Page 2 - Introduction; It’s Hard To Stop A Trane.
© 2004 American Standard Inc. All rights reserved RT-PRC001-EN Introduction Packaged RooftopAir Conditioners Through the years, Trane has designedand developed the most complete line ofPackaged Rooftop products available inthe market today. Trane was the first tointroduce the Micro—microelectronic u...
Page 3 - Contents; Model Number Description
3 Contents RT-PRC001-EN Introduction Features and Benefits Application Considerations Selection Procedure Model Number Description General Data Performance Data Cooling PerformanceFan PerformanceHeat Performance Controls Electric Power Dimension and Weights Mechanical Specifications 2 4 10 11 13 14 ...
Page 5 - Quality and Reliability; —prevents the unit from short cycling,; ReliaTel Makes Testing Easy; ReliaTelTM
5 RT-PRC001-EN Features andBenefits Easy to Install, Service andMaintain Because today’s owners are very cost-conscious when it comes to service andmaintenance, the Trane Voyager wasdesigned with direct input from servicecontractors. This valuable informationhelped to design a product that would get...
Page 6 - Drum and Tube Heat Exchanger
RT-PRC001-EN 6 Features andBenefits Drum and Tube Heat Exchanger • The heat exchanger is manufacturedusing aluminized steel with stainlesssteel components for maximumdurability. The requirement for cycletesting of heat exchangers is 10,000cycles by ANSI Z21.47. This is thestandard required by both U...
Page 8 - Rigorous Testing; VariTracTM
RT-PRC001-EN 8 Reference or Comparative Enthalpy Measures and communicates humiditywhile maximizing comfort control. Sloped Drain Pans Standard on every unit. Standardized Components Components are placed in the samelocation on all Voyager units. Familiarizeyourself with one Voyager and you arefamil...
Page 12 - Dehumidification Selection; supply airflow
RT-PRC001-EN 12 SelectionProcedure Dehumidification Selection Determine normal unit cooling andheating capacities as previouslydescribed in the selection procedures onprior page. Typical 20 ton YFD241C6400 cfm Total Supply airflow2560 cfm Outside Air (40%)3840 cfm Return Air1.00” External Static Pre...
Page 13 - Packaged Gas/Electric Unit Typical Model Nomenclature; YF = With Factory Installed Options
13 RT-PRC001-EN Digit 8 - Electrical Characteristics 3 = 208-230/60/34 = 460/60/3W = 575/60/3K = 380/60/3 Digit 9 - Heating Capacity L = Low HeatM = Medium HeatH = High Heat Digit 10 - Factory-Installed Options 0 = Packed Stock, No OptionsA = Downflow EconomizerB = Oversized MotorC = Downflow Econom...
Page 14 - General Data; Table GD-1 — General Data; Standard Efficiency
RT-PRC001-EN 14 General Data Table GD-1 — General Data 12½ Ton Downflow and Horizontal Units 15 Ton Downflow and Horizontal Units YC*150D3,D4,DWL, DK YC*150D3,D4,DWH, DK YC*180B3,B4,BWL, BK YC*180B3,B4,BWH, BK Cooling Performance 1 Gross Cooling Capacity 150,000 182,000 EER 2 (Downflow/Horizontal) 9...
Page 15 - Table GD-2 — General Data
15 RT-PRC001-EN General Data Table GD-2 — General Data 17½ Ton Downflow and Horizontal Units 20 Ton Downflow and Horizontal Units YC*210C3,C4,CWL, CK YC*210C3,C4,CWH, CK YC*240B3,B4,BWL, BK YC*240B3,B4,BWH, BK Cooling Performance 1 Gross Cooling Capacity 210,000 242,000 EER 2 9.6 9.5 Nominal CFM / A...
Page 16 - Table GD-3 — General Data
RT-PRC001-EN 16 General Data (25 Ton) Standard Efficiency Table GD-3 — General Data 25 Ton Downflow and Horizontal Units YC*300B3,B4,BWL, BK YC*300B3,B4,BWH, BK Cooling Performance 1 Gross Cooling Capacity 290,000 EER 2 9.7 Nominal CFM / ARI Rated CFM 10,000 / 8,750 ARI Net Cooling Capacity 272,000 ...
Page 17 - Table GD-4 — General Data; High Efficiency
17 RT-PRC001-EN General Data Table GD-4 — General Data 12½ Ton Downflow and Horizontal Units 15 Ton Downflow and Horizontal Units YC*151C3,C4,CW YC*181C3,C4,CW Cooling Performance 1 Gross Cooling Capacity 154,000 189,000 EER 2 11.30 10 11.50 9 Nominal CFM / ARI Rated CFM 5,000 / 4400 6,000 / 5,300 A...
