Page 2 - CERBERUS CS1145 series Fire Indicator Panel. Model Number CI1145
Data and design subject to changewithout notice. / Supply subject toavailability . E Copyright by Siemens Building Technologies AG We reserve all rights in this documentand in the subject thereof. Byacceptance of the document therecipient acknowledges these rightsand undertakes not to publish thedoc...
Page 3 - Operating instructions CI1145
e1955 11.1999 3 Siemens Building Technologies Cerberus Division Operating instructions CI1145 Introduction 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Operating access 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...
Page 4 - Introduction; System components
e1955 11.1999 4 Siemens Building Technologies Cerberus Division Introduction This Cerberus fire detection installation consists of the following components: System components Equipped Operating console Type ’CI1145’ Series of fire detectors ? Interactive detectors Includes also extinguishing SECTION...
Page 5 - Operating access; Possible access levels:; Access level 1; Everybody; access to all user functions; Service; How to get USER operating access:; See ’Overview operating menus’ on pages 36 up to 41; How to get SERVICE ENGINEER operating access:; Log in; To cancel keying errors press; Log out
e1955 11.1999 5 Siemens Building Technologies Cerberus Division Operating access General: The control console is protected by a front door against unauthorized or unintentional manipulation. So no fur-ther password protection is necessary except for some special functions which are restricted to the...
Page 6 - Control console layout; Firefighter facility; Special keys and indicators
e1955 11.1999 6 Siemens Building Technologies Cerberus Division Control console layout 1 2 3 4 5 6 7 8 9 ok F2 F1 0 C AlgoRex R Alarms Faults Isolation Information Alarm device Alarm device Alarm device Premises active fault isolate(d) manned Remote alarm Remote transmission Remote alarm Alarm delay...
Page 7 - tivity is in progress.; Function key pad
e1955 11.1999 7 Siemens Building Technologies Cerberus Division Control console layout cont. Firefighter facility 17 Text display with yellow illumination. dark, if no danger message («Alarm») is pending and no operator ac- tivity is in progress. 17a Information bar Information is context dependent ...
Page 8 - Message categories; There are the following message categories:; Information display field
e1955 11.1999 8 Siemens Building Technologies Cerberus Division Message categories There are the following message categories: Alarms danger messages acquired by the system Priority 1 Faults messages that require an immediate response Priority 2 Isolation system components out of service Priority 3 ...
Page 9 - Terminology ’Area’, ’Section’ and ’Zone’; For this reason we have
e1955 11.1999 9 Siemens Building Technologies Cerberus Division Terminology ’Area’, ’Section’ and ’Zone’ What is an «Area»? It normally covers a whole building or part of a building and represents also the operating level.This is the logical designation for several, usually adjacent sec-tions Area ’...
Page 10 - Normal operation / Mains available; What is «Normal operation»?; The system is ready for receiving danger messages; What is «Mains available»?; The green indicator
e1955 11.1999 10 Siemens Building Technologies Cerberus Division Normal operation / Mains available What is «Normal operation»? The system is ready for receiving danger messages No alarm and no fault messages are pending and no part of the system is isolated Ü The system can either be in state «mann...
Page 11 - Operating states ’manned’ and ’unmanned’; Basic rules; Manual switch over from «manned» to «unmanned»; Automatic switchover
e1955 11.1999 11 Siemens Building Technologies Cerberus Division Operating states ’manned’ and ’unmanned’ Is the Cerberus Alarm Concept activated? Yes No Basic rules The operating states «Manned» and «Unmanned» are only relevant for systems in which the signals for auto-matic fire detectors and manu...
Page 12 - Quick reference instructions; How to start operating ?; The MAIN MENU is displayed; Select desired function in ’MAIN MENU’ by using; option selected is shown inverse; Notes
e1955 11.1999 12 Siemens Building Technologies Cerberus Division Quick reference instructions How to start operating ? 1. Press F2 Ü The MAIN MENU is displayed 2. Select desired function in ’MAIN MENU’ by using the arrow keys and 3. Then press ok Ü option selected is shown inverse Function ’FIRE det...
Page 13 - Cerberus Alarm Concept; How does the Cerberus Alarm Concept function?; Alarm; Alarm acknowledgement time «V1»; the preprogrammed time.; system operates in «manned» mode.
e1955 11.1999 13 Siemens Building Technologies Cerberus Division Cerberus Alarm Concept How does the Cerberus Alarm Concept function? When the system operates in «manned» mode, manual call points and automatic fire detectors trigger differentactions in the event of an alarm. F ÈÈÈÈ ÈÈÈÈ ÈÈÈÈ ÈÈÈÈ ÈÈ...
