22-1754-17 3 Contents Features and Benefits 2 General Data 4 Product Specifications 4 A-weighted Sound Power Level [dB(A)] 4 Accessory Description and Usage 5 AHRI Standard Capacity Rating Conditions 5 Model Nomenclature 6 Electrical Data 7 Dimensions 10Mechanical Specifications 11
4 22-1754-17 Product Specifications Model No. 1 4TWX6024E1 4TWX6036E1 4TWX6048E1 4TWX6060E1 Electrical Data V/Ph/Hz 2 230/1/60 230/1/60 230/1/60 230/1/60 Min Cir Ampacity 14 22 28 39 Max Fuse Size (Amps) 20 35 45 60 Compressor CLIMATUFF ® - SCROLL CLIMATUFF ® - SCROLL CLIMATUFF ® - SCROLL CLIMATUFF ...
22-1754-17 5 General Data AHRI Standard Capacity Rating Conditions AHRI STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F DB, 67°F WB air entering indoor coil, 95°F DB air entering outdoor coil. (B) High Temperature Heating 47°F DB, 43°F WB air entering outdoor coil, 70°F DB air entering indoor ...