Page 2 - General information; Foreword; Reception; Reception in France only:
General information CG-SVU02B-E4 2 Foreword These instructions are given as aguide to good practice in theinstallation, start-up, operation, andmaintenance by the user, of TraneCH530 chiller control system onCGWN/CCUN and CGAN 209-214chillers. They do not contain fullservice procedures necessary for...
Page 3 - Warranty
General information 3 CG-SVU02B-E4 Warranty Warranty is based on the generalterms and conditions of themanufacturer. The warranty is voidif the equipment is repaired ormodified without the writtenapproval of the manufacturer, if theoperating limits are exceeded or ifthe control system or the electri...
Page 4 - Contents; General Information; Display Screens; TechView Interface; Software Download; Diagnostics
Contents CG-SVU02B-E4 4 General Information 2 Overview 5 DynaView Interface 6 Display Screens 6 TechView Interface 19 Software Download 20 Diagnostics 22
Page 5 - Overview; communication interface to; Controls Interface; TechView
Overview 5 CG-SVU02B-E4 The Trane CH530 control systemthat runs the chiller consists ofseveral elements:• The main processor collectsdata, status, and diagnosticinformation and communicatescommands to the LLID (for Low Level Intelligent Device) bus. Themain processor has an integraldisplay (DynaView...
Page 6 - DynaView Interface; Radio Buttons
DynaView Interface CG-SVU02B-E4 6 The display on DynaView is a1/4 VGA display with a resistivetouch screen and an LED backlight.The display area is approximately4 inches wide by 3 inches high(102mm x 60mm). CAUTION! Equipment Damage! Puttingexcessive pressure on the touchscreen could cause damage. I...
Page 8 - Main Screens; Auto
DynaView Interface CG-SVU02B-E4 8 Main Screens The Main screen shall be the defaultscreen. After an idle time of30 minutes the CH530 shall displaythe Main screen with the first datafields. The remaining items (listed inthe following table) will be viewedby selecting the up/down arrowicons. Figure 3 ...
Page 16 - Reports Screen
DynaView Interface CG-SVU02B-E4 16 Figure 6 - Reports screen Table 3 - Reports screen Description Units Resolution Evaporator Evap Entering Water Temp Temperature + or -XXX.X Evap Leaving Water Temp Temperature + or -XXX.X Evap Water Flow Switch Status (Flow, No Flow) Circuit Evaporator Evap Sat Rfg...
Page 18 - Settings Screen
DynaView Interface CG-SVU02B-E4 18 Settings Screen The Settings screen provides a userthe ability to adjust settings justifiedto support daily tasks. The layoutprovides a list of sub-menus,organized by typical subsystem.This organization allows eachsubscreen to be shorter in lengthwhich should impro...
Page 20 - Diagnostics Screen
DynaView Interface CG-SVU02B-E4 20 Diagnostics Screen The diagnostic screen is accessibleby depressing the Alarmsenunciator A scrollable list of thelast (up to 20) active diagnostics willbe presented. Performing a Reset All ActiveDiagnostics will reset all activediagnostics regardless of type,machin...
Page 35 - Notes