Table of Contents Siemens Building Technologies, Inc. i Table of Contents How to Use this Manual................................................................................................ 1 Manual Organization.........................................................................................
Page 9 - How to Use this Manual; Manual Organization; Notation Symbol
How to Use this Manual Siemens Building Technologies, Inc. 1 How to Use this Manual Manual Organization This manual contains the following sections: • How to Use this Manual , describes the organization of this manual and the symbols used throughout this manual. • Safety Instructions , provides gene...
Page 11 - Safety Instructions
Safety Instructions Siemens Building Technologies, Inc. 3 Safety Instructions The following guidelines are provided for your safety, to prevent damage, and to extend the service life of the SED2 product and any connected equipment. Read this information carefully . Specific Warnings, Cautions, and N...
Page 12 - Electronic Bypass Option Overview; General Description
SED2 VFD Electronic Bypass Option Operating Instructions 4 Siemens Building Technologies, Inc. Electronic Bypass Option Overview General Description During normal operation in a typical application, the input and output contactors close and the SED2 operates the motor (Figure 1). The bypass contacto...
Page 13 - Controller Board
Electronic Bypass Option Overview Siemens Building Technologies, Inc. 5 Controller Board The Controller board is the foundation of the SED2 Electronic Bypass Option. It controls communications to and from the SED2, keypad, isolated digital inputs, relay/digital outputs, and contactors (Figure 3). CO...
Page 14 - Contactors; Bypass Contactor; Output Contactor; Input Contactor; Keypad Functions
SED2 VFD Electronic Bypass Option Operating Instructions 6 Siemens Building Technologies, Inc. Contactors The Controller board provides two or three relay contact circuits controlled by the Electronic Bypass Option: bypass, input, and output contactors. Each circuit includes a NO relay. Controller b...
Page 15 - Pushbutton/Indicator Description
Electronic Bypass Option Overview Siemens Building Technologies, Inc. 7 Pushbutton/Indicator Description Input On/Off VFD0098R1 The Input On/Off pushbutton is supplied with the optional drive input contactor. In VFD mode, this switch does nothing. In bypass mode, this switch closes/opens the input c...
Page 17 - Installation Instructions; Environmental Conditions; Inspection; Dimensions and Weights
Installation Instructions Siemens Building Technologies, Inc. 9 Installation Instructions Environmental Conditions Install the Electronic Bypass Option in a heated, indoor controlled environment that is free of moisture and conductive contaminants such as condensation and dust. The air entering the ...
Page 18 - Mounting
SED2 VFD Electronic Bypass Option Operating Instructions 10 Siemens Building Technologies, Inc. Mounting 1. To ensure safe installation, verify that the surface of the mounting location is level. 2. Mount the Electronic Bypass Option vertically with the SED2 operator panel, Electronic Bypass Option ...
Page 20 - Electrical Installation
SED2 VFD Electronic Bypass Option Operating Instructions 12 Siemens Building Technologies, Inc. Electrical Installation See Figure 9 for all Electronic Bypass Option wiring. 1. Route shielded twisted pair (recommended wire type) cable, 24 gauge minimum control wiring in conduit through knockout and ...
Page 27 - Startup Procedures; Safety Precautions
Startup Procedures Siemens Building Technologies, Inc. 19 Startup Procedures Safety Precautions WARNING: When you connect input power to the Electronic Bypass Option, the motor terminals are energized even if the motor is not running. Do not make any connections with input power connected to the Ele...
Page 28 - Enable; Switch; Input
SED2 VFD Electronic Bypass Option Operating Instructions 20 Siemens Building Technologies, Inc. After the basic sanity test, if the DIP switches have not changed and there is no operator intervention, the most recent bypass function is restored. If the DIP switches have changed, the Electronic Bypas...
Page 29 - Wrong Rotation in Bypass, Right in VFD Mode; Quick Commissioning
Startup Procedures Siemens Building Technologies, Inc. 21 9. If motor rotation is incorrect in either VFD, bypass, or both modes, have the appropriate site personnel take corrective action as follows: − Wrong Rotation in Bypass, Right in VFD Mode – Swap two input leads on the main input device of th...
Page 30 - Parameter Description
SED2 VFD Electronic Bypass Option Operating Instructions 22 Siemens Building Technologies, Inc. Parameter Description Action Setting/ Default P0003 User Access Level Allows you to access more parameters. 1 = Standard 2 = Extended 3 = Expert 1. Press to access parameter r0000 and to enter the SED2 pa...
Page 39 - Additional Parameter Settings
Startup Procedures Siemens Building Technologies, Inc. 31 Additional Parameter Settings NOTE: If Display Selection for r0000, parameter P0005 = 21 (actual frequency), then the BOP display alternately shows setpoint values and the actual value (0 Hz). Flying Start Parameter Description Action Setting...
