SINAMICS G150 Drive converter cabinet units SINAMICS G150 cabinet units 3/2 Siemens D 11 · 2008 3 Overview SINAMICS G150 drive converter cabinet units, versions A and C With its SINAMICS G150 drive converter cabinet units, Siemensis offering a drive system on which all line-side and motor-sidecompon...
Page 3 - Benefits; Siemens
SINAMICS G150 Drive converter cabinet units 75 kW to 1500 kW 3/3 Siemens D 11 · 2008 3 Benefits • Particularly quiet and compact converters due to the use of state-of-the-art IGBT power semiconductors and an innova-tive cooling concept. • Individual modules and power components can be replaced quick...
Page 4 - Design
SINAMICS G150 Drive converter cabinet units 75 kW to 1500 kW 3/4 Siemens D 11 · 2008 3 Design (continued) Basic design of a SINAMICS G150 drive converter cabinet unit with anumber of version-specific options Basic design of a SINAMICS G150 drive converter cabinet unit withparallel circuit in order t...
Page 5 - AOP30 Ad vanced Operator Panel; Drive commissioning; Operation; Help
SINAMICS G150 Drive converter cabinet units 75 kW to 1500 kW 3/5 Siemens D 11 · 2008 3 Function AOP30 Ad vanced Operator Panel An AOP30 Advanced Operator Panel is located in the cabinetdoor of the converter for operation, monitoring and commission-ing tasks. The AOP30’s two-stage safety concept prev...
Page 6 - F u nc tion; S of tw are and p rotec tion f u nc tions; The V
SINAMICS G150 Drive converter cabinet units 75 kW to 1500 kW 3/6 Siemens D 11 · 2008 3 F u nc tion (continued) Com m u nica tion w ith hig her-lev el control a nd cu s tom er’sterm ina l b lock A communications interface on the CU 3 20 Control U nit and theTM 3 1 Terminal M odule and TB 3 0 Terminal...
Page 7 - Function; Safety Integrated; STO
SINAMICS G150 Drive converter cabinet units 75 kW to 1500 kW 3/7 Siemens D 11 · 2008 3 Function (continued) Safety Integrated Safe Torq ue O ff (STO ) Description of functions This function prevents the drive from restarting unexpectedly in accordance with EN 6 0204-1, Section 5.4.Safe Torque O ff d...
Page 8 - Technical specifications
SINAMICS G150 Drive converter cabinet units 75 kW to 1500 kW 3/8 Siemens D 11 · 2008 3 Technical specifications Deviations from the defined classes are identified by underlining. 1) The EN standard specified is the European edition of internationalstandard IEC 62103. 2) The EN standards specified ar...
Page 9 - Voltage derating depending on installation altitude
SINAMICS G150 Drive converter cabinet units 75 kW to 1500 kW 3/9 Siemens D 11 · 2008 3 Technical specifications (continued) Derating data Compensation of current derating as a function of installation al-titude/ambient temperature If the SINAMICS G150 drive converter cabinet units are oper-ated at a...
Page 10 - Power
SINAMICS G150 Drive converter cabinet units 75 kW to 1500 kW 3/10 Siemens D 11 · 2008 3 Technical specifications (continued) Current derating depending on pulse frequency To reduce motor noise or to increase output frequency, the pulsefrequency can be increased relative to the factory setting. Whent...
Page 11 - T ech nical s pecif ications; Low overload
SINAMICS G150 Drive converter cabinet units 75 kW to 1500 kW 3/11 Siemens D 11 · 2008 3 T ech nical s pecif ications (continued) Degrees of protection of cabinet units Standard EN 60529 applies to the protection of electrical eq uip-ment by means of housings, covers or eq uivalent, and includes:• Pr...
Page 17 - Selection and ordering data; Version A
SINAMICS G150 Drive converter cabinet units 75 kW to 1500 kW 3/17 Siemens D 11 · 2008 3 Selection and ordering data Single circuit Order No. supplement Note: The type rating data in hp units are based on the NEC/CECstandards for the North American market. P arallel circuit Note: The type rating data...
Page 18 - Options; Available options
SINAMICS G150 Drive converter cabinet units 75 kW to 1500 kW 3/18 Siemens D 11 · 2008 3 Options Note: When ordering a converter with options, add " -Z " to the order number of the converter, followed by the order code(s) forthe desired option(s). Example: 6SL3710-1GE32-1CA0-Z+M07+D60+... See...
