Page 3 - Class A EMC Statements; Requesting a Declaration of Conformity
Class A EMC Statements FCC Part 15 NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a c...
Page 4 - Special Symbols; RISK OF ELECTRIC SHOCK; - Refer to your operator’s manual for additional information, such
Special Symbols The following are examples of symbols used on the UPS or accessories to alert you to important information: RISK OF ELECTRIC SHOCK - Indicates that a risk of electric shock is present and the associated warning should be observed. CAUTION: REFER TO OPERATOR’S MANUAL - Refer to your o...
Page 5 - Table of Contents; Introduction; Powerware Hot Sync CAN Bridge Card; Service and Support
EATON Powerware ® 9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com i Table of Contents 1 Introduction 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Safety Warnings 3 . . . . . . . . . . . . . . ....
Page 7 - Chapter 1; Hot Sync
EATON Powerware ® 9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com 1 Chapter 1 Introduction A Tie Cabinet can be installed as a wall-mounted bypass or to provide support for aparallel system for redundancy or extra capacity. A wall-mounted bypass switch is used to ...
Page 9 - Chapter 2; IMPORTANT SAFETY INSTRUCTIONS; D A N G E R; This UPS contains; LETHAL VOLTAGES; . All repairs and service should be performed by; AUTHORIZED; W A R N I N G
EATON Powerware ® 9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com 3 Chapter 2 Safety Warnings IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that you should follow during installation and maintenance ofthe UPS and...
Page 10 - Consignes de Sécurité; CONSIGNES DE SÉCURITÉ IMPORTANTES; A V E R T I S S E M E N T !
SAFETY WARNINGS EATON Powerware ® 9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com 4 Consignes de Sécurité CONSIGNES DE SÉCURITÉ IMPORTANTES CONSERVER CES INSTRUCTIONS Ce manuel comporte des instructions importantes que vous êtes invité à suivre lors de toute procé...
Page 11 - Advertencias de Seguridad; INSTRUCCIONES DE SEGURIDAD IMPORTANTES; P E L I G R O
SAFETY WARNINGS EATON Powerware ® 9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com 5 Advertencias de Seguridad INSTRUCCIONES DE SEGURIDAD IMPORTANTES GUARDE ESTAS INSTRUCCIONES Este manual contiene instrucciones importantes que debe seguir durante la instalación y ...
Page 13 - Chapter 3; The Powerware 9355 has the following power connections:; To hardwire the Tie Cabinet:
EATON Powerware ® 9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com 7 Chapter 3 Tie Cabinet Installation The Powerware 9355 has the following power connections: S 3-phase (L1, L2, and L3), neutral, and ground connection for rectifier/bypass input S 3-phase (L1, L2, ...
Page 14 - Figure 2. Tie Cabinet Front Cover
TIE CABINET INSTALLATION EATON Powerware ® 9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com 8 5. Remove the Tie Cabinet front cover (see Figure 2). Figure 2. Tie Cabinet Front Cover 6. Remove the internal covers to gain access to the breakers (see Figure 3). Figure...
Page 15 - punch or similar device.; Figure 4. Tie Cabinet Bypass Breaker; Mount the Tie Cabinet to the wall and install the conduit.
TIE CABINET INSTALLATION EATON Powerware ® 9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com 9 7. Punch holes for the conduit (AC input, UPS output, load connection, andmaintenance bypass contact wires) using a Greenlee ® punch or similar device. 8. Verify that the ...
Page 16 - From each UPS, remove the UPS front door.; Figure 5. UPS Front View; Remove the UPS conduit landing box from the rear panel and retain.
TIE CABINET INSTALLATION EATON Powerware ® 9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com 10 10. From each UPS, remove the UPS front door. 11. Verify that the UPS input circuit breaker is in the OFF position. 12. Verify that each UPS battery circuit breaker is in...
Page 17 - Hardwire the UPS input terminations.; Table 1. Terminal Block Wiring
TIE CABINET INSTALLATION EATON Powerware ® 9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com 11 18. Hardwire the UPS input terminations. See Table 1 for specifications and Figure 6 for a detailed view of the UPSterminal block. NOTE Input neutral must be wired for pr...
Page 18 - Figure 6. UPS Terminal Block
TIE CABINET INSTALLATION EATON Powerware ® 9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com 12 Jumpers(remove threewires fordual-feed) Input TerminalBlockL1, L2, L3, N, N Output TerminalBlockL1, L2, L3, N, N Remote DC(battery)DC +, DC – MaintenanceBypass AuxiliaryC...
