monitoring board.• Data of up to 256 groups of air conditioner (when the option DIII board is used) are controllable by...
Page 125 - Major functions of air-conditioner devices
124 • Control systems • Standard protocol interfaces • BACnet Interface Function Major functions of air-conditioner devices Function Air-conditioning equipment Remarks VRV Inverter series Interface adapter for Sky Air series (SA Heat Pump) HRV Wiring adapter for other air-conditioners Start/stop con...
Page 126 - Wiring and Setting Procedures; System Wiring
125 • Control systems • Standard protocol interfaces • BACnet Interface Wiring and Setting Procedures System Wiring [DIII-NET master] setting Make sure to connect the unit with [DIII-NET master]. Do not remove the master central setting connector.Remove the master central setting connectors of the c...
Page 127 - External wiring
126 • Control systems • Standard protocol interfaces • BACnet Interface Wiring and Setting Procedures External wiring Everything relating with field wiring must be supplied in the field. Ethernet communication wiring DIII-NET wiring Cautions 1 Do not use multicore cables with three or more cores.2 U...
Page 128 - Open network integration
127 • Control systems • Standard protocol interfaces • LonWorks Interface VRV network Open network integration of VRV, applied systems and air handling units monitoring and control functions into LonWorks networks › Interface for Lon connection to LonWorks networks › Communication via Lon protocol (...
Page 129 - LowWorks Interface for VRV; Survey of Functions
128 • Control systems • Standard protocol interfaces • LonWorks Interface LowWorks Interface for VRV Survey of Functions Function Description Controlling items ON/OFF Command Starts/stops air conditioner operation. Operation Mode Setting Sets operation mode (heating/cooling/ventilation/auto). Temper...
Page 130 - Applicable Models
129 • Control systems • Standard protocol interfaces • LonWorks Interface Applicable Models Function Air Conditioners VRV Large Sky Air Multi Sky Air (Adapter for Sky Air) Facility A/C (Centralized control adapter) HRV RA (General purpose adapter) ON/OFF operation and monitoring ▲ ▲ ▲ ▲ ▲ ▲ A/C erro...
Page 132 - Definition of LED and switch; LED
131 • Control systems • Standard protocol interfaces • LonWorks Interface External connection diagram 10A Alive/wink Service Caution Service switch F1 F2 N L T2 T1 L0 100-240V ~ 50/60Hz F1, F2 F1, F2 Make sure the power supply is off when carrying out the following works: 1. When taking off the fron...
Page 133 - Air Conditioning; Data
132 • Control systems • Remote monitoring and maintenance • ACNSS Air Conditioning Network Service System (ACNSS) The challenge of your technical management is safeguarding in the long term optimal operation of your air conditioning system without incurring huge costs along the way. Daikin's Air Con...
Page 134 - Data transmission; ACNSS energy saving; COMFORT MAINTAINED
133 • Control systems • Remote monitoring and maintenance • ACNSS 1 Data transmission Air conditioners's running information and other necessary data are collected and compiled, and sent to the centre. Advance failure forecasts and monitoring data for accidental problems are transmitted. 3 data anal...
Page 135 - Simplified; graphical interface to; Simplified commissioning; › Less time is required on the roof configuring the
134 • Control systems • Daikin Configurator Software Simplified commissioning Retrieve initial system settings Simplified commissioning: graphical interface to configure, commission and upload system settings Simplified commissioning The Daikin configurator for Daikin Altherma and VRV is an advanced...
Page 136 - Flexible; and; easy; installation; Connection diagram; Wireless room temperature sensor
Flexible and easy installation › Accurate temperature measurement thanks to flexible placement of the sensor › No need for wiring › No need to drill holes › Ideal for refurbishment Connection diagram Daikin indoor unit PCB (FXSQ-P example) Air sensor – X16A , X19 Power supply – X35 , X13 RF SENDER R...
Page 137 - Wired room temperature sensor
› Accurate temperature measurement, thanks to flexible placement of the sensor Dimensions (HxW) mm 60 x 50 Weight g 300 Length of branch wiring m 12 Specifications Wired room temperature sensor 136 • Control systems • Sensors & other devices • KRCS01-1B / KRCS01-4B • Wired room temperature senso...
Page 138 - Concept and benefits
(E)KRP1B* adapter for wiring • Facilitates integration of auxiliary heating apparatus, humidifiers, fans, damper • Powered by and installed at the indoor unit KRP2A*/KRP4A* Wiring adapter for electrical appendices • Remotely start and stop up to 16 indoor units (1 group) (KRP2A* via P1 P2) • Remotel...