Page 2 - Bonding and Grounding Hazard; Hazardous Voltage & Shock Hazard
• Only qualified licensed electricians should install or service SPDs • Hazardous voltages exist within SPDs • SPDs should never be installed or serviced when energized • Use appropriate safety precautions including Personal Protection Equipment • Failure to follow these instructions can result in d...
Page 3 - Table of Contents; Tables
Table of Contents FAIluRe To FolloW THeSe INSTRucTIoNS coulD ReSulT IN DeATH oR SeRIouS INjuRy .............................. 2 Do Not Hi-Pot Test SPDs .......................................................................................................................................................
Page 4 - Introduction; Do Not Hi-Pot Test SPDs
Introduction Thank you for choosing Siemens TPS3 Surge Protective Device (SPD). This is a high quality, high energy surge suppressor designed to protect sensitive equipment from damaging transient overvoltages. Proper installation is important to maximize performance. Please follow the steps outline...
Page 5 - General Information; Type 1 –
2008 Nec Art 285 & ul 1449-3 SPD Types: Types 1, 2, 3, & 4 Based on Location within electrical distribution system (also coincides with ANSI/IEEE C62.41.2 - 2002 Categories C, B &A) Figure 1: SPD Types General Information Product Family Outline TPS3 12 – Single Module in enclosureTPS3 15...
Page 6 - Figure 1; Figure 2; Figure 3
TPS SERIES DESCRIPTION TPS3 12 Externally mounted SPD, single module in enclosure, standard modes of protection TPS3 L12 Externally mounted SPD, single module in enclosure, 10 modes of protection TPS3 15 Externally mounted SPD, dual replaceable modules in enclosure, standard modes of protection TPS3...
Page 7 - Pre-Installation and Planning
Parallel Connection This is a Parallel connected SPD – not series connected. As outlined previously, an SPD ‘drains off’ excessive voltage from an electrical system. Because of parallel connection, installation of the SPD reasonably near the equipment to be protected is satisfactory. Tip: It is very...
Page 8 - Pullbox & Flush mount
Table 2: Weight & Dimensions TPS3 12 H/W/D (in./mm.) Weight Standard Enclosure 12" x12" x 7.5"(305x305x191) 22 lbs(10 kg) Standard Enclosure, 400 – 500kA with Opt. Disc. Switch 16" x 14" x 6"(496x356x152) 32 lbs(14.5 kg) 4X Non-Metallic 14" x 12" x 7"(356x305x...
Page 10 - Mount SPD
Optional Flush Mount Installation Considerations The TPS3 12 and TPS3 15 are approximately 6” deep. The unit will not mount flush unless there is at least 6” of depth clearance. The TPS3 12 and TPS3 15 are not designed to mount flush on a typical 2 x 4 stud wall. Back Flange Mounting: Mount as close...
Page 11 - TPS3 12 and TPS3 15 Installation Instructions; CONDUCtING DIeLeCtRIC AND/OR; Do not perform dielectric or high potential; CAUtION; Will cause death or serious injury.; DANGER
PRE-PLAN INSTALLATION TO ACCOMPLISH THE FOLLOWING: • Meet all National and Local codes (NEC® Article 285 addresses SPDs) • Mount SPD as close to panel or equipment as possible to keep leads short • Ensure leads are as short and straight as possible, including neutral and ground. Consider a breaker p...
Page 12 - Figure 4: Electrical Drawings; Figure 5: Mechanical Drawings
Figure 4: Electrical Drawings Figure 1 SPLIT 2 Hots, 1 Neu, 1 Grnd Hot (BLK) Hot (BLK) Neutral (WHT) V V } } Ground (GRN) Figure 2 WYE 3 Hots, 1 Neu, 1 Grnd } Phase A (BLK) Phase B (BLK) Neutral (WHT) Phase C (BLK)Ground (GRN) A C N V B Figure 3 HI-LEG DELTA (B High) 3 H o t s , ( B H I G H ) , 1 Ne...
Page 13 - Operation; If an inoperative condition were to occur,
Phase A, B & c: Green LED indicators—one per phase. Green is good. Extinguished green LED indicates loss of protection. Every suppression element in this SPD is monitored. N-G suppression element monitoring is logic-connected to Phase A. Service leD (red): LED illuminates in the event of problem...
Page 14 - DRY CONTACTS; NC NC C NO; Maintenance
Dry Contact Option Two sets of Form C dry contacts are included with the Dry Contact option. Dry Contacts change state during inoperative conditions, including loss of power. Any status change can be monitored elsewhere via Dry Contacts. A Terminal Block includes two sets of Normally Open (N.O.) and...
Page 15 - Service
Display Replacement The display is field replaceable. Deenergize SPD, confirm with appropriate measurement equipment and discharge internal capacitance to ground. Mark locations and carefully disconnect diagnostic cables, contacts, connecting conductors, etc. Unbolt display and replace. Reinstall in...