Powerware ® FERRUPS FE/QFE UPS Installation Guide 500 VA–18 kVA, 50 and 60 Hz www.powerware.com
Class A EMC Statements FCC Part 15 NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference whenthe equipment is operated in a co...
i Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com T ABLE OF C ONTENTS 1 Introduction 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Plug-Receptacle Installation 1 . . . . . . . . . . . . . . . . . ...
Table of Contents ii Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com
1 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com C H A P T E R 1 I NTRODUCTION The Powerware 9 FERRUPS uninterruptible power system (UPS) is available in plug-receptacle or hardwired models. The plug-receptaclemodels have an input plug and receptacles on ...
Introduction 2 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com : If you purchased an external battery cabinet, see Chapter 7, “BatteryCabinet Installation” for wiring connections. : Complete the phase check as described in Chapter 8, “Phase Check.” : Conti...
3 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com C H A P T E R 2 S AFETY W ARNINGS Read the following precautions before you install the UPS. I M P O R T A N T S A F E T Y I N S T R U C T I O N S SAVE THESE INSTRUCTIONS. This manual contains important ins...
Safety Warnings 4 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com C A U T I O N : Batteries can present a risk of electrical shock or burn from high short-circuitcurrent. Observe proper precautions. Servicing should be performed by qualifiedservice personn...
Safety Warnings 5 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com A D V A R S E L : Batterier kan udgøre en fare for elektrisk stød eller forbrændinger forårsaget af højkortslutningsspænding. De korrekte forholdsregler bør overholdes. : Korrekt bortskaffel...
Safety Warnings 6 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com O P G E L E T : Batterijen kunnen gevaar voor elektrische schok of brandwonden veroorzaken alsgevolg van un hoge kortsluitstroom. Volg de desbetreffende aanwijzingen op. : De batterijen moet...
Safety Warnings 7 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com V A R O : Akusto saattaa aiheuttaa sähköiskun tai syttyä tuleen, jos akusto kytketäänoikosulkuun. Noudata asianmukaisia ohjeita. : Akusto täytyy hävittää säädösten mukaisella tavalla. Noudat...
Safety Warnings 8 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com A T T E N T I O N ! : Les batteries peuvent présenter un risque de décharge électrique ou de brûlure pardes courts-circuits de haute intensité. Prendre les précautions nécessaires. : Une mis...
Safety Warnings 9 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com V O R S I C H T ! : Batterien können aufgrund des hohen Kurzschlußstroms Elektroschocks oderVerbrennungen verursachen. Die entsprechenden Vorsichtsmaßnahmen sindunbedingt zu beachten. : Die ...
Safety Warnings 10 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com : Ãéá íá óõìöùíåß ìå ôá äéåèíÞ ðñüôõðá êáé ôïõò êáíïíéóìïýò êáëùäßùóçò, ôï ñåýìá äéáññïÞò ðñïò ôç ãç ïëüêëçñïõ ôïõ åîïðëéóìïý, ðïõ åßíáé óõíäåäåìÝíïò ìå ôçí Ýîïäï ôïõ óõãêåêñéìÝíïõ UPS, äåí...
Safety Warnings 11 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com : Per ridurre il rischio di incendio o di scossa elettrica, installare il gruppo statico dicontinuità in un ambiente interno a temperatura ed umidità controllata, privo diagenti contaminant...
Safety Warnings 12 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com : Alt utstyr som er forbundet med utgangen av denne UPS’en må ikke ha en sterkeretotal lekkasjestrøm enn 1,5 milliampere for å være i overensstemmelse medinternasjonale standarder og forkab...
Safety Warnings 13 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com P E R I G O : As baterias podem apresentar o risco de choque elétrico, ou queimadurasprovenientes de alta corrente de curto-circuito. Observe as instruções adequadas. : Siga as instruções a...
Safety Warnings 14 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com : Для обеспечения соблюдения требований международныхстандартов и требований к разводке электрических цепей,суммарная величина тока утечки на землю всего оборудования,подключенного к выходу...
Safety Warnings 15 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com : Para reducir el riesgo de incendio o de choque eléctrico, instale este SIE en unlugar cubierto, con temperatura y humedad controladas, libre de contaminantesconductores. La temperatura am...
Safety Warnings 16 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com : Minska risken för brand eller elektriska stötar genom att installera dennaUPS-enhet inomhus, där temperatur och luftfuktighet är kontrollerade och där ingaledande föroreningar förekommer....
17 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com C H A P T E R 3 S ETUP This chapter explains the requirements for setting up the UPS: : UPS, battery cabinet, and bypass switch dimensions : Equipment clearances : Location requirements : Moving the UPS an...
Setup 18 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com Table 2. FERRUPS FE/QFE 4.3–18 kVA Dimensions Dimensions (See Figure 1) UPS Model Height (D) Width (E) Depth without Internal Bypass (F) Depth with Internal Bypass Switch (F) 4.3 kVA and 5.3 kVA 29.5...