Page 18 - Table GD-4 — Continued
RT-PRC001-EN 18 Table GD-4 — Continued 12½ Ton Downflow and Horizontal Units 15 Ton Downflow and Horizontal Units YC*151C3,C4,CW YC*181C3,C4,CW Filters - Type Furnished 8 Throwaway Throwaway (No.) Size Recommended Downflow (2)20 X 20 X 2/(4)20 X 25 X 2 (4)20 X 20 X 2/(4)20 X 25 X 2 Horizontal (2)20 ...
Page 19 - Table GD-5 — General Data
19 RT-PRC001-EN General Data Table GD-5 — General Data 17½ Ton 20 Ton 25 Ton Units Downflow and Horizontal Units Downflow and Horizontal Units Downflow and Horizontal Units YC*211C3,C4,CW YC*241C3,C4,CW YC*301C3,C4,CW Cooling Performance 1 Gross Cooling Capacity 220,000 268,000 9 300,000 EER 2 11.0 ...
Page 20 - Table GD-5 — Continued
RT-PRC001-EN 20 General Data (17½, 20, 25 Ton) High Efficiency Table GD-5 — Continued 17½ Ton 20 Ton 25 Ton Units Downflow and Horizontal Units Downflow and Horizontal Units Downflow and Horizontal Units YC*211C3,C4,CW YC*241C3,C4,CW YC*301C3,C4,CW Filters - Type Furnished 8 Throwaway Throwaway Thro...
Page 21 - Table PD-1 — Gross Cooling Capacities (MBH) 121⁄2 Ton Three Phase YC
21 RT-PRC001-EN PerformanceData (12½ Ton)Standard Efficiency Table PD-1 — Gross Cooling Capacities (MBH) 12½ Ton Three Phase YC * 150D3, D4, DW, DK Ambient Temperature 85 95 105 115 EnterDry Entering Wet Bulb CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MB...
Page 22 - Table PD-2 — Gross Cooling Capacities (MBH) 15 Ton Three Phase YC; Table PD-3 — Gross Cooling Capacities (MBH) 171⁄2 Ton Three Phase YC
RT-PRC001-EN 22 PerformanceData (15, 17½ Ton)Standard Efficiency Table PD-2 — Gross Cooling Capacities (MBH) 15 Ton Three Phase YC * 180B3, B4, BW, BK Ambient Temperature 85 95 105 115 Enter.Dry Entering Wet Bulb CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) MBH SHC MBH SHC MBH SHC MBH SH...
Page 23 - Table PD-4 — Gross Cooling Capacities (MBH) 20 Ton Three Phase YC; Table PD-5— Gross Cooling Capacities (MBH) 25 Ton Three Phase YC
23 RT-PRC001-EN PerformanceData (20, 25 Ton)Standard Efficiency Table PD-4 — Gross Cooling Capacities (MBH) 20 Ton Three Phase YC * 240B3, B4, BW, BK Ambient Temperature (F) 85 95 105 115 Enter.Dry Entering Wet Bulb (F) CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) MBH SHC MBH SHC MBH SHC...
Page 24 - Table PD-6 — Gross Cooling Capacities (MBH) 121⁄2 Ton Three Phase YC
RT-PRC001-EN 24 PerformanceData (12½ Ton)High Efficiency * Indicates both downflow and horizontal units. Table PD-6 — Gross Cooling Capacities (MBH) 12½ Ton Three Phase YC * 151C3, C4, CW— Standard Refrigeration System Ambient Temperature 85 95 105 115 EnterDry Entering Wet Bulb CFM Bulb 61 67 73 61...
Page 31 - Table PD-17 — Evaporator Fan Performance — 121⁄2 Ton— YC*150D — Continued; Table PD-17 — Evaporator Fan Performance — 121⁄2 Ton — YC*150D
31 RT-PRC001-EN PerformanceData (12½ Ton)Standard Efficiency Factory supplied motors, in commercial equipment, aredefinite purpose motors, specifically designed and tested tooperate reliably and continuously at all cataloged conditions.Using the full horsepower range of our fan motors as shown inour...
Page 32 - Table PD-18 — Evaporator Fan Performance — 15 Ton — YC*180B; Table PD-18 — Evaporator Fan Performance — 15 Ton— YC*180B — Continued
RT-PRC001-EN 32 (15 Ton)Standard Efficiency PerformanceData * Indicates both downflow and horizontal units. Table PD-18 — Evaporator Fan Performance — 15 Ton — YC*180B External Static Pressure (Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM ...