Page 23 - line; Meaning
SINAMICS G150 Drive converter cabinet units 75 kW to 1500 kW 3/23 Siemens D 11 · 2008 3 Options (continued) B02S afely isolated 24 V power supply (P ELV ) If no protective separation for 24 V supply (PELV) is available atthe customer end, this option is used to fit a second power sup-ply to guarante...
Page 25 - Max. connectable motor cable lengths; kW
SINAMICS G150 Drive converter cabinet units 75 kW to 1500 kW 3/25 Siemens D 11 · 2008 3 Options (continued) K51VSM10 Voltage Sensing Module Cabinet-Mounted The VSM10 Voltage Sensing Module reads the voltage wave-shape at the motor end. This allows the SINAMICS G150 con-verter to be connected to a pe...
Page 26 - Type rating
SINAMICS G150 Drive converter cabinet units 75 kW to 1500 kW 3/26 Siemens D 11 · 2008 3 Options (continued) Minimum motor cable lengths for operation with power unitsconnected in parallel Minimum motor cable lengths must be adhered to in the case of• a 12-pulse supply and• a motor with a winding sys...
Page 27 - k line; Converter; Line
SINAMICS G150 Drive converter cabinet units 75 kW to 1500 kW 3/27 Siemens D 11 · 2008 3 Options (continued) L22/L23Delivery without line reactor (L22 for converters " 500 kW ) W ith line reactor 2 % (L23 for converters in singleciruit > 500 kW ) The line reactor is included in the converter a...
Page 28 - O p tio n s
SINAMICS G150 Drive converter cabinet units 75 kW to 1500 kW 3/28 Siemens D 11 · 2008 3 O p tio n s (continued ) L50Cab in et light w ith s erv ic e s ock et One universal lamp w ith an integrated service socket isinstalled for each cab inet panel. T h e pow er supply (on terminal b lock -X 3 9 0) f...
Page 29 - = Power which is permissible every 90 s for 15 s; Rated pow er; Option; P ow er
SINAMICS G150 Drive converter cabinet units 75 kW to 1500 kW 3/29 Siemens D 11 · 2008 3 Options (continued) L61, L62B raking u nits It may be necessary to use braking units for drives that allow re-generative braking. The braking unit comprises two components: a B raking Modulefitted in the converte...
Page 31 - O p tion s
SINAMICS G150 Drive converter cabinet units 75 kW to 1500 kW 3/31 Siemens D 11 · 2008 3 O p tion s ( continued) M13To p c a b le e n try, lin e s id e T he control cabinet is provided with an additional hood in thecase of a line connection from above. T his hood contains the ter-minal link s for the...
Page 33 - Line-side power components; Ov erv iew; Line h a rmonics f ilters
SINAMICS G150 Drive converter cabinet units Line-side power components Line h a rmonics f ilters 3/33 Siemens D 11 · 2008 3 Ov erv iew Line harmonics filters reduce the converter’s low-frequency har-monic effects to a level that can otherwise only be achieved us-ing 12-pulse rectifiers. They render ...
Page 34 - T echnical specifications
SINAMICS G150 Drive converter cabinet units Line-side power componentsLine harmonics filters 3/34 Siemens D 11 · 2008 3 T echnical specifications 1) The rated current of the line harmonics filters is defined in accordancewith the active power. It can therefore be lower than the rated inputcurrent of...
Page 35 - Ty pe rating
SINAMICS G150 Drive converter cabinet units Line-side power components Recommended fuses 3/35 Siemens D 11 · 2008 3 Overview The fuses specified below are the recommended types for pro-tecting the unit on the low-voltage distribution panel. If option L26 (main switch or circuit-breaker) has been sel...
Page 37 - Conductor cross-sections and connections
SINAMICS G150 Drive converter cabinet units Conductor cross-sections and connections 3/37 Siemens D 11 · 2008 3 Overview The tables below show the recommended or maximum possibleconductor cross-sections on the line and motor sides. The recommended cross-sections are based on the listed fusesand sing...
Page 40 - mm
SINAMICS G150 Drive converter cabinet units Conductor cross-sections and connections 3/40 Siemens D 11 · 2008 3 Overview (continued) Required cable cross-sections for line and motorconnections It is always advisable to use 3-wire three-phase cables or to con-nect several cables of this type in paral...