Setup 19 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com D D A B BPE-01 BPE-02, 04, and 05 C E A B C E Figure 3. Bypass Switch Dimensions Equipment Clearances All cabinet sizes require the following clearances to allow for servicingand adequate ventilation...
Setup 20 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com J I I G G H H Figure 4. Installation and Service Clearances Location Requirements Install the FERRUPS as close as possible to the equipment to beprotected. If the UPS is more than 25 ft (7.6m) from t...
Setup 21 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com Storage and Operating Environment Storage Temperature: Store the batteries (in the UPS or external battery cabinet) at - 20 ° to + 40 ° C ( - 4 ° to + 104 ° F). Batteries will have a longer shelf lif...
23 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com C H A P T E R 4 E LECTRICAL I NSTALLATION NOTE If you have a plug-receptacle unit, continue to “Battery Cabinet Installation” on page 53 to install optional battery cabinets or to the startup section in th...
Electrical Installation 24 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com Bypass Switches Bypass switches are available in two types: external (a separate cabinetthat is wall-mounted) or internal (attached to the back of the UPS). Thebypass switch has thr...
Electrical Installation 25 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com Table 7 and Table 8 show the bypass switch models available for theFERRUPS UPS. Table 7. External Bypass Switch Specifications Model Number Ratings (UL/CSA) Continuous Ratings (TÜV)...
29 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com C H A P T E R 5 E XTERNAL B YPASS S WITCH I NSTALLATION W A R N I N G Only qualified service personnel (such as a licensed electrician) should perform thehardwired installation. Risk of electrical shock. C...
External Bypass Switch Installation 31 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com 2. Review the installation wiring diagram and applicable notes tofind the proper circuit breaker size for your installation. In theUS, see Table 10 to size the wire. In ...
External Bypass Switch Installation 32 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com C A U T I O N To prevent electrical shock or damage to your equipment, verify that the UPS ON/OFFswitch is in the OFF position before you remove the UPS front cover pane...
External Bypass Switch Installation 33 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com 8. Find the terminal strip inside the bypass switch. Using the labelon the back of the switch’s lower front cover panel, wire theterminal strip and tighten all connectio...
External Bypass Switch Installation 34 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com 10. If your UPS does not have an external battery cabinet(s),continue to “Phase Check” on page 65. If your UPS has an external battery cabinet(s), continue to“Battery Ca...
External Bypass Switch Installation 36 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com QFE: 50 Hz 120 Vac Input and Output ORFE: 60 Hz 120 Vac Input and Output ORFE 1.15–3.1 kVA only: 60 Hz 220 Vac Input and Output (with single-voltage output) For 220 Vac,...
External Bypass Switch Installation 37 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com 60 Hz 208 Vac or 240 Vac Input - 120/208 Vac or 120/240 Vac Output For 208 Vac, use only a BBM switch. Figure 9. FE 500 VA–3.1 kVA UPS with External Bypass Switch Table ...
External Bypass Switch Installation 38 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com 60 Hz 208 or 480 Source/240 Vac Input - 120/240 Vac Output (with Transformer) Figure 10. FE 500 VA–3.1 kVA UPS with External Bypass Switch Table 15. Minimum Recommended ...
External Bypass Switch Installation 39 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com 50 Hz 220, 230, or 240 Vac Input and Output Figure 11. QFE 500 VA–3.1 kVA UPS with External Bypass Switch Table 16. Input Current - Size Overcurrent Protection According...
External Bypass Switch Installation 40 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com 60 Hz 120 Vac Input - 120 Vac Output Figure 12. FE 4.3–7 kVA UPS with External Bypass Switch Table 17. Minimum Recommended Circuit Breakers for 120 Vac Charger 4.3 kVA 5...
External Bypass Switch Installation 41 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com 60 Hz 208 Vac or 240 Vac Input - 120/208 Vac or 120/240 Vac Output For 208 Vac, use only a BBM switch. Figure 13. FE 4.3–18 kVA UPS with External Bypass Switch Table 18....
External Bypass Switch Installation 42 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com 60 Hz 208 or 480 Source/240 Vac Input - 120/240 Vac Output (with Transformer) Figure 14. FE 4.3–18 kVA UPS with External Bypass Switch Table 19. Minimum Recommended Circ...
External Bypass Switch Installation 43 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com QFE: 50 Hz 220, 230, or 240 Vac Input and Output ORFE: 60 Hz 220 Vac Input and Output For FE 60 Hz 220 Vac, use only a BBM switch. Figure 15. FE or QFE 4.3–18 kVA UPS wi...
45 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com C H A P T E R 6 I NTERNAL B YPASS S WITCH I NSTALLATION W A R N I N G Only qualified service personnel (such as a licensed electrician) should perform thehardwired installation. Risk of electrical shock. C...
Internal Bypass Switch Installation 46 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com 2. Review the installation wiring diagram and applicable notes tofind the proper circuit breaker size for your installation. In theU.S., see Table 22 to size the wire. I...
Internal Bypass Switch Installation 48 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com Installation Wiring Diagrams for Internal Bypass Switches The following notes are referenced in the internal bypass switch wiringdiagrams (Figure 17 through Figure 20). ...
