Summary
2 / 8 Siemens Electromotoric actuators CE1N4540en Building Technologies 05.11.2009 Type summary Type Operating voltage Positioning signal Positioning time SQD35.00 AC 230 V 3-position 170 s SQD65 1) DC 0…10 V, 0…1000 Ω SQD85.03 1) AC 24 V 3-position 43 s 1) UL approved versions: SQD65UG, SQD85.03UG ...
3 / 8 Siemens Electromotoric actuators CE1N4540en Building Technologies 05.11.2009 • The valve opens / closes in proportion to the control signal at Y or R. • At DC 0 V or 0 Ω the valve is closed (A AB). • When power supply is removed, the actuator maintains its current position. Connector S1 (und...
4 / 8 Siemens Electromotoric actuators CE1N4540en Building Technologies 05.11.2009 Mounting notes Mounting Instructions are enclosed in the product packaging. Type Mounting instructions SQD.. M4540 ASC9.6 G4573.1 Installation notes 90° 43 62 Z 01 90° Commissioning notes When commissioning the system...