Page 2 - Table of Contents
2 PTAC-SVX01C-EN Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Model Number Description . . . . . . . . . . . . . . . . . . . . . . . . . 3 General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Pre-Installation . . . . . . . . . ....
Page 3 - = Internal Condensate Pump; Model Number Description; P T E E 0 9 0 1 * A A
PTAC-SVX01C-EN 3 *All heat pump units must have electric heat. Digit 8—Main Power Supply 1 = 230-208V/60Hz/1phase 2 = 265V/60Hz/1phase 4 = 115V/60Hz/1phase (Hydronic Only) Digit 9 —Electric Heat Capacity* U = Universal Heater (Heater kW determined by power cord, see Accessories Section) W = Hydronic...
Page 4 - WARNING; General Information
General Information © 2005 American Standard Inc. All rights reserved PTAC-SVX01C-EN NOTICE: Warnings and Cautions appear in appropriate sections throughout this manual. Read these carefully. WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or serious ...
Page 6 - Checklist; Minimum unit clearance
6 PTAC-SVX01C-EN Pre-Installation Pre-Installation Considerations Before beginning installation, make the following considerations: 1. Verify the wall opening is in the correct location and the correct size. 2. Drill mounting holes on both sides of the wall sleeve, if equipment requires any of the f...
Page 7 - Receiving and Handling; Shipping Package
PTAC-SVX01C-EN 7 Pre-Installation Receiving and Handling Shipping Package The chassis and the cabinet front ship in one carton. Accessories ship separate. Receiving Checklist Complete the following checklist immediately after receiving unit shipment to detect possible shipping damage. • Verify that ...
Page 8 - Unit with wall sleeve and subbase accessory; Unit Dimensions
8 PTAC-SVX01C-EN Unit Dimensions Figure 4. Unit with wall sleeve and subbase accessory Figure 5. Wall Sleeve Unit Dimensions
Page 9 - Top view of the hydronic kit; PTAC Wall Sleeve; Front View
PTAC-SVX01C-EN 9 Unit Dimensions Figure 6. Top view of the hydronic kit Figure 7. Hydronic kit front view Figure 8. Hydronic kit side view PTAC Wall Sleeve Air discharge Unit controls compartment 1“ 20-1/4” 16-1/5” 1-1/20” 53-2/3” PTAC Air inlet Steam inlet and outlet connection (right hand coil con...
Page 10 - Installation
10 PTAC-SVX01C-EN Installation WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in hand...
Page 12 - Panel wall installation
12 PTAC-SVX01C-EN Installation Installation Procedure WARNING Hazardous Voltage w/Capacitors! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or ...
Page 13 - level from right to left; . If using an extended; Insulation strip location; Front
PTAC-SVX01C-EN 13 Installation 2. Grasping the top and bottom flanges of the rear closure panel as shown in Figure 12 , the entire panel is pulled out diagonally from one side. Step 2. Install drain kit in wall sleeve. Drain kits are available for indoor or outdoor installation to help condensate dr...
Page 16 - Indoor Temperature setpoint; COOL; Fan Speed Selection; HIGH; Field commissioning support; Manual Test Mode; Digital display module; Dehumidification
16 PTAC-SVX01C-EN Installation Notes: EN = Enabled - operations based on other logic Notes: N/C = No change from prior state Step 8. Configure the display module settings Indoor Temperature setpoint The indoor temperature setpoint buttons tell the unit how warm or cool the occupant wants the room. T...
Page 17 - Vent Door Configuration
PTAC-SVX01C-EN 17 Installation Step 9. Programmable Settings The controller has a total of six (7) parameters that are user-configurable: 1. Vent Door Configuration 2. Indoor Fan Cycle configuration 3. Temperature Setpoint Limiting configuration 4. Energy Management Setpoint Offset configuration 5. ...
Page 18 - Ventilation Door Function; Operation without configuration
18 PTAC-SVX01C-EN Installation 1. Ventilation Door Function The power door works based upon control logic functions. When the unit is on, the vent door will open to allow fresh air to be conditioned before entering the room. When the unit is off, the door closes to prevent unconditioned air from ent...
Page 19 - Occupancy States; occupied; Occupied state; Occupied Standby state
PTAC-SVX01C-EN 19 Installation Energy Management System Occupancy States The controller is designed to handle two possible occupancy states: • occupied • occupied standby When the Energy Management System input is present, it is possible for the controller to switch between the two occupancy states....
Page 21 - Sequence of Operation; Random Restart Function; Operation
PTAC-SVX01C-EN 21 Sequence of Operation Automatic 3-minute Compressor Lockout After the compressor cycles off, it will not restart for three minutes. This feature prevents the compressor from short cycling and extends the overall life. Automatic 2nd Stage Electric Heat (PTHE only) If the room temper...
