Page 2 - Single Packaged Convertible Gas/Electric System
2 It's Hard to Stop a Trane. Single Packaged Convertible Gas/Electric System Trane offers a complete family of packaged gas/electric heating and cooling sys-tems, designed to give you the unbeatable combination of energy efficiency andlower operating costs. In warm weather, the packaged gas/electric...
Page 3 - Contents
3 Contents Optional Equipment Listing 4 General Data 5 Performance Data Cooling 9 Indoor Fan 11 Typical Wiring 15 Optional Equipment 18 Dimensional Data 23 Mechanical Specifications 29
Page 4 - Optional Equipment Listing
4 Optional Equipment Listing OPTIONAL EQUIPMENT FOR PACKAGED UNITS (check mark [ ✓ ✓ ✓ ✓ ✓ ] indicates accessories included) Hinged Filter Access Door (4YCY4024-036) 8 ................................................................ BAYACCDOR1A[ ] Hinged Filter Access Door (4YCY4042-060) 8 ............
Page 5 - General Data
5 MODELRATED Volts/PH/HzPerformance Cooling BTUH j Indoor Airflow (CFM)Power Input (KW)EER/SEER(BTU/Watt-Hr.) n Sound Power Rating [dB(A)] 8 Performance Heating k Input BTUH - 1st Stage (Natural Gas) p Input BTUH - 2nd Stage (Natural Gas) p AFUETemp. Rise — Min/Max ( ° F) Orifice Qty / Drill Size (N...
Page 9 - Performance Data Cooling
9 Performance Data Cooling 4YCY4036A1/3 AT 1200 NOM CFM (COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES) OD ID TOT SENS CAP AT ENTERING DB TEMP TOTAL AMB WB CAP 72 75 78 80 KW 85 59 34.5 28.8 32.4 34.5 34.5 2.7 63 36.0 23.4 27.0 30.5 32.9 2.7 67 38.8 18.5 22.0 25.6 27.9 2.8 71 41.9 13.5 17.1 20...
Page 11 - Indoor Blower Performance
11 Indoor Blower Performance Indoor Fan Performance 4YCY4024A Down Airflow Horizontal Airflow 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 Watts 52 66 89 115 140 164 186 206 229 259 300 CFM 706 716 727 733 731 719 700 679 662 659 682 Watts - 94 120 148 177 207 233 254 267 290 320 CFM - 793 805 813 813 80...
Page 15 - Typical Field Wiring
15 Typical Field Wiring C 757192i2 BG Y W1W2 R COMMONFAN COMPRESSORHEAT FIRST STAGEHEAT SECOND STAGE 24V UNIT CONTROL BOX GROUNDWIRE 3 PHPOWERUNITNOTE 1 1 PHPOWER BG Y W1W2 R COMMONFAN COMPRESSORHEAT FIRST STAGEHEAT SECOND STAGE 24V B G Y W1 W2 R (GR) (WH) (WH) (GR) (WH) (WH) (GR) (WH) (WH)
Page 16 - Typical Wiring
Page 18 - Optional Equipment
18 Optional Equipment BAYCURB050A Full Perimeter Roof Mounting Curb for *****018-036A 46 3/8 17 7/8 3 3 5/8 19 1/2 2 3/16 19 1/2 14 1 1/2 38 7/8 15 35 7/8 43 3/8 The drawings on this page are prepared by themanufacturer in order to provide detail regardingjob layout only. These drawings are not inte...
Page 20 - BAYACCDOR1A & BAYACCDOR2A Hinged Filter Access Door
20 Optional Equipment The drawings on this page are prepared by the manufacturer in order to provide detail regarding job layout only. These drawingsare not intended to be used as a basis to construct, build or modify the items depicted in the drawings. The manufacturer is notresponsible for the una...
Page 22 - (Mounts Over Horizontal Return AIr Opening)
22 A B C D FULLYOPEN 2/3 1/3 FULLYCLOSED BAYDMPR101,102A, 25% Motorized Outside Air Damper (Mounts Over Horizontal Return AIr Opening) BAYOSAH001,002A, 25% Outside Air Damper (Replaces Filter/Coil Access Panel) Optional Equipment The drawings on this page are preparedby the manufacturer in order to ...
Page 23 - Dimensional Data
23 Dimensional Data 4YCY4024A through 4YCY4036A (1 of 3)
Page 29 - Mechanical Specifications
29 Mechanical Specifications General All units shall be factory assembled, piped,internally wired and fully charged withrefrigerant. All units shall be designed tooperate at outdoor ambient temperaturesas high as 115°F. Cooling capacities shallbe rated in accordance with A.R.I.standards. The 4YCY4 h...