Page 2 - Thermostat Piping; Thermostat

VAV-SVX02B-EN Thermostat Selectionand Location In general, both one- and two-pipethermostats have a gain of 2.5 psi perdegree Fahrenheit, unless specialthermostats are used that provide adifferent gain. The major differencebetween them is that a one-pipethermostat is considered a low-capacity thermo...

Page 3 - Specifications; Output P

3 VAV-SVX02B-EN Thermostat Specifications TP970 Series Pneumatic T-statsMaximum Safe Air Pressure:25psi (172 kPa)Maximum Safe Air Temperature:150°F (66°C) Throttling Range:2–10°F (1–5°C) Gain:2.5 psi/°F Adjustable Operation Pneumatic thermostats modulateoutput air pressure in response to roomair tem...

Page 4 - Installation and Operation; Reversing Relay; Figure 6 – Reversing Relay Connections; PSI In

VAV-SVX02B-EN Installation and Operation The reversing relay is a proportional,non-bleeding device for use in pneu-matic control systems where a propor-tional signal from a controlling devicemust be reversed (see Figure 5). Themost common use of the reversingrelay is to change the action of apneumat...