Page 14 - Alarm – general information; How are alarm messages shown in the text display?; st alarm; Text Display; Message text
e1955 11.1999 14 Siemens Building Technologies Cerberus Division Alarm – general information How are alarm messages shown in the text display? Room Room Corridor Zone «Room 104» 1st alarm message 2nd alarm message Zone «Room 102» 1st message+ «scroll box» last message 103 102 Room 103 Room 104 up to...
Page 15 - Message order; unacknowledged alarms; Acknowledge; Each message has to be acknowledged separately; Select the desired unacknowledged mes-; Supplementary information; Reset; Each message has to be reset separately; Select the message to be reset; The confirmation dialog is displayed
e1955 11.1999 15 Siemens Building Technologies Cerberus Division Alarm – general information cont. Message order Messages are presented in the following order: 1. unacknowledged alarms 2. acknowledged alarms 3. isolated alarms Within these categories the messages are sorted chronologically. Acknowle...
Page 17 - What to do if alarm cannot be reset ?; Select ZONE on alarm to be isolated; to confirm; ZONE de–isolation procedure; Select the isolated ZONE in the; alarms; Note; Isolation; list
e1955 11.1999 17 Siemens Building Technologies Cerberus Division Alarm – what to do ? cont. What to do if alarm cannot be reset ? As long as a detector still detects a fire phenomena (smoke, heat, flame) the alarm cannot be reset. In order toremove such an alarm the corresponding detector zone has t...
Page 18 - Detector zone, temporary isolation; What is ISOLATION of a ZONE ?; If zones are NOT in alarm; ZONE isolation procedure if zone is NOT on alarm; The AREAS overview is displayed; The SECTIONS overview is displayed; The ZONES overview is displayed
e1955 11.1999 18 Siemens Building Technologies Cerberus Division Detector zone, temporary isolation What is ISOLATION of a ZONE ? Isolated zones have the following characteristics: The zone state (alarm and fault) is evaluated and displayed Alarms on isolated zones do NOT activate any control output...
Page 19 - The FUNCTION LIST ’zone’ is displayed; ZONE reactivation procedure; Select the message category by pressing the; key; Select the zone to be de–isolated; The message is displayed in inverted colors
e1955 11.1999 19 Siemens Building Technologies Cerberus Division Detector zone, temporary isolation cont. 5. Press F1 Ü The FUNCTION LIST ’zone’ is displayed Select the function ’ISOLATE zone’Press ok to confirm Ü The selected ZONE is isolated Ü It is displayed spontaneously (if no messages ofhigher...
Page 20 - Isolation of individual detectors; When does a detector have to be isolated ?; Isolate a detector when a fault message is pending; Faults
e1955 11.1999 20 Siemens Building Technologies Cerberus Division Isolation of individual detectors When does a detector have to be isolated ? Only when it is damaged or defective until it is replaced.NoteAn isolated detector cannot generate any messages.The isolation of detectors only makes sense if...
Page 21 - Fault; What to do in case of reported fault messages?; What remedies are available to the user?; reinsert the detector; For all other faults call the Cerberus service organization
e1955 11.1999 21 Siemens Building Technologies Cerberus Division Fault What to do in case of reported fault messages? 1. Confirm the message by pressing ACK 2. Read the fault location on the display 3. Go to the fault location 4. If the fault cannot be removed call the Cerberus service organization ...
Page 22 - Mode ’Detector test’; What is the «Detector test» mode for?
e1955 11.1999 22 Siemens Building Technologies Cerberus Division Mode ’Detector test’ What is the «Detector test» mode for? The mode «Detector test» allows individual on-site function testing of automatic fire detectors and manual callpoints without generating an alarm message. Automatic fire detect...
Page 23 - Recommendations for detector test; Testing of automatic AlgoRex; detectors; «Test alarm» is simulated.
e1955 11.1999 23 Siemens Building Technologies Cerberus Division Mode ’Detector test’ cont. Recommendations for detector test Perform the function test periodically. The interval of this test is determined by the service engineer. Switch only the fire detectors of one SECTION at a time to «Detector ...
Page 24 - Terminate «Detector test» for all detector zones within a SECTION
e1955 11.1999 24 Siemens Building Technologies Cerberus Division Mode ’Detector test’ cont. Terminate «Detector test» for all detector zones within a SECTION 1. Press F2 Ü The MAIN MENU is displayed 2. Press ok Ü The AREAS overview is displayed Press to select the desired AREA 3. Press ok Ü The SECT...
Page 25 - Poll ’test alarms’ in the event memory; The STATIONS overview is displayed; The function list Event Memory is displayed; The TEST Alarms are displayed
e1955 11.1999 25 Siemens Building Technologies Cerberus Division Mode ’Detector test’ cont. Poll ’test alarms’ in the event memory 1. Press F2 Ü The MAIN MENU is displayed Press to select DEVICE level 2. Press ok Ü The STATIONS overview is displayed Press to select the desired STATION 3. Press F1 Ü ...