Page 22 - Remote Fan Operation; CAUTION; Remove the front cabinet.; Discharge air grille; Screws
22 PTAC-SVX01C-EN Operation Notes:1. Connection to R enables input functions W, Y, GL, GH, O,VT, and/or EN. 2. Connect 24VAC, 3VA maximum Remote Fan Control Relay to RF and C Remote Fan Operation PTACs can operate a remote fan to provide conditioned air to additional rooms or areas that are not well...
Page 30 - Maintenance Procedures; procedure to reinstall the filters.; Intake air filter removal; Maintenance
30 PTAC-SVX01C-EN Maintenance Procedures Perform the following maintenance procedures to ensure proper unit operation. WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a ...
Page 31 - Scheduled Maintenance; Vent filter removal; Vent door; Micron gauge to check vacuum
PTAC-SVX01C-EN 31 Maintenance 5. Reinstall the filter by reattaching the hook to the bottom of the vent door and replacing the two screws, slide the chassis back into the wall sleeve, secure it in place with six screws and reinstall the front cabinet. Scheduled Maintenance To achieve top performance...
Page 32 - Leak Testing; Brazing
32 PTAC-SVX01C-EN Maintenance Leak Testing Refrigerant leaks are best detected with a halide or electronic leak detector. WARNING Use of Pressure Regulator – Valves – Gauges! Always use pressure regulators, valves, and gauges to control drum and line pressures when pressure testing equipment. Failur...
Page 33 - Refrigeration sealed system — heat pump (air conditioning; Evacuation
PTAC-SVX01C-EN 33 Maintenance Figure 22. Refrigeration sealed system — heat pump (air conditioning model Figure 23. Refrigeration sealed system — Heat pump (heat pump model) Evacuation CAUTION Fan Motor Overheat! Never test operation without the unit in the wall sleeve. A serious change in design sp...
Page 34 - Recheck for refrigerant leaks.; Proper placement of
34 PTAC-SVX01C-EN Maintenance 4. Start the vacuum pump and open the shut-off valve to the high vacuum gauge manifold only. After the compound gauge (low side) has dropped to approximately 29 inches of vacuum, open the valve to the vacuum thermocouple gauge. See that the vacuum pump will bank-off to ...
Page 35 - Thermometers; Record supply voltage to unit.
PTAC-SVX01C-EN 35 Maintenance Cooling Performance Test Thermometers The following precautions are necessary in observing the thermometer readings in the cooling performance test. 1. Use two accurately calibrated refrigeration type thermometers or a thermocouple potentiometer. 2. Thermometers are aff...
Page 37 - Resistance Test; Testing capacitance; Ground Test; Testing capacitor; Voltmeter; Carefully apply line voltage.; Compressor ground test
PTAC-SVX01C-EN 37 Maintenance Resistance Test 1. With no power, remove the leads from the compressor terminals. 2. Touch the leads of an ohmmeter to terminals C-S, start windings and C-R, run winding. If either winding does not test continuous, replace the compressor. Testing capacitance capacitance...
Page 40 - Indoor Fan and Motor; Outdoor Fan and Motor; Power jumper
40 PTAC-SVX01C-EN Maintenance Removing the Outdoor Coil and Outdoor Air Thermistors 1. Remove the chassis from the wall. 2. Remove the front cabinet. 3. Remove the control box cover. 4. Disconnect the outdoor coil/air thermistor wiring from the control board. 5. Gently pull outdoor coil thermistor f...
Page 41 - Diagnostics; Resetting Diagnostics; Cycling power to the controller; Manual Output Test; Troubleshooting
PTAC-SVX01C-EN 41 Diagnostics The controller is equipped to display a diagnostic code through the interface module; if the display is not present (Class 2 control), there is no method to retrieve the diagnostic codes from the unit. If there is no interface module to indicate the presence of a diagno...
Page 45 - Wiring Diagram
PTAC-SVX01C-EN 45 Figure 29. 230/208V wiring diagram (07 models) GR YL OR BK HI L N L H N BR YL LO HI N RD RD YL RD BK 1 2 3 4 5 6 7 8 3.0KW 1 2 3 4 5 6 7 8 8 7 6 5 4 3 2 1 2.0KW 6 5 4 3 21 RD BK WH YL/GR 1.0KW 2.0KW 2.0KW RD RD BK REMOTE FAN RELAY THERMOSTAT REMOTE VENTILATION INPUT DISPLAY REMOTE ...
Page 49 - Energy management system
PTAC-SVX01C-EN 49 Wiring Diagram Figure 33. Energy management system Figure 34. 3rd party class 2 thermostat wiring Figure 35. Remote display wiring R W Y GH GL O VT EN R W Y GH GL O VT EN + _ + _
Page 50 - Full 1st Year Warranty; Warranty
50 PTAC-SVX01C-EN Full 1st Year Warranty Trane will repair or replace any part which proves to be defective due to workmanship or materials, free of charge. This includes parts and labor. Full 2nd - 5th Sealed System Warranty Trane will repair or replace the evaporator, condenser, compressor, or con...