Page 2 - Siemens
Additional RDF600KN features: • Independent function for window contact and presence detector Additional RDF301.50 features: • Four buttons to control KNX actuators via KNX S-mode (functions: switching, dimming, blinds control, 8-bit scene) Additional RDF301.50H features: • Four buttons for hotel fu...
Page 4 - YE; -position
Applications for fan coil systems Application and output signal, DIP switches, diagram • 2-pipe fan coil unit ON/OFF (heating or cooling) 1 ON 2 3 • 2-pipe fan coil unit with el. heater (heating or cooling) ON/OFF 1 ON 2 3 30 76 D 20 (B1) M1 Y1 T B2 T T (B1) Y1 M1 31 71 D 21 T B2 YE T (B1) T (B1) • ...
Page 5 - Chilled / heated ceiling with electric; Chilled / heated ceiling; Chilled ceiling and radiator ON/OFF
Applications for Universal systems Application and output signal, DIP switches, diagram • Chilled / heated ceiling ON/OFF (heating or cooling) 1 ON 2 3 • Chilled / heated ceiling with electric heater (heating or cooling) ON/OFF 1 ON 2 3 3191S 11 N1 T B1 T B2 T D3 Y1 3191S 12 N1 T YE B1 T B2 T D3 Y1 ...
Page 6 - or; and; Key
Applications for heat pump systems Application and output signal, DIP switches, diagram • 1-stage compressor ON/OFF (heating or cooling) 1 ON 2 3 • 1-stage compressor with electric heater (heating or cooling) ON/OFF 1 ON 2 3 3181S 31 N1 T B1 T D3 3181S 32 N1 T YE B1 T D3 • 1-stage compressor ON/OFF ...
Page 7 - Round CEE conduit box min 60 mm diameter and min 40 mm depth.
Type summary Product no. Stock no. Operating voltage Control outputs S u ita b le c o n d u it b o x 2 ) 3- pos ON/ OFF DC 0..10 V KNX switching groups RDF301 S55770-T104 AC 230 V 1 1) 2 1) -- rectangular RDF301.50 S55770-T105 AC 230 V 1 1) 2 1) -- rectangular RDF301.50H S55770-T334 AC 230 V 1 1) ...
Page 8 - Accessories; -position actuators
Electrical actuator, 3-position (for radiator valve) SSA31... 4893 Electrical actuator, 3-position (for 2- and 3-port valves / V…P45) SSC31 4895 Electrical actuator, 3-position (for small valve 2,5 mm) SSP31… 4864 Electrical actuator, 3-position (for small valve 5,5 mm) SSB31... 4891 Electrical actu...
Page 11 - KNX
Commissioning notes The room thermostats are delivered with a fixed set of applications. Select and activate the relevant application during commissioning using one of the following tools: − Local DIP switch and HMI − Synco ACS − ETS Set the DIP switches before snapping the front panel to the mounti...
Page 12 - Assign KNX device; Switching groups
The thermostat's control parameters can be set to ensure optimum performance of the entire system (see basic documentation P3171). The parameters can be adjusted using − Local HMI − Synco ACS − ETS • The control sequence may need to be set via parameter P01 depending on the application. The factory ...
Page 13 - Caution
Technical data Power supply Rated voltage AC 230 V Overvoltage category III Frequency 50/60 Hz Power consumption RDF301... RDF600KN Max. 4 VA / 3.0 W Max. 3.5 VA / 1.2 W No internal fuse External preliminary protection with max C 10 A circuit breaker Required in all cases Outputs Fan control Q1, Q2,...
Page 16 - Connection diagrams; Electric heater
Connection diagrams Application N1 Room thermostat RDF301... , RDF600KN M1 1- or 3-speed fan Y1 Valve actuator, 2- or 3-position Y1, Y2 Valve actuator, 2-position E1 Electric heater C1, C2 1-stage compressor F External circuit breaker S1, S2 Switch (keycard, window contact, presence detector, etc.) ...
Page 17 - Dimensions; Dimensions in mm; Subject to change
Dimensions Dimensions in mm RDF301... RDF600KN 86 8 6 3 0 7 6 M 0 1 3 1 7 1 M 1 3 14 30 16 3 0 7 6 M 1 2 80 3 0 7 6 M 1 3 _ 0 1 © 2009 - 2014 Siemens Switzerland Ltd Subject to change 17 / 17 Siemens RDF301, RDF301.50..., RDF600KN CE1N3171en Building Technologies Semi flush-mount communicating room ...