Page 26 - Mode ’Installation test’; What is the mode «Installation test» for?; Termination of mode «Installation test» of a zone; Information
e1955 11.1999 26 Siemens Building Technologies Cerberus Division Mode ’Installation test’ What is the mode «Installation test» for? The mode «Installation test» allows to test the correct function of the whole fire detection system including firecontrols, acoustical alarm devices, etc. All functions...
Page 27 - Mode ’Renovation’; What is the «Renovation» mode for?; Termination of mode «Renovation» of a zone
e1955 11.1999 27 Siemens Building Technologies Cerberus Division Mode ’Renovation’ What is the «Renovation» mode for? In «Renovation» mode, automatic detectors are much less sensitive. This may be required while unusual workis in progress (e.g. during renovation of a building).The fire detection sys...
Page 28 - Remote transmission ISOLATE/DE–ISOLATE; What is «Remote transmission»?; Remote alarm isolate; ISOLATING the remote transmission
e1955 11.1999 28 Siemens Building Technologies Cerberus Division Remote transmission ISOLATE/DE–ISOLATE This system is equipped with a remote transmission facility for FIRE ALARM Yes, destination: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ....
Page 29 - Alarm devices ISOLATE/DE–ISOLATE; ISOLATING the alarm devices; DE–ISOLATING the alarm devices; Press key; The alarm devices can also be isolated and de–isolated via the menu.
e1955 11.1999 29 Siemens Building Technologies Cerberus Division Alarm devices ISOLATE/DE–ISOLATE When do alarm devices (horns, sirens, etc.) have to be isolated ? Normally the alarm devices operate in active stand-by. Isolation is needed only in special cases, for example fortesting the control fun...
Page 30 - Printer ISOLATE/DE–ISOLATE; When does the printer have to be ISOLATED?; DE–ISOLATING the printer
e1955 11.1999 30 Siemens Building Technologies Cerberus Division Printer ISOLATE/DE–ISOLATE This system is equipped with a printer Yes No When does the printer have to be ISOLATED? Normally the printer (if installed) operates in active stand-by. Isolation is needed only in special cases (for exam-pl...
Page 31 - Printer B2Q191: paper replenishing; Valid for this system; Spare paper rolls
e1955 11.1999 31 Siemens Building Technologies Cerberus Division Printer B2Q191: paper replenishing Valid for this system Yes, system equipped with printer B2Q191 No printer of this type installed 1 Isolate the printer firstSwing out printer unit ÎÎÎ ÎÎÎ ÎÎÎ ÎÎÎ ÎÎÎ ÎÎÎÎ ÎÎÎÎ ÎÎÎÎ ÎÎÎ ÎÎÎ ÎÎÎ ÎÎÎ ÎÎ...
Page 32 - Lamp test; What is the «Lamp test» used for?; The lamp test is initiated
e1955 11.1999 32 Siemens Building Technologies Cerberus Division Lamp test What is the «Lamp test» used for? For testing the correct functioning of all indicators (LEDs), the display, and the alarm buzzer.All visual and audible devices of the control console are activated for a few seconds. Initiate...
Page 33 - Alarm counter; What is the purpose of polling the alarm counter?; The number of alarms is displayed
e1955 11.1999 33 Siemens Building Technologies Cerberus Division Alarm counter What is the purpose of polling the alarm counter? The alarm counter shows the number of past alarm events. Polling alarm counter 1. Press F2 Ü The MAIN MENU is displayed 2. Press ok Ü The AREAS overview is displayed Press...
Page 34 - Event memory; Polling event memory of an ’AREA’; The display now shows the desired list.; Printing selected entries of the event memory
e1955 11.1999 34 Siemens Building Technologies Cerberus Division Event memory Polling event memory of an ’AREA’ 1. Press F2 Ü The MAIN MENU is displayed 2. Press ok Ü The AREAS overview is displayed Press to select the desired AREA 3. Press F1 Ü The FUNCTION LIST ’area’ is displayed Press to select ...
Page 35 - Set clock and date; Setting the clock; Setting the date
e1955 11.1999 35 Siemens Building Technologies Cerberus Division Set clock and date Normally the date and time do not have to be corrected!The date and time are set by the service engineer when installing the system. The summer/winter time changeover is performed automatically. Time and date are alw...
Page 36 - Overview operating menus; To enter ’MAIN MENU’ press
e1955 11.1999 36 Siemens Building Technologies Cerberus Division Overview operating menus To enter ’MAIN MENU’ press F2 FUNCTION LIST ’area’switching MANNED/UNMANNEDpoll COUNTER ’fire alarms’reset COUNTER ’fire alarms’poll COUNTER ’remote alarms’DE–ISOLATE alarm HORNSISOLATE alarm HORNSalarm HORN –&...