Summary
© 2002 American Standard Inc. All Rights Reserved 18-BC51D3-2 Installer’s Guide ture to prevent excess roof run-off water from pouringdirectly on the unit. Do not locate unit(s) close tobedroom(s). 4. The top discharge area must be unrestricted for at least five (5) feet above the unit. 5. When the ...
18-BC51D3-2 3 Installer’s Guide b. Isolation hangers should also be used when refriger- ant lines are run in stud spaces or enclosed ceilings. c. Where the refrigerant lines run through a wall or sill, they should be insulated and isolated. d. Isolate the lines from all ductwork. E. SERVICE VALVE OP...
4 18-BC51D3-2 Installer’s Guide 3. Attach center hose of manifold gauges to vacuum pump. 4. Evacuate until the micron gauge reads no higher than 350 microns. 5. Close off valve to vacuum pump and observe the micron gauge. If gauge pressure rises above 500 microns in one(1) minute, then evacuation is...