Page 2 - Class A EMC Statements; Requesting a Declaration of Conformity
Class A EMC Statements FCC Part 15 NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interferencewhen the equipment is operated in a co...
Page 3 - Table of Contents
EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com i Table of Contents 1 Introduction 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Installing the Modbus Card 3 . . . . . . . . . . . . . . . . . . ....
Page 5 - Chapter 1; Configuration Port; Figure 1. The Modbus Card
EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 1 Chapter 1 Introduction The Eaton ® Powerware ® Modbus ® Card is an X-Slot ® connectivity device that allows you to continuously and reliably monitor the UPSs in yourBuilding Management System (BMS). The card uses the ...
Page 6 - Power Meter; Ethernet; Figure 2. UPS Integrated with RS-485 Network
INTRODUCTION EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 2 RS-485 Network Power Meter PLC UPS with Modbus Card Ethernet Gateway Building Management Software Ethernet -270.6 -270.6 Figure 2. UPS Integrated with RS-485 Network
Page 7 - Chapter 2; Powerware Expansion; Inspecting the Equipment
EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 3 Chapter 2 Installing the Modbus Card The Modbus Card is available: S as a separate card for use with UPSs that have an X-Slot S factory-installed in a Powerware Expansion Chassis Use the following sequence for install...
Page 8 - Four-Wire Communication; Figure 3. Removing the Modbus Card
INSTALLING THE MODBUS CARD EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 4 Four-Wire Communication The factory-default setting for the Modbus Card is for two-wirecommunication. To change the default setting, adjust the jumpers on theModbus Card. C A U T I O N To pr...
Page 9 - Figure 4. Modbus Card Jumpers; Reinstall the Modbus Card into the Powerware Expansion Chassis.
INSTALLING THE MODBUS CARD EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 5 3. Change the J9 and J10 jumpers to the desired setting as shown inFigure 4. 1 1 J11 2 3 4 5 6 O N S2 J7 J8 J10 J9 J9 J10 Four-Wire 1 1 J9 J10 Two-Wire (Default) 1 1 Figure 4. Modbus Card Ju...
Page 10 - Installing the Modbus Card into an X-Slot; Figure 5. Removing the Single-Port Module; Install the Modbus Card into the X-Slot on the UPS.
INSTALLING THE MODBUS CARD EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 6 Installing the Modbus Card into an X-Slot C A U T I O N To prevent electrostatic discharge (ESD), place one hand on an unpainted metal surface suchas the UPS rear panel. 1. Remove the X-Slot...
Page 11 - Chapter 3; Master Device
EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 7 Chapter 3 Wiring the Modbus Card The Modbus Card provides an easy path for integrating a PowerwareUPS into an RS-485 Modbus network and also provides isolation of thecommunication between the UPS and the RS-485 Modbus...
Page 12 - RS-485 Terminal Strip
WIRING THE MODBUS CARD EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 8 Four-Wire Networks The Modbus Card also supports four-wire, half-duplex, RS-485 networks.Figure 7 shows a detailed view of four-wire connections using theModbus Card terminal strip. Slave Device...
Page 13 - Table 1. RS-485 Terminal Strip Pin Assignments; Pin Number; Signal common
WIRING THE MODBUS CARD EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 9 For four-wire networks. All four RS-485 network signals including TxD(+), RxD(+), TxD(–), and RxD(–) must be connected to the terminal strip asillustrated in Table 1. Verify that the Modbus Card...
Page 14 - Termination
WIRING THE MODBUS CARD EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 10 3 8 7 9 1 6 2 4 5 Figure 9. RS-485 DB-9 Pin Numbers Table 2. RS-485 DB-9 Pin Assignments Pin Number Modbus Card Signal Name RS-485 Network Signals Master Signal Name 1 RxD(+) TxD(+) 2 TxD(+) Rx...
Page 15 - ON; Figure 10. S2 Termination Configuration; Biasing Resistors; C A U T I O N
WIRING THE MODBUS CARD EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 11 1 J11 S2 J7 J8 J10 J9 RxD(–) Pull Down (620 Ω) RxD Terminator (120 Ω) Four-Wire Two-Wire ON *OFF 1 2 3 4 5 6 TxD(–) Pull Down (620 Ω) TxD(+) Pull Up (620 Ω) TxD Terminator (120 Ω) RxD(+) Pull U...
Page 17 - Chapter 4; To use the configuration screens for the Modbus Card, you need:; Configuring the Modbus Card; Figure 12. Configuration Port
EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 13 Chapter 4 Modbus Card Configuration The Modbus Card has an RS-232 configuration port that you can accesswith a terminal or a computer equipped with a terminal emulationprogram. To use the configuration screens for th...
Page 18 - Figure 13. Configuration Screen; Verify that the UPS has input power and is turned on.; BD; followed by a
MODBUS CARD CONFIGURATION EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 14 2. Press [Enter]. The Configuration screen appears (see Figure 13). Powerware Modbus CardVersion 1.00 (1-16-02) Current Configuration: Baud Rate: 9600 Slave Address: 29 ---------------------...
Page 19 - AD
MODBUS CARD CONFIGURATION EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 15 4. To configure the slave address, type AD followed by a space and node (1 through 247) and press [Enter]. The default is 29. Thissetting affects both RS-232 and RS-485 Modbus connections. 5...
Page 21 - Chapter 5; Generating Modbus Data; Figure 14. Configuration Port
EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 17 Chapter 5 Integrating the UPS Powerware provides a software tool named Modbus Profiler thatcreates a Modbus register map specifically for your Powerware UPS.Refer to the Master Modbus Register Map for a complete list...
Page 22 - profiler; Example Modbus Profiler Output Files; Register; Registers 1–16 are mutually exclusive.
INTEGRATING THE UPS EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 18 5. Run profiler from the command prompt or double-click profiler.exe from Microsoft Windows Explorer. By default, Modbus Profiler uses the communication port specifiedin the [Connection] section o...
Page 23 - Unit
INTEGRATING THE UPS EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 19 Unit Format Value Name Register 113 Rectifier Input Status 1 BOOL Status 114 Bypass Status 0 BOOL Status 115 Bypass Input Status 1 BOOL Status 116 Input Circuit Breaker Status (CB1) 1 BOOL Status ...
Page 27 - Chapter 6; Problem; profiler comX
EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 23 Chapter 6 Troubleshooting Problem Possible Cause Corrective Action The Modbus Profilertool does notgenerate the fil fil The wrong communication port number wasentered in the profiler comX command. Verify the correct ...
Page 28 - Figure 15. Modbus Card Default Jumper Settings
TROUBLESHOOTING EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 24 1 J11 2 1 3 4 5 6 O N S2 J7 J8 J10 J9 S2 Termination (Default ”OFF”) J11 Half Duplex Full-Duplex (Default) 1 1 J9 J10 Two-Wire (Default) 1 1 Two-Wire/Four-Wire J7 J8 DCE DCE/DTE (Default) 1 1 Figure 1...
Page 29 - Service and Support; Local Distributor; Call your local service representative
TROUBLESHOOTING EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 25 Service and Support If you have any questions or problems with the Modbus Card, call your Local Distributor or the Help Desk at one of the following telephone numbers and ask for a Modbus Card technic...