Page 2 - Products International. The Regency; INFORMATION FOR MOBILE/MANUFACTURED HOMES AFTER FIRST SALE; This Regency
2 U37-1 Regency ® ULTIMATE Rear Vent Direct Vent Freestanding Gas Stove To the New Owner: Congratulations! You are the owner of a state-of-the-art ULTIMATE Rear Vent Direct Vent Gas Stove by FPI Fireplace Products International. The Regency ® Gas Series of hand crafted appliances has been designed t...
Page 3 - TABLE OF CONTENTS
U37-1 Regency ® ULTIMATE Rear Vent Direct Vent Freestanding Gas Stove 3 TABLE OF CONTENTS SAFETY LABEL Copy of Serial No. Decal ............................................... 4 REQUIREMENTS MA Code - CO Detector ................................................ 5 INSTALLATION Important Message ........
Page 4 - SAFETY LABEL; Copy of Safety Label for U37; DOOR SEAL ADJUSTMENT:; Please check that door is properly sealed.
4 U37-1 Regency ® ULTIMATE Rear Vent Direct Vent Freestanding Gas Stove This is a copy of the label that accompanies each ULTIMATE Rear Vent Direct Vent Free-standing Gas Stove. We have printed a copy of the contents here for your review. The safety label is located on the inside of the drop down pe...
Page 5 - REQUIREMENTS; MA Code - CO Detector
U37-1 Regency ® ULTIMATE Rear Vent Direct Vent Freestanding Gas Stove 5 REQUIREMENTS 5.08: Modifications to NFPA-54, Chapter 10 (2) Revise 10.8.3 by adding the following additional requirements: (a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or s...
Page 6 - INSTALLATION
6 U37-1 Regency ® ULTIMATE Rear Vent Direct Vent Freestanding Gas Stove IMPORTANT MESSAGE SAVE THESE INSTRUCTIONS The ULTIMATE Rear Vent Direct Vent Freestand-ing Gas Stove must be installed in accordance with these instructions. Carefully read all the instructions in this manual fi rst. Consult the ...
Page 8 - EXTERIOR VENT TERMINAL LOCATIONS
8 U37-1 Regency ® ULTIMATE Rear Vent Direct Vent Freestanding Gas Stove INSTALLATION EXTERIOR VENT TERMINAL LOCATIONS A= Clearance above grade, veranda, porch, deck, or balcony *(min. 12"/30cm) B= Clearance to window or door that may be opened *(12"/30cm) #(9"/23cm) C= Clearance to perma...
Page 9 - IMPORTANT
U37-1 Regency ® ULTIMATE Rear Vent Direct Vent Freestanding Gas Stove 9 PLANNING YOUR VENTING INSTALLATION INSTALLATION IMPORTANT Read all instructions carefully before starting the installation. Failure to follow these instruc-tions may create a fi re or other safety hazard, and will void the warran...
Page 10 - ” X 6-5/8” RIGID PIPE CROSS REFERENCE CHART
10 U37-1 Regency ® ULTIMATE Rear Vent Direct Vent Freestanding Gas Stove 4” X 6-5/8” RIGID PIPE CROSS REFERENCE CHART Components from different Manufacturers may not be mixed. Not All Rigid Pipe components are available directly from FPI. Description Simpson Direct Vent Pro ® Simpson Direct Vent GS ...
Page 11 - Offset Pipe Selection:; Use this table to determine offset pipe lengths.
U37-1 Regency ® ULTIMATE Rear Vent Direct Vent Freestanding Gas Stove 11 Description Simpson Direct Vent Pro ® Simpson Direct Vent GS ® Discontinued Selkirk Direct-Temp™ American Metal Products ® Amerivent Direct Metal-Fab ® Sure Seal Security Secure Vent ® Attic Insulation Shield 12” 46DVA-IS - N/A...
Page 12 - RIGID PIPE VENTING - VERTICAL TERMINATIONS
12 U37-1 Regency ® ULTIMATE Rear Vent Direct Vent Freestanding Gas Stove INSTALLATION RIGID PIPE VENTING - VERTICAL TERMINATIONS FOR BOTH RESIDENTIAL & MANUFACTURED HOMES/MOBILE HOMES Offset to Vertical Terminations Vertical Terminations with Co-linear Flex System The shaded area in the diagram ...
