Page 2 - One of the Equipment Series
Helical-RotaryWater Chillers One of the Equipment Series A publication ofThe Trane Company—Worldwide Applied Systems Group
Page 3 - Preface; water chillers; A Trane Air Conditioning Clinic; Helical-Rotary Water Chillers
Preface © 1999 American Standard Inc. All rights reserved TRG-TRC012-EN ii The Trane Company believes that it’s incumbent on manufacturers to serve the industry by regularly disseminating information gathered through laboratory research, testing programs and field experience. The Trane Air Condition...
Page 4 - Contents
TRG-TRC012-EN iii Contents Introduction ............................................................1 period one Components ...........................................................3 Compressor .............................................................4 Oil Separator ..............................
Page 6 - notes; Introduction; chilled water; absorption
TRG-TRC012-EN 1 notes Introduction Water chillers are used in a variety of air conditioning and process cooling applications. They are used to make cold water that can be transported throughout a facility using pumps and pipes. This cold water can be passed through the tubes of coils in order to coo...
Page 7 - helical-rotary water
2 TRG-TRC012-EN notes Introduction Water chillers using the vapor-compression refrigeration cycle vary by the type of compressor used. Reciprocating and scroll compressors are typically used in smaller chillers. Helical-rotary (or screw) compressors are typically used in medium-sized chillers. Centr...
Page 8 - Components; period one; Helical-Rotary Water Chiller
TRG-TRC012-EN 3 notes period one Components Many of the components of the helical-rotary water chiller are similar to those of other chiller types. This particular helical-rotary water chiller makes use of a shell-and-tube evaporator where refrigerant evaporates inside the shell and water flows insi...
Page 9 - Compressor; rotors; Helical Rotors
4 TRG-TRC012-EN notes period one Components Compressor The helical-rotary chiller uses 2 screw-like rotors to perform the compression process. The rotors are meshed and fit, with very close tolerances, within a housing. Only the male rotor is driven by the compressor motor. The lobes of the male rot...
Page 10 - intake port
TRG-TRC012-EN 5 period one Components notes In the operation of the helical-rotary compressor, refrigerant vapor enters the compressor housing through the intake port . The intake port in this example is at the top of the compressor housing. The entering refrigerant vapor is at a low, suction pressu...
Page 12 - ported
TRG-TRC012-EN 7 period one Components notes Continued rotation of the rotors causes the meshing point to travel toward the discharge end of the compressor, driving the trapped refrigerant vapor ahead of it. This action progressively reduces the volume of the pockets, compressing the refrigerant. Fin...
Page 13 - oil separator; Oil Separator
8 TRG-TRC012-EN notes period one Components Oil Separator The oil leaves the compressor entrained within the discharged refrigerant vapor. The oil is recovered from the discharged refrigerant by an oil separator , which can have an efficiency of greater than 99%. The separator consists of a vertical...
Page 14 - water-cooled condenser; subcooler; Condenser
TRG-TRC012-EN 9 period one Components notes operation and is, therefore, constantly moving to lower pressure areas of the chiller. In this system, oil flows in 2 distinct paths, each performing a separate function: 1) bearing lubrication and cooling and 2) rotor oil injection. Oil leaves the sump an...
Page 16 - Expansion Device; electronic expansion valve; Electronic Expansion Valve
TRG-TRC012-EN 11 period one Components notes Expansion Device An expansion device is used to maintain the pressure difference between the high-pressure (condenser) and low-pressure (evaporator) sides of the system, as established by the compressor. This pressure difference allows the evaporator temp...
Page 17 - orifice plate; Liquid/Vapor Separator; liquid/vapor separator; Orifice Plates
12 TRG-TRC012-EN notes period one Components The orifice plate is another type of expansion device found in helical-rotary chillers. The column of liquid refrigerant creates a head pressure at its base, allowing it to pass through the orifices and undergo a pressure drop equal to the head (H) before...