Page 33 - Table PD-19 — Evaporator Fan Performance — 171⁄2 Ton— YC*210C — Continued; Table PD-19 — Evaporator Fan Performance — 171⁄2 Ton — YC*210C
33 RT-PRC001-EN * Indicates both downflow and horizontal units. PerformanceData (17½ Ton)Standard Efficiency For Standard Evaporator Fan Speed (RPM), reference Table PD-31.For Oversize Evaporator Fan Speed (RPM), reference Table PD-33.For Standard Motor and Low Static Drive, reference Table PD-34.Fa...
Page 34 - Table PD-20 — Evaporator Fan Performance — 20 Ton— YC*240B — Continued; Table PD-20 — Evaporator Fan Performance — 20 Ton — YC*240B
RT-PRC001-EN 34 * Indicates both downflow and horizontal units. PerformanceData (20 Ton)Standard Efficiency Factory supplied motors, in commercial equipment, aredefinite purpose motors, specifically designed and tested tooperate reliably and continuously at all cataloged conditions.Using the full ho...
Page 35 - Table PD-21— Evaporator Fan Performance — 25 Ton — YC*300B; Table PD-21 — Evaporator Fan Performance — 25 Ton — YC*300B — Continued
35 RT-PRC001-EN PerformanceData (25 Ton)Standard Efficiency * Indicates both downflow and horizontal units. Table PD-21— Evaporator Fan Performance — 25 Ton — YC*300B External Static Pressure (Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM B...
Page 37 - Table PD-24 — Evaporator Fan Performance — 121⁄2 Ton— YCH151C — Continued
37 RT-PRC001-EN PerformanceData (12½ Ton)High Efficiency Factory supplied motors, in commercial equipment, aredefinite purpose motors, specifically designed and tested tooperate reliably and continuously at all cataloged conditions.Using the full horsepower range of our fan motors as shown inour tab...
Page 38 - Table PD-25 — Evaporator Fan Performance — 15 Ton— YC*181C — Continued; Table PD-26 — Evaporator Fan Performance — 15 Ton— Y*D181C — Continued
RT-PRC001-EN 38 (15 Ton)High Efficiency PerformanceData For Standard Evaporator Fan Speed (RPM), reference Table PD-31.For Standard Motor and High Static Drive (RPM), reference Table PD-32.For Oversize Evaporator Fan Speed (RPM), reference Table PD-33.Data includes pressure drop due to filters and w...
Page 39 - Table PD-27 — Evaporator Fan Performance — 171⁄2 Ton— YC*211C — Continued
39 RT-PRC001-EN (17½ Ton)High Efficiency PerformanceData * Indicates both downflow and horizontal units. Table PD-27— Evaporator Fan Performance — 17½ Ton — YC*211C— Standard or TXV Refrigeration System External Static Pressure (Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP R...
Page 40 - Table PD-29— Evaporator Fan Performance — 20 Ton— Y*D241C — Continued
RT-PRC001-EN 40 PerformanceData (20 Ton)High Efficiency Factory supplied motors, in commercial equipment, aredefinite purpose motors, specifically designed and tested tooperate reliably and continuously at all cataloged conditions.Using the full horsepower range of our fan motors as shown inour tabu...
Page 41 - Table PD-30— Evaporator Fan Performance — 25 Ton — YC*301C— Continued
41 RT-PRC001-EN * Indicates both downflow and horizontal units. (25 Ton)High Efficiency PerformanceData Table PD-30 — Evaporator Fan Performance — 25 Ton — YC*301C— Standard Refrigeration or TXV System External Static Pressure (Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RP...
Page 42 - Table PD-34 — Low Static Fan Drive
RT-PRC001-EN 42 * Indicates both downflow and horizontal units. Table PD-31— Standard Motor & Drive/Fan Speed (Rpm) Unit 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn Tons Model No. Open Open Open Open Open Open Closed YC*150D3,4,W, YC*151C3,4,W 640 680 720 760 800 840 N/A 12½ YC*150DK 705 756 ...
Page 43 - Table PD-35 — Gas-Fired Heating Capacities
43 RT-PRC001-EN Table PD-35 — Gas-Fired Heating Capacities Unit Heating Heating Air Temp. Tons Model No. Input MBH Output MBH Rise, F YC*150D-L1 , YC*151C-L1 150/100 122/81 10-40 12½ YC*150D-H1,YC*151C-H1 250/175 203/142 25-55 YC*180B-L1 250/175 203/142 25-55 15 YC*180B-H1,YC*181C-H1 350/250 284/203...
