Page 2 - MANUFACTURED MOBILE HOME REQUIREMENTS; INFORMATION FOR MOBILE/MANUFACTURED HOMES AFTER FIRST SALE
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace 2 To the New Owner: Congratulations!You are the owner of a state-of-the-art Gas Fireplace by REGENCY. The P121/P121LC/P121RC/P131 is a hand crafted appliance and has been designed toprovide you with all the warmth and c...
Page 3 - TABLE OF CONTENTS
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace 3 TABLE OF CONTENTS Operating Instructions Operating Instructions ............................................... 29Lighting Procedure .................................................... 29Shutdown Procedure .............
Page 4 - SAFETY LABEL
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace 4 This is a copy of the label that accompanieseach P121-1/P121LC-1/P121RC-1/P131-1 ZeroClearance Direct Vent Gas Fireplace. We haveprinted a copy of the contents here for yourreview. The safety label is located on the f...
Page 5 - INSTALLATION; YOUNG CHILDREN SHOULD BE; Note: These units are
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace 5 INSTALLATION CHECKLIST 1 ) Locate appliance a ) Room location, page 8.b ) C l e a r a n c e s t o C o m b u s t i b l e s , page 9. c ) Mantle Clearances, page 9.d ) Framing & Finishing Requirements, page 10. e ) ...
Page 6 - SPECIFICATIONS
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace 6 INSTALLATION SPECIFICATIONS P121-1 See Thru P131-1 Pier Note: These units arenon-load bearing.
Page 9 - COMBUSTIBLE MANTELS; Mantel Clearances
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace 9 INSTALLATION COMBUSTIBLE MANTELS CLEARANCES The clearances listed below are Minimum distances unless otherwise stated (refer to diagrams on page 8): WARNING: Fire hazard is an extreme risk if these clearances (air spa...
Page 10 - FRAMING AND FINISHING; Framing Dimensions
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace 10 B C A FRAMING AND FINISHING CAUTION: The unit does not have to be completely enclosed ina chase. The clearance on top of the unit is 0" to the standoffsso combustible building materials can be laid directly on to...
Page 11 - Top Standoff Assembly
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace 11 VENTING INTRODUCTION The P121-1/P121LC-1/P121RC-1/P131-1 usesthe "balanced flue" technology Co Axialsystem. The inner liner vents products of com-bustion to the outside while the outer linerdraws outside comb...
Page 12 - EXTERIOR VENT TERMINATION LOCATIONS
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace 12 INSTALLATION EXTERIOR VENT TERMINATION LOCATIONS . B B B B A C V V V V V V V A A V Fixed Fixed Openable Closed Closed Openable N L B E B M D F K H j V ertical Termination V V ent terminal Area where terminal is not p...
Page 13 - VENTING ARRANGEMENT - HORIZONTAL TERMINATIONS; Regency Direct Vent System (Flex) Horizontal Terminations Only
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace 13 VENTING ARRANGEMENT - HORIZONTAL TERMINATIONS Regency Direct Vent System (Flex) Horizontal Terminations Only These venting systems, in combination with the P121-1/P121LC-1/P121RC-1/P131-1 Direct Vent Gas Fireplace, h...
Page 14 - Horizontal or Vertical Terminations; Flat Wall Installation
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace 14 S i m p s o nD u r a - V e n tDirect Vent GS SIMPSON DURA-VENT VENTING COMPONENTS LIST All Simpson Dura-Vent components are available directly from Regency. SIMPSON DURA-VENT VENTING Horizontal or Vertical Terminatio...
Page 15 - VENTING ARRANGEMENTS - HORIZONTAL TERMINATIONS; Straight Out Horizontal Venting; Option
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace 15 INSTALLATION VENTING ARRANGEMENTS - HORIZONTAL TERMINATIONS SIMPSON DURA-VENT DIRECT VENT GS SYSTEM (Propane & Natural Gas) The diagram below shows examples of horizontal termination arrangements using one, two, ...
Page 16 - Elbows; Elbows
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace 16 INSTALLATION Diagram 3 Horizontal Venting with Two (2) 90 o Elbows Option V H + H1 A) 1' (305mm) Minimum 2' (610mm) Maximum B) 2' (610mm) Minimum 5' (1.5m) Maximum C) 3' (914mm) Minimum 8' (2.4m) Maximum D) 4' (1.22m...
Page 17 - VENTING ARRANGEMENTS - VERTICAL TERMINATIONS; SIMPSON DURA-VENT DIRECT VENT GS SYSTEM; Straight Up Vertical Venting; IMPORTANT
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace 17 INSTALLATION VENTING ARRANGEMENTS - VERTICAL TERMINATIONS SIMPSON DURA-VENT DIRECT VENT GS SYSTEM (Propane & Natural Gas) • Vent must be supported at offsets • Maintain clearances to combustibles as listed on pag...