Page 19 - Repeat Steps 11 through 19 for each UPS.; Figure 7. UPS Output to Tie Cabinet Wiring
TIE CABINET INSTALLATION EATON Powerware ® 9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com 13 19. Hardwire the output terminations from the UPS to the Tie Cabinet (see Figure 7). 20. Repeat Steps 11 through 19 for each UPS. Neutral Ground Line 1 Line 2 Line 3 Figu...
Page 20 - Figure 8. Load Connections
TIE CABINET INSTALLATION EATON Powerware ® 9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com 14 21. Hardwire the load to the Tie Cabinet (see Figure 8). Neutral Line 1 Ground Line 2 Line 3 Maintenance BypassWiring to UPS TB4 Figure 8. Load Connections
Page 21 - Figure 9. Parallel Wiring Diagram; Reinstall the UPS wiring access cover.
TIE CABINET INSTALLATION EATON Powerware ® 9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com 15 22. Wire the maintenance bypass auxiliary contacts and terminate to themaintenance bypass wires in the Tie Cabinet (see Figure 6 on page 12). Connect the black and the re...
Page 22 - Figure 10. Bypass AC Input Wiring; Verify the phase rotation for each UPS and the bypass input.
TIE CABINET INSTALLATION EATON Powerware ® 9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com 16 25. Wire the AC input to the bypass breaker (see Figure 10). Line 1 Line 2 Line 3 Figure 10. Bypass AC Input Wiring 26. Verify the phase rotation for each UPS and the byp...
Page 25 - Chapter 4; This section describes the Powerware Hot Sync CAN Bridge Card.; Figure 12. Communication Options and Control Terminals; Figure 13. Powerware Hot Sync CAN Bridge Card
EATON Powerware ® 9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com 19 Chapter 4 Installing Options This section describes the Powerware Hot Sync CAN Bridge Card. For other options, such as additional X-Slot t cards, Powerware LanSafe ® Power Management Software, re...
Page 26 - To install the Powerware Hot Sync CAN Bridge Card:; Figure 14. Communication Wiring Access
INSTALLING OPTIONS EATON Powerware ® 9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com 20 To install the Powerware Hot Sync CAN Bridge Card: 1. Remove the UPS front door. 2. Remove the communication wiring access plate from the UPS rear panel andpunch a hole in it u...
Page 27 - If only two UPSs are paralleled, then set both cards to Pins 1 and 2.; Repeat Steps 1 through 6 for each UPS.
INSTALLING OPTIONS EATON Powerware ® 9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com 21 4. Set the jumper pins on the Powerware Hot Sync CAN Bridge Card according tothe parallel configuration (see Figure 15): S If only two UPSs are paralleled, then set both cards ...
Page 28 - Figure 16. Routing the Cables; Connect SHIELD Pin 10 on all cards together.
INSTALLING OPTIONS EATON Powerware ® 9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com 22 8. Route the wiring through the conduit from the communication wiring accessplate to the opening between the two X-Slot communication bays on each UPS(see Figure 16). Figure 16...
Page 29 - Figure 17. Installing Communication Cables
INSTALLING OPTIONS EATON Powerware ® 9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com 23 10. Route the pull-chain wiring through the middle of the fan section and secure inthe cable clips for each UPS (see Figure 17). Figure 17. Installing Communication Cables
Page 30 - C A U T I O N
INSTALLING OPTIONS EATON Powerware ® 9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com 24 11. Wire the pull-chain wiring to Signal Input 2 on each UPS and daisy chain thewiring to each UPS as shown in Figure 18. Be sure to check correct polarity: S Connect Pull-Chai...
Page 31 - Figure 18. CAN Bridge Card and Pull-Chain Wiring
INSTALLING OPTIONS EATON Powerware ® 9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com 25 ALARM 1ALARM 2BPO RS232 RELAY OUTPUT PULL CHAIN OUTP PARALLEL ONLY X27 X57 X43 X-- NP X52-- NC X45 X44 ALARM 1ALARM 2BPO RS232 RELAY OUTPUT PULL CHAIN OUTP PARALLEL ONLY X27 X5...
Page 33 - Chapter 5; Local Distributor; Call your local service representative
EATON Powerware ® 9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com 27 Chapter 5 Service and Support If you have any questions or problems with the UPS, call your Local Distributor or the Help Desk at one of the following telephone numbers and ask for a UPS technica...