Summary

Page 4 - 6BC Phase Unbalance/Broken Conductor; Fig 2. IEC Overcurrent Curves; Fig 3. ANSI Overcurrent Curves; Description of Functionality

Siemens Protection Devices Limited 4 46BC Phase Unbalance/Broken Conductor Element has settings for pickup level and DTL delay. With the circuit breaker closed, if the NPS:PPS current ratio is above setting this could be due to a broken conductor. 50BF Circuit Breaker Fail The circuit breaker fail f...

Page 5 - Serial Communications

60CTS CT Supervision The relay monitors each phase current input and operates if any one or two inputs fall below the setting. The element types have user operate and delay settings. 64H Restricted Earth Fault The measured earth fault input may be used in a 64H high impedance restricted earth fault ...

Page 6 - Reydisp Evolution

Reydisp Evolution is a Windows based software tool, providing the means for the user to apply settings, interrogate settings and retrieve events and disturbance waveforms from the device and is common to the entire range of Reyrolle protection relays. Fig 5. Typical Reydisp Evolution Screenshot Lang...