Page 19 - HORIZONTAL
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace 19 INSTALLATION HORIZONTAL INSTALLATIONS Install the vent system according to them a n u f a c t u r e r ' s i n s t r u c t i o n s i n c l u d e dwith the components. 1 ) Set the unit in its desired location. Check to...
Page 21 - Offset Chart; for Regency AstroCap; Direct
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace 21 INSTALLATION inside each other and can be adjusted for2 x 4 or 2 x 6 walls. The liners must slipover the collars a minimum of 1-3/8". 5 ) Slip the assembled liner and termination assembly through the thimble maki...
Page 23 - System Data
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace 23 INSTALLATION GAS PIPE PRESSURE TESTING The appliance must be isolated from the gassupply piping system by closing its individualmanual shut-off valve during any pressuretesting of the gas supply piping system at test...
Page 24 - LOG INSTALLATION
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace 24 INSTALLATION LOG INSTALLATION Read the instructions below carefully and refer to the diagrams.If logs are broken do not use the unit until they are replaced.Broken logs can interfere with the pilot operation. The gas...
Page 26 - FINISHING TRIM
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace 26 GLASS DOOR REMOVAL 1 ) Remove the 8 screws that secure the glass door. INSTALLATION 2 ) Pull the door slightly out on an angle and then lift up and pull completely out. 3 ) P131 & P121LC/P121RC Corner Model: Remo...
Page 27 - Thermostat Wire Table; WALL THERMOSTAT
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace 27 Option 1: REMOTE CONTROL Can be used with Option 2 or 3 but not both. Use the Regency Remote Control Kit approvedfor this unit. Use of other systems may void yourw a r r a n t y . The remote control kit comes with a ...
Page 28 - WIRING DIAGRAM
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace 28 WIRING DIAGRAM Caution: Ensure that the wires donot touch any hot surfaces and areaway from sharp edges. CAUTION: Label all wiresprior to disconnection whenservicing controls. Wiring er-rors can cause improper anddan...
Page 29 - OPERATING INSTRUCTIONS
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace 29 OPERATING INSTRUCTIONS OPERATING INSTRUCTIONS 1 ) Read and understand these instructions before operating this appliance. 2 ) Check to see that all wiring is correct and enclosed to prevent possible shock. 3 ) Check ...
Page 30 - General Vent Maintenance; DO NOT REMOVE THIS INSTRUCTION PLATE
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace 30 MAINTENANCE INSTRUCTIONS 1 ) Always turn off the gas valve before cleaning. For relighting, refer to lightinginstructions. Keep the burner and controlcompartment clean by brushing and vacu-uming at least once a year....
Page 31 - MAINTENANCE; LOG REPLACEMENT; THERMOCOUPLE; GLASS REPLACEMENT; REMOVING VALVE
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace 31 MAINTENANCE 2 ) Remove the Cap, and shine a flashlight down the Vent. Remove any bird nests, orother foreign material. 3 ) Check for evidences of excessive con- densation, such as water droplets formingin the inner l...
Page 32 - INSTALLING VALVE
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace 32 12) Lift the entire assembly out. 8 ) Remove the Side Base Brick Panels and finally the Long Base Brick Panels. MAINTENANCE Remove Left & Right Side Base Brick Panels Remove the 2 Long Base Brick Panels 9 ) Disco...
Page 33 - FAN REPLACEMENT
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace 33 FAN REPLACEMENT 1) Shut off power. 2) Remove top louvers. 3) Unplug power wires. 4) Remove 4 screws securing fan to mounting bracket. MAINTENANCE 5) Remove 2 connector wires. 6) Replace fan. 7) Repeat for opposite si...
Page 34 - PARTS LIST
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace 34 PARTS LIST P121-1 (SEE THRU) MAIN ASSEMBLY Part # Description Part # Description Part # Description 1 ) 360-528 Door Assy Front - Tempered 360-538 Door Assy Front - Ceramic(Optional) 2 ) 360-529 Door Assy Side - Temp...
Page 39 - WARRANTY
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace 39 WARRANTY Regency Fireplace Products, are designed with reliability and simplicity in mind. In addition, our internal Quality AssuranceTeam carefully inspects each unit thoroughly before it leaves our door. Regency In...
Page 40 - Installer: Please complete the following information; Printed in Canada
Installer: Please complete the following information Dealer Name & Address: ______________________________________________ __________________________________________________________________ Installer: ___________________________________________________________ Phone #: __________________________...