Internal Bypass Switch Installation 49 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com NOTE 10 The load fuse or circuit breaker should be sized to match the load current requirements. NOTE 11 For 208 Vac, use a step-up transformer For 480 Vac, use a step-d...
Internal Bypass Switch Installation 50 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com 60 Hz 208 Vac or 240 Vac Input - 120/208 Vac or 120/240 Vac Output For 208 Vac, use only a BBM switch. Figure 18. FE 4.3–18 kVA UPS with Internal Bypass Switch Table 24....
Internal Bypass Switch Installation 51 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com 60 Hz 208 or 480 Source/240 Vac Input - 120/240 Vac Output (with Transformer) Figure 19. FE 4.3–18 kVA UPS with Internal Bypass Switch Table 25. Minimum Recommended Circ...
Internal Bypass Switch Installation 52 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com QFE: 50 Hz 220, 230, or 240 Vac Input and OutputFE: 60 Hz 220 Vac Input and Output For FE 60 Hz 220 Vac, use only a BBM switch. Figure 20. FE or QFE 4.3–18 kVA UPS with ...
53 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com C H A P T E R 7 B ATTERY C ABINET I NSTALLATION NOTE If you have an optional Floor Saver battery cabinet, see the Floor Saver instructions that came with your FERRUPS UPS. W A R N I N G Only qualified serv...
Battery Cabinet Installation 54 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com : Align the cables on the battery terminals so that the cable lug will not contact anypart of the cabinet even if the battery is moved. Keep the cable away from anysharp metal ...
Battery Cabinet Installation 55 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com Table 27. Nominal DC Battery Voltage Models Nominal Battery Voltage QFE 500 VA, 700 VA, 850 VA, 1.15 kVA, and 1.4 kVA 12 Vdc FE 500 VA, 700 VA, and 850 VA 24 Vdc QFE 1.8 kVA, 2...
Battery Cabinet Installation 56 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com Installing and Connecting the Batteries 1. Use the battery installation diagram that came with your UPSbatteries and cabinet as you follow the steps below. 2. Place the battery...
Battery Cabinet Installation 57 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com 4. The battery cabinet ground (or earth) must be connected to theUPS chassis ground (or earth). You must make a good connection to the battery cabinetchassis ground (or earth)....
Battery Cabinet Installation 59 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com NOTE If you have an external DC disconnect switch between the UPS and batteries, see the instructions that came with your disconnect switch. 8. Clean the cable and battery post...
Battery Cabinet Installation 60 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com Square: Torque to 17 in lb or 1.9 Nm.(BAT-0058) Modified Square: Torque to 35 in lb or 3.9 Nm.(BAT-0065) Screw Posts: Torque to 85 in lb or 9.6 Nm.(BAT-0071) Figure 23. Battery...
Battery Cabinet Installation 62 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com NOTE If you have an external DC disconnect switch, see the instructions that came with your disconnect switch. Now, turn the DC ON/OFF switch on the battery cabinet(s) tothe ON...
Battery Cabinet Installation 63 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com Replacing the Batteries C A U T I O N Only qualified service personnel (such as a licensed electrician) should perform thebattery installation. Risk of electrical shock. Consid...
Battery Cabinet Installation 64 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com 3. Handle used batteries with care! Assume that old batteries are fully charged. Use the sameprecautions you would use when handling a new battery. Donot short battery terminal...
65 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com C H A P T E R 8 P HASE C HECK After all hardwired connections are complete (including external batterycabinets, if applicable), complete the phase check using the followingsteps. You will need an AC voltme...
Phase Check 66 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com 10–18 kVA: If you have an external battery cabinet(s) with a DC switch, turn the switch to the ON position. 6. Turn the UPS ON/OFF switch to the ON position. The switchis located on the back of...
Phase Check 68 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com 10. Measure the AC voltage between the following points on theterminal strip. This reading must be no more than 1 Vac; if it is,call your service representative. Internal Bypass Switch N (AC to...
Phase Check 69 Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com 16. Turn off the DC switch, if applicable, according to your UPSmodel: 500 VA–3.1 kVA: If you have an external battery cabinet(s) with a DC switch, turn the switch to the OFF position. 4.3–7 kV...
Powerware Manuals
-
Powerware 5110
Manual
-
Powerware 9315 UPS
Manual
-
Powerware 9125
Manual
-
Powerware 100160 kVA
Manual
-
Powerware 700 VA
Manual
-
Powerware 10001500 VA
Manual
-
Powerware 1085
Manual
-
Powerware 9315
Manual
-
Powerware 10001100 kVA
Manual
-
Powerware 2500
Manual
-
Powerware 15 KVA
Manual
-
Powerware IPK-0318
Manual
-
Powerware 5125
Manual
-
Powerware 5115A USB
Manual
-
Powerware 5140
Manual
-
Powerware IPK-0320
Manual
-
Powerware 3115
Manual
-
Powerware 5105
Manual
-
Powerware 6000 VA
Manual
-
Powerware Powerware 9390
Manual