Page 45 - Table PD-37— Hot Gas Reheat Temperature Rise
45 RT-PRC001-EN Table PD-37— Hot Gas Reheat Temperature Rise 2,3 Leaving Evaporator Dry Bulb [F] 1 Tons SCFM 35 40 45 50 55 60 65 2500 23.4 23.8 25.0 26.9 29.5 32.9 37.0 3000 21.4 21.6 22.5 24.0 26.0 28.7 31.9 3500 19.5 19.7 20.4 21.5 23.1 25.2 27.7 12½ 4000 17.8 18.1 18.6 19.6 20.9 22.5 24.5 4500 1...
Page 46 - Controls; Field Installed Control Options; Zone Sensors
RT-PRC001-EN 46 Controls Field Installed Control Options Zone Sensors Zone sensors are the building occupant’scomfort control devices. They replace theconventional electro-mechanicalthermostats. The following zone sensoroptions are available for Voyager unitswith the ReliaTel™ control: Manual Change...
Page 48 - Standard Refrigeration System
RT-PRC001-EN 48 * Indicates both downflow and horizontal units. (High Efficiency) ElectricalData Table ED-5— Electrical Characteristics — Compressor Motor And Condenser Motor — 60 Cycle — Dehumidification (Hot Gas Reheat) Option (Downflow Only) Compressor Motor Condenser Fan Motors Unit Amps 1 Amps ...
Page 49 - Table ED-6 — Unit Wiring - Standard Efficiency
49 RT-PRC001-EN Table ED-6 — Unit Wiring - Standard Efficiency Standard Indoor Fan Motor Oversize Indoor Fan Motor Unit Minimum Maximum Fuse Minimum Maximum Fuse Unit Operating Circuit Size or Maximum Circuit Size or Maximum Tons Model No. Voltage Range Ampacity 2 Circuit Breaker 1 Ampacity 2 Circui...
Page 58 - All dimensions are in inches.; Downflow Unit Clearance
RT-PRC001-EN 58 12½, 15, 17½ Ton (Standard Efficiency) All dimensions are in inches. RETURN SUPPLY 1 1/2" PERIMETERCURB FLANGE 14 1/16" 1" 1" 1" 1 13/16" 7 7/16" 2" 66 5/8" 63" 55 1/2" 20 7/8" 17 1/8" 28 1/2" 102 1/4" 101 7/8" 7 1/2"...
Page 59 - Downflow Duct Connections — Field Fabricated; down inside the
59 RT-PRC001-EN 12½, 15, 17½ Ton (Standard Efficiency) All dimensions are in inches. Downflow Duct Connections — Field Fabricated Horizontal Unit Supply/Return and UnitClearance RETURN SUPPLY 1 1\2"PERIMETERCURB FLANGE 59 7/16" 17 7/8" 26 5/16" 52 1/2" 1" 14 1/16" 7 7/16&...
Page 66 - Weights
RT-PRC001-EN 66 Table W-1 — Accessory Net Weights (Lbs) 1,2 Oversize LPG All High 4 Low 4 Unit Economizer Outside Air Damper Roof 3 Motor Conversion Zone Power 3 Static Static Model No. Net Motorized Manual Curb Adder Kit Sensors Exhaust Drive Drive YCD150D,151CYCD180B,210C 65 60 32 205 5 5 1 95 2 2...
Page 68 - inch high
RT-PRC001-EN 68 MechanicalSpecifications General The units shall be dedicated downflow orhorizontal airflow. The operating rangeshall be between 115°F and 0°F in coolingas standard from the factory for all units.Cooling performance shall be rated inaccordance with ARI testing procedures.All units sh...
Page 69 - Factory Installed Options; The disconnect switch will be sized
69 RT-PRC001-EN MechanicalSpecifications Controls Unit shall be completely factory wiredwith necessary controls and contactorpressure lugs or terminal block for powerwiring. Unit shall provide an externallocation for mounting a fused disconnectdevice. ReliaTel controls shall be providedfor all 24 vo...
Page 71 - Field Installed Options
71 RT-PRC001-EN Field Installed Options CO 2 Sensing The CO 2 sensor has the ability to monitor space occupancy levels within thebuilding by measuring the parts permillion of CO 2 (Carbon Dioxide) in the air. As the CO 2 levels increase, the outside air damper modulates to meet the CO 2 space ventil...