Page 18 - Evaporator; Flooded Evaporator
TRG-TRC012-EN 13 period one Components notes By removing the vapor portion of the mixture before it gets to the evaporator the separator enhances the effectiveness of the evaporation process. Evaporator In the flooded shell-and-tube evaporator cool, low-pressure liquid refrigerant enters the distrib...
Page 19 - direct; Direct Expansion Evaporator
14 TRG-TRC012-EN notes period one Components Another type of evaporator found in helical-rotary chillers is the direct expansion (DX) shell-and-tube evaporator . In this type of evaporator the cool, low-pressure liquid refrigerant flows through the tubes and water fills the surrounding shell. As hea...
Page 20 - Controls and Starter; control panel; starter; Controls And Starter
TRG-TRC012-EN 15 period one Components notes Controls and Starter A microprocessor-based control panel is provided on the chiller to provide accurate chilled water control as well as monitoring, protection, and adaptive limit functions. These controls monitor the chiller’s operation and prevent the ...
Page 21 - Refrigeration Cycle; Refrigeration Cycle
16 TRG-TRC012-EN notes A pressure-enthalpy (p- h ) chart illustrates the refrigeration cycle of the helical- rotary water chiller. But first, lets review the components of the helical-rotary chiller’s refrigeration cycle... Refrigerant vapor leaves the evaporator and flows to the compressor where it...
Page 22 - liquid
TRG-TRC012-EN 17 period two Refrigeration Cycle notes separated from the mixture and routed directly to the suction side of the compressor and the remaining liquid refrigerant enters the evaporator. In the evaporator, the liquid refrigerant boils as it absorbs heat from water. The resulting vapor is...
Page 24 - Refrigerants
TRG-TRC012-EN 19 period two Refrigeration Cycle notes Manufacturers are continuously improving their designs of helical-rotary water chillers. New chillers need to be designed around the characteristics of the refrigerant. Today there are 5 strong candidates for use with positive-displacement, helic...
Page 25 - Thermodynamic Characteristics
20 TRG-TRC012-EN notes period two Refrigeration Cycle Today the most commonly used refrigerant in helical-rotary chillers is HCFC-22. Due to the scheduled phaseout of HCFC-22, most helical-rotary chillers will be redesigned using HFC refrigerants. Many challenges are encountered when redesigning a c...
Page 26 - Compressor Capacity Control; slide valve; radial discharge; axial discharge; period three; Slide Valve
TRG-TRC012-EN 21 notes period three Compressor Capacity Control The capacity of the helical-rotary compressor presented in this clinic is controlled by a slide valve that is an integral part of the compressor housing. Other helical-rotary compressor designs may use a variety of methods to vary capac...
Page 27 - Full Load; Part Load
22 TRG-TRC012-EN notes period three Compressor Capacity Control At full load, the slide valve is closed. The compressor pumps its maximum volume of refrigerant, discharging it through both the radial and axial ports. At part load, the slide valve modulates toward the open position. The opening creat...
Page 28 - Unloading
TRG-TRC012-EN 23 period three Compressor Capacity Control notes As the slide valve continues to open, further unloading the compressor, its radial discharge port eventually travels past the opening in the compressor housing. Once this occurs, all of the refrigerant vapor being pumped by the compress...
Page 29 - Slide Valve Operation
24 TRG-TRC012-EN notes period three Compressor Capacity Control The slide valve is operated by a piston and cylinder assembly. Extension and retraction of the operator shaft positions the slide valve along the compressor rotors. High-pressure refrigerant vapor, controlled by 2 solenoid valves, is fe...
Page 30 - Maintenance Considerations; Maintenance Considerations; Operating log
TRG-TRC012-EN 25 notes period four Maintenance Considerations This period discusses general maintenance requirements of helical-rotary water chillers. Although some of the information applies specifically to the design presented in this clinic, requirements for other helical-rotary chiller designs a...