Page 13 - HORIZONTAL TERMINATIONS; RESIDENTIAL AND MANUFACTURED HOMES /
U37-1 Regency ® ULTIMATE Rear Vent Direct Vent Freestanding Gas Stove 13 INSTALLATION Diagram 2a HORIZONTAL TERMINATIONS Diagram 1 *Dia 2a & 2b: As specifi ed in CGA B149 Instal-lation Code. Local codes or regulations may require different clearances. RESIDENTIAL AND MANUFACTURED HOMES / MOBILE H...
Page 15 - VERTICAL TERMINATION WITH
U37-1 Regency ® ULTIMATE Rear Vent Direct Vent Freestanding Gas Stove 15 Flex Liner Exhaust Flue Air Intake Co-Linear Flex Adapter with Kit# 946-563 Co-linear DV Vertical Termination Cap # 946-529 Inner Pipe Adapter with Kit# 946-563 U37 Rigid Pipe Adaptor Part # 640-994 Outer Pipe with Kit# 946-563...
Page 16 - General; Converting a Factory
16 U37-1 Regency ® ULTIMATE Rear Vent Direct Vent Freestanding Gas Stove CONVERTING CLASS-A METAL CHIMNEY OR MASONRY CHIMNEY TO DIRECT VENT SYSTEM General There are two different types of direct vent conversion systems listed below. Follow the appropriate directions for your installation. A) Through...
Page 19 - Also check that the pilot and main
U37-1 Regency ® ULTIMATE Rear Vent Direct Vent Freestanding Gas Stove 19 15) Verify that if the conversion is from NG to LPG, the screw must be re-assem-bled with the red o-ring visible (Fig. 5). LPG Configuration Red o-ring visible Fig.5 16) Re-assemble the black protection cap (Fig. 6). Fig. 6 WAR...
Page 20 - The gas log kit contains the following:; Note: Prior to any pressure testing of
20 U37-1 Regency ® ULTIMATE Rear Vent Direct Vent Freestanding Gas Stove AERATION ADJUSTMENT The burner aeration is factory set but may need adjusting due to either the local gas supply, air supply or altitude. Natural Gas: 1/4" open Propane: 3/8" open The aeration adjustment gears are locat...
Page 22 - GAS PIPE PRESSURE TESTING; DOOR INSTALLATION; Valve Description
22 U37-1 Regency ® ULTIMATE Rear Vent Direct Vent Freestanding Gas Stove INSTALLATION GAS PIPE PRESSURE TESTING The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressur...
Page 23 - CAUTION
U37-1 Regency ® ULTIMATE Rear Vent Direct Vent Freestanding Gas Stove 23 WALL THERMOSTAT A wall thermostat may be installed if desired. Connect the wires as per the wiring diagrams. Note that the wires are connected to the "TH" on the gas valve. Use table below to determine the maximum wire ...
Page 24 - WIRING DIAGRAM; WARNING: Electrical Grounding Instructions
24 U37-1 Regency ® ULTIMATE Rear Vent Direct Vent Freestanding Gas Stove WIRING DIAGRAM This heater does not require a 120V A.C. sup-ply for operation. In case of a power failure, the burner switch and the optional remote control/thermostat will continue to operate. However, a 120V A.C. power supply...
Page 25 - OPERATING INSTRUCTIONS
U37-1 Regency ® ULTIMATE Rear Vent Direct Vent Freestanding Gas Stove 25 OPERATING INSTRUCTIONS OPERATING INSTRUCTIONS 1) Read and understand these instructions before operating this appliance. 2) Check to see that all wiring is correct and enclosed to prevent possible shock. 3) Check to ensure ther...
