Page 2 - ICTORY; II; VHS Models; Natural
V ICTORY II VHS Models NOTE: Height dimensions increase by 1 3 ⁄ 4 " and depth increases to 22 1 ⁄ 4 " when combustible floor kit is used. Natural #49 50 50 50 51 51 51 52 52 52 Propane #57 58 59 59 60 60 61 62 63 63 VHS-30 30,000 2 8 1 ⁄ 8 " 14 5 ⁄ 8 " 190 VHS-60 60,000 3 11 1 ⁄ 8 &...
Page 6 - ProTech FasNSeal System
V ICTORY II VHS Models Heat-Fab Saf-T Vent System BoilerModel No. MinimumLength, Ft. 0 to5500 Ft.Altitudes 5500 to7000 Ft.Altitudes 7000 to10,000 Ft.Altitudes EquivalentLength ofeach 90°Elbow, Ft. Max. Equivalent Length (Ft.) VHS-30, 40 40 40 3 2 60, 90and 120 VHS-150 40 40 20 3 2 VHS-180 40 20 20 3...
Page 7 - Figure 6
V ICTORY II VHS Models Figure 6 Figure 5 VICTORY II HORIZONTAL (SIDEWALL) VENTING All joints must be liquid and pressure tight. Use U/L listed single wall 3" dia. AL29-4C* S.S. venting materials * Definition of Snow Line: Knowledge of local conditions will reveal the maximum height that repeated...
Page 11 - Natural Draft Chimney and Type “B” Venting Tables
V ICTORY II VHS Models Table 1. Masonry Vitreous Tile-Lined Chimney (not metal lined) Chimneys not exposed to the outdoors below the roof line. (5" dia. vent adapter must be used) Natural Draft Chimney and Type “B” Venting Tables Additional National Fuel Gas Code Boiler Gas Appliance Reference T...
Page 14 - GAS PIPING; DANGER; Thermostat Connections
V ICTORY II VHS Models 14 VENTING SYSTEM REGULAR INSPECTION A. Inspect the system regularly for condensation, corrosion and/or physical damage. A qualified professional should ser-vice the boiler annually and include such an inspection at thattime. The homeowner should look over the system monthly f...
Page 15 - Victory; Air Control System
V ICTORY II VHS Models Figure 11a. Figure 11b. WATER PIPING Always follow good piping practices. Observe minimum 1"clearance to combustibles around all uninsulated hot waterpipes or when openings around pipes are not protected bynon-combustible materials. On a hot water boiler installed above ra...
Page 17 - Figure 15. Piping Arrangement
V ICTORY II VHS Models Figure 14. Figure 15. Piping Arrangement 17
Page 18 - Boiler Water Content
V ICTORY II VHS Models 18 An automatic air vent is used to remove air from the sys-tem. It should be installed in the top of the boiler as shownin Figure 15. If system pressure needs further control, addan additional tank in parallel with original tank or install alarger capacity tank. Use appropria...
Page 20 - Boiler rated input in; Gas Rate Table
V ICTORY II VHS Models The gas metered in 3 minutes to obtain rated input for each boiler model, using 1000 Btu/cu. ft. gas, is tabu-lated in gas rate table. B. Main Burners 1. Fire the boiler continuously for at least 15 minutes, to reach burner operating temperature. 2. Observe the flames, all bur...
Page 21 - If the boiler is vented horizontally through the wall,
V ICTORY II VHS Models 1. High Limit Control Test Set thermostat high enough for water temperature toreach high limit control setting of Aquastat. When thistemperature is reached, the high limit switch should openand the main gas valve should close automatically. 2. Gas Control Safety Shutdown Test ...
Page 24 - General Troubleshooting Guide For Servicepeople
V ICTORY II VHS Models BURNERS FAIL TO OPERATECAUSE REMEDY 1. Gas supply valve shut off 1. Open gas valve 2. No power, main electric switch open 2. Close switch 3. No power, blown or defective line fuse 3. Replace fuse 4. Pilot flame too low 4. Adjust pilot flame 5. Flame sensor contaminated 5. Clea...
Page 25 - IF REPLACEMENT PARTS ARE NEEDED; replacement
V ICTORY II VHS Models 25 DELAYED IGNITIONCAUSE REMEDY 1. Pilot flame too low 1. Adjust pilot flame 2. Excessive primary air 2. Adjust primary air shutter 3. Excessive burner input 3. Check and reduce to input shown on rating plate NOT ENOUGH HEATCAUSE REMEDY 1. Thermostat setting is too low 1. Set ...
Page 26 - III
V ICTORY II VHS Models 26 APPENDIX A Vent System Location and Condensation Drain Requirements 1. The venting system shall terminate at least 3 feet above any forced air inlet located within 10 feet. 2. The venting system shall terminate at least 4 feet below, 4 feet horizontally from, or 1 foot abov...