Page 31 - Reducing Emission of Halogenated; ASHRAE Guideline 3
26 TRG-TRC012-EN notes period four Maintenance Considerations The American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE) has published Guideline 3 titled Reducing Emission of Halogenated Refrigerants in Refrigeration and Air Conditioning Equipment and Systems . This guide...
Page 32 - Required maintenance; Mechanical Components
TRG-TRC012-EN 27 period four Maintenance Considerations notes Direct-drive, semi-hermetic compressor designs require no periodic maintenance on the compressor/motor assembly. The compressor contains only 3 main moving parts: the male and female rotors and the slide valve. The semi-hermetic motor eli...
Page 33 - Heat Transfer Surfaces; Recommended maintenance
28 TRG-TRC012-EN notes period four Maintenance Considerations Some helical-rotary compressor designs do require periodic maintenance of mechanical system components. This includes oil and refrigerant filter changes, oil strainer changes, and a compressor rotor inspection. Open-motor compressor desig...
Page 34 - Fluid Analysis; Oil analysis; Refrigerant charge
TRG-TRC012-EN 29 period four Maintenance Considerations notes determine the level of water treatment required to remove contaminants from the cooling tower water. Scale deposits are best removed by chemical means. The water-cooled condenser is commonly isolated from the rest of the cooling tower wat...
Page 35 - Why perform regular oil analyses?
30 TRG-TRC012-EN notes period four Maintenance Considerations Refrigerant analysis measures contamination levels and determines suitability for continued use. It can also determine the acceptability of recycled refrigerant for reuse. Refrigerant analysis helps extend the life of the existing charge ...
Page 36 - Application Considerations; period five
TRG-TRC012-EN 31 notes period five Application Considerations There are several considerations to address when applying helical-rotary water chillers, including: ■ Air-cooled or water-cooled condensing ■ Condensing temperature control ■ Constant or variable evaporator water flow ■ Short evaporator w...
Page 37 - Comparison
32 TRG-TRC012-EN notes period five Application Considerations is the elimination of the cooling tower. This eliminates the concerns and maintenance requirements associated with water treatment, makeup water availability and quality, tower mechanical maintenance, freeze protection, and chiller conden...
Page 38 - Condensing Temperature Control
TRG-TRC012-EN 33 period five Application Considerations notes and temperatures that the air-cooled chiller. Generally, air-cooled chillers last 15 to 20 years, while water-cooled chillers last 20 to 25 years. To summarize the comparison of air-cooled and water-cooled helical-rotary chillers, air-coo...
Page 39 - Cooling Tower Bypass
34 TRG-TRC012-EN notes period five Application Considerations Controlling the refrigerant pressure difference between the evaporator and condenser of a water-cooled chiller is accomplished by varying the temperature or flow rate of the water flowing through the condenser. The following are 5 common ...
Page 40 - Constant or Variable Evaporator Water Flow; Constant or Variable Flow; Limitations
TRG-TRC012-EN 35 period five Application Considerations notes Constant or Variable Evaporator Water Flow In previous designs, chillers were required to maintain a constant flow rate of water through the evaporator. This requirement has changed due to advances in chiller controls. Increased sensing a...
Page 41 - Short Evaporator Water Loops
36 TRG-TRC012-EN notes period five Application Considerations 1) The water flow rate through the chiller’s evaporator must stay between the minimum and maximum evaporator bundle flow rates as specified by the chiller manufacturer. These limits depend on the specific details of the actual evaporator ...
Page 43 - Equipment Certification Standards; Purpose
38 TRG-TRC012-EN notes period five Application Considerations Equipment Certification Standards The Air Conditioning & Refrigeration Institute (ARI) establishes rating standards for packaged HVAC equipment. ARI also certifies and labels equipment through programs that involve random testing of a...