Page 26 - COPY OF THE LIGHTING PLATE INSTRUCTIONS; DO NOT REMOVE THIS INSTRUCTION PLATE; FOR YOUR SAFETY READ BEFORE LIGHTING; LIGHTING INSTRUCTIONS
26 U37-1 Regency ® ULTIMATE Rear Vent Direct Vent Freestanding Gas Stove COPY OF THE LIGHTING PLATE INSTRUCTIONS OPERATING INSTRUCTIONS 1) Push in gas control knob slightly and turn to “PILOT” position. 2) Push in control knob all the way and hold in until the pilot lights up. Continue to hold the c...
Page 27 - MAINTENANCE
U37-1 Regency ® ULTIMATE Rear Vent Direct Vent Freestanding Gas Stove 27 MAINTENANCE MAINTENANCE INSTRUCTIONS 1) Always turn off the valve before cleaning. For relighting, refer to lighting instructions. Keep the burner and control compartment clean by brushing and vacuuming at least once a year. Wh...
Page 28 - LATCH ADJUSTMENT; MITRED DOOR; Installing Glass
28 U37-1 Regency ® ULTIMATE Rear Vent Direct Vent Freestanding Gas Stove MAINTENANCE LATCH ADJUSTMENT The door latch may require adjustment as the door gasket material compresses after a few fi res and after glass replacement. Turn the handle on the adjustable catch to tighten or loosen the latch. GL...
Page 29 - REMOVING VALVE; FAN MAINTENANCE
U37-1 Regency ® ULTIMATE Rear Vent Direct Vent Freestanding Gas Stove 29 REMOVING VALVE If your valve requires maintenance or replace-ment, use the following instructions: Note: Always close off the gas supply before removing the valve. 1) Open front pedestal door. You may want to put a soft cloth o...
Page 30 - DC SPARKER
30 U37-1 Regency ® ULTIMATE Rear Vent Direct Vent Freestanding Gas Stove 6) Remove the two outside frame pieces by removing two screws per side. See diagram below. 7 ) At this point you should disconnect the gas at the valve. You can access it through the front now that the control panel is off, or ...
Page 31 - PARTS LIST; MAIN ASSEMBLY
U37-1 Regency ® ULTIMATE Rear Vent Direct Vent Freestanding Gas Stove 31 PARTS LIST 1) 560-920 Louver Assy - Gold 560-921 Louver Assy - Brush Nickel 560-922 Louver Assy - Black 9) 730-560 Relief Door Assembly 10) 730-034 Mounting Plate Gasket 11) 730-517/P Fan Assembly (120 V) 910-331/P Fan Motor 12...
Page 32 - BURNER & LOG ASSEMBLY
32 U37-1 Regency ® ULTIMATE Rear Vent Direct Vent Freestanding Gas Stove PARTS LIST BURNER & LOG ASSEMBLY 51) 910-241 Burner ON/OFF Switch (3-way) 52) 910-190 Piezo Ignitor & Nut 53) 904-586 Knob - Fan Control Switch 54) 910-373 Knob - Pilot Valve Extension 55) 910-372 Flame Adjusting Knob 5...
Page 33 - DOOR ASSEMBLIES
U37-1 Regency ® ULTIMATE Rear Vent Direct Vent Freestanding Gas Stove 33 DOOR ASSEMBLIES Part # Description 730-923 Brush Nickel Mitred Door - Complete 730-924 Gold Mitred Door - Complete 730-926 Black Mitred Door - Complete 730-932 Gold Wrap Door - Complete 730-928 Gold Panel Door - Complete 101) 6...
Page 34 - NOTES
34 U37-1 Regency ® ULTIMATE Rear Vent Direct Vent Freestanding Gas Stove NOTES ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ _____________...
Page 35 - WARRANTY
U37-1 Regency ® ULTIMATE Rear Vent Direct Vent Freestanding Gas Stove 35 WARRANTY Regency Fireplace Products are designed with reliability and simplicity in mind. In addition, our internal Quality Assurance Team carefully inspects each unit thoroughly before it leaves our facility. FPI Fireplace Pro...
Page 36 - Installer: Please complete the following information; Printed in Canada
Installer: Please complete the following information Dealer Name & Address: ______________________________________________ ___________________________________________________________________ Installer: ___________________________________________________________ Phone #: _________________________...