Page 42 - Automatic Restart Continued
SED2 VFD Electronic Bypass Option Operating Instructions 34 Siemens Building Technologies, Inc. Automatic Restart Continued Parameter Description Action Setting/ Default P1210 (Continued) P1210 = 4, Restart after supply power brownout (P1211 disabled): For these settings it is fundamental that the d...
Page 44 - Vdc Controller
SED2 VFD Electronic Bypass Option Operating Instructions 36 Siemens Building Technologies, Inc. Parameter Description Action Setting/ Default P1213 Restart Time Increment Selects the amount (seconds) that the restart time is incremented for each restart of the SED2 if P1210 automatic restart is acti...
Page 47 - Motor Data Identification Continued
Startup Procedures Siemens Building Technologies, Inc. 39 Motor Data Identification Continued 6. Press to advance to setting P1910=3. Press to confirm and save the setting. When P1910=3, Alarm 0541 (motor data identification active) is output and internally P0340 is set to 2. Initiate the measuring ...
Page 48 - Reset to Factory Defaults
SED2 VFD Electronic Bypass Option Operating Instructions 40 Siemens Building Technologies, Inc. Reset to Factory Defaults Parameter Description Action Setting/ Default P0010 P0970 Reset to Factory Default Resets SED2 parameters to the factory defaults. 1. Press to enter the SED2 parameter mode and t...
Page 49 - Required SED2 Parameter Settings; Parameter Setting
Required SED2 Parameter Settings Siemens Building Technologies, Inc. 41 Required SED2 Parameter Settings The following SED2 parameters are programmed by the factory before shipping. If these parameters are changed or if the SED2 is ever reset to factory default, you must reset these parameters as fo...
Page 50 - Overview; Auto Bypass without Interlock; Description
SED2 VFD Electronic Bypass Option Operating Instructions 42 Siemens Building Technologies, Inc. Application Feature Setup Overview The Controller board supports six isolated digital inputs and six digital relay outputs for customer use (Figure 13). The digital inputs include: Remote Start Input, Rem...
Page 51 - Settings; Example SED2 Settings
Application Feature Setup Siemens Building Technologies, Inc. 43 NOTES: 1. All safety conditions must be met for bypass mode operation. 2. The input contactor remains energized. The Electronic Bypass Option will return to VFD mode operation as soon as the SED2 Relay in control opens. When the Electr...
Page 52 - Interlock
SED2 VFD Electronic Bypass Option Operating Instructions 44 Siemens Building Technologies, Inc. Interlock Description The Interlock feature (also called damper end switch logic) enables the SED2 outputs to inhibit motor start until a safety condition (proofing sequence) is confirmed. Any call to sta...
Page 54 - Wiring Example for Interlock; Essential Services
SED2 VFD Electronic Bypass Option Operating Instructions 46 Siemens Building Technologies, Inc. Wiring Example for Interlock Customer Proof Power to Customer Device Programmable Output, NO COM NC DIGITAL OUTPUTS DIGITAL INPUTS J2 J1 13 14 15 16 17 18 19 20 21 22 23 24 25 26 1 2 3 4 5 6 7 8 9 10 11 1...
Page 56 - Interlock and Auto Bypass on VFD Fault
SED2 VFD Electronic Bypass Option Operating Instructions 48 Siemens Building Technologies, Inc. Interlock and Auto Bypass on VFD Fault Description Interlock and Auto Bypass features are both active. Auto bypass now becomes auto bypass on a VFD fault only (bypass is initiated by the SED2 Fault and th...
Page 57 - Technical Specifications; Specifications Description
Technical Specifications Siemens Building Technologies, Inc. 49 Technical Specifications Table 5. Electronic Bypass Specifications. Specifications Description 208V, 3 ac±10% 240V, 3 ac ±10% 480V, 3 ac ±10% Input Voltage (3 phase) 575V, 3 ac ±10% Digital Inputs Six Digital Inputs as follows: • Remote...
Page 59 - Basic Sanity
Troubleshooting Siemens Building Technologies, Inc. 51 Troubleshooting WARNING: Always disconnect all power sources before opening the SED2 Electronic Bypass Option. Power-on Initialization Failure (Unit Fault Condition) During power-on initialization, a unit fault condition occurs if the Electronic...
Page 60 - Override Jumper
SED2 VFD Electronic Bypass Option Operating Instructons 52 Siemens Building Technologies, Inc. Override Jumper An Override Jumper (J8) is supplied on the Controller board. Moving this jumper to the override position removes the Controller board and its keypad from the control and closes the drive ou...
Page 61 - Bypass Option Part Number
Troubleshooting Siemens Building Technologies, Inc. 53 Table 8. Fuse Replacement Information. Bypass Option Part Number Primary Fuse (F3 and F4) Secondary Fuse (F2) VBE10.5… to VBE17.5… Bussmann/Littlefuse LP-CC-1 Bussmann/Littlefuse LP-CC-6/10 VBE110… to VBE110… Bussmann/Littlefuse LP-CC-2 Bussmann...