Page 44 - Standard rating conditions
TRG-TRC012-EN 39 period five Application Considerations notes The standard rating conditions used for ARI certification represent typical design temperatures and flow rates for which water-cooled and air-cooled systems are designed. They are not suggestions for good design practice for a given syste...
Page 45 - Review—Period 1; period six; Review
40 TRG-TRC012-EN notes Let’s review the main concepts that were covered in this clinic on helical-rotary water chillers. In Period 1, the following components of a helical-rotary water chiller were discussed: compressor, oil separator, oil supply system, condenser, expansion device, liquid/vapor sep...
Page 46 - Review—Period 2; Review—Period 3
TRG-TRC012-EN 41 period six Review notes In Period 2, the refrigeration cycle of the helical-rotary water chiller was examined on a pressure-enthalpy chart. Also, the performance characteristics of the various refrigerants were compared. In Period 3, the operation of the modulating slide valve was e...
Page 47 - Review—Period 4; Maintenance considerations; Review—Period 5; Application considerations
42 TRG-TRC012-EN notes period six Review In Period 4, the general maintenance requirements of a helical-rotary water chiller were discussed, including: ■ Recommended data to be logged daily ■ Required and recommended maintenance of the mechanical components ■ Required and recommended maintenance of ...
Page 48 - Engineers Newsletter
TRG-TRC012-EN 43 period six Review notes For more information, refer to the following references: ■ Trane product catalogs for helical-rotary water chiller products (Trane literature order numbers RLC-DS-1, RLC-DS-2, RLC-DS-4, and RLC-DS-6) ■ Water-Cooled Series R ® Chiller—Model RTHC Mechanical Ope...
Page 49 - Quiz
44 TRG-TRC012-EN Questions for Period 1 1 What components of the helical-rotary compressor are used to compress the refrigerant? 2 What are the 2 functions of the oil supply system presented in this clinic? 3 In a flooded shell-and-tube evaporator, is the refrigerant flowing inside or outside of the...
Page 50 - Questions for Period 3; Questions for Period 4
TRG-TRC012-EN 45 Quiz Questions for Period 3 7 At full load, is the slide valve fully closed or fully open? 8 Explain how the slide valve varies the refrigerant flow rate through the helical-rotary compressor. Questions for Period 4 9 What document recommends the data points to be logged daily for e...
Page 51 - Answers
46 TRG-TRC012-EN 1 Male and female screw rotors 2 Bearing lubrication and cooling, and rotor oil injection 3 Outside of the tubes 4 Electronic expansion valve and orifice plate 5) a) compression b) condensation (desuperheat, condense, subcool) c) expansion d) evaporation 6 Point 1, the suction inlet...
Page 52 - Glossary
TRG-TRC012-EN 47 air-cooled condenser A type of condenser that rejects the heat of the refrigerant to air flowing through it. ARI Air Conditioning & Refrigeration Institute ARI Standard 550/590 A publication, titled “Standard for Water Chilling Packages Using the Vapor-Compression Cycle”, used t...
Page 54 - POSTAGE WILL BE PAID BY ADDRESSEE; POSTAGE WILL BE PAID BY ADDRESSEE
NO POSTAGENECESSARYIF MAILEDIN THEUNITED STATES BUSINESS REPLY MAIL FIRST-CLASS MAIL LA CROSSE, WI PERMIT NO. 11 POSTAGE WILL BE PAID BY ADDRESSEE THE TRANE COMPANYAttn: Applications Engineering3600 Pammel Creek RoadLa Crosse WI 54601-9985 NO POSTAGENECESSARYIF MAILEDIN THEUNITED STATES BUSINESS REP...
Page 55 - Comment Card; Response Card; Thank you for your interest!
Comment Card We want to ensure that our educational materials meet your ever-changing resource development needs. Please take a moment to comment on the effectiveness of this Air Conditioning Clinic. Give the completed card to thepresenter or drop it in the mail.Thank you! Helical-Rotary Water Chill...