Page 3 - òÿå; II; – A POTENTIAL HAZARD THAT WILL CAUSE SERIOUS INJURY OR LOSS OF LIFE.
3 òÿå Do not attempt to install the generator yourself. Extremely high and dangerous electrical voltages are present in utility power source lines and in generator load leads when the unit is running. Therefore, be sure to turn OFF all power voltage supplies at their source before attempting to comp...
Page 4 - Units with broken or missing parts, without
200-2667 4 The National Electrical Code (NEC) requires the frame and external electrically conductive parts of the generator to be connected to an approved earth ground. Keep a fire extinguisher near the generator at all times. Extinguishers rated "ABC" by the National Fire Protection Associ...
Page 8 - Note: Check your local; NOTE: Utility wiring from the house to power the; Check your local building; Do not plant trees or plants close to the unit.
200-2667 8 Once installation planning is complete and all necessary local permits are granted, installation of thegenerator may begin. Within the following sectiongeneral recommendations are given for installing thegenerator. However, installations are affected by localsite conditions, regional cons...
Page 9 - WA
9 200-2667 The generator is supplied with an integral molded plastic base for use as an installation pad. Use of thisbase is intended to minimize installation cost byeliminating the need for a poured concrete pad. A pad of crushed gravel a minimum of three inches thick is recommended as a base to se...
Page 11 - Once the generator is anchored in its final position, it; Select proper power output wire; To connect the wires, strip; FIELD CONNECTIONS; TO BE PERFORMED BY A
11 200-2667 Once the generator is anchored in its final position, it is ready for electrical connections. The generator issupplied with two terminal blocks for connection of threedistinct electrical circuits; main line output power, utilitypower input and generator start signal. Main line outputpowe...
Page 12 - A receptacle is provided with the generator to power; Select proper utility supply wire size; When the control panel mode switch is placed in the
200-2667 12 A receptacle is provided with the generator to power the battery charger for reliable starting. It is alsointended to power an optional block heater if that optionis desired. Connection of this circuit to a power supplythat is only present when normal utility power is suppliedis recommen...
Page 14 - FUEL CONSUMPTION TABLE
200-2667 14 The engine driving the generator is engineered to provide reliable power on either Liquefied Propane Vapor(LPG) or Natural Gas. For proper operation on thesefuels, it is important to deliver gas with adequate energycontent, at sufficient pressure and flow rate. Thisgenerator is designed ...
Page 16 - To insure reliable starting in most weather; or 26R battery; , with a minimum recommended rating of; Use tools with insulated handles.
200-2667 16 To insure reliable starting in most weather conditions, it is important to properly match a battery tothe requirements of the generator. The generator uses a12 Volt, direct current, negative ground control systempowered by an automotive style lead acid battery.Successful engine starting ...
Page 23 - UPPER LIMIT
23 200-2667 Prior to checking the oil level, start the generator by pressing the MANUAL Mode button on the control panel.Allow the generator to run for one or two minutes, thenshut it down by pressing the OFF button on the controlpanel. After the engine comes to a stop let the engineset for a couple...
Page 24 - Chart C
200-2667 24 Selection of the correct grade and type of engine oil greatly affects the performance of the generator,especially when starting. Before selecting replacementoil for an oil change, consider the anticipated operatingconditions the generator may be exposed to. Choose theappropriate weight o...
Page 26 - Table A
200-2667 26 Engine spark plugs are an important part of the engine ignition system. Worn or incorrectly adjustedspark plugs can negatively affect engine starting andoperation. Therefore, it is important to inspect and regap,or replace the engine spark plugs as indicated in theservice interval table....
Page 27 - Do not place a cover over the generator.; Over time, normal engine operation leads to wear in
27 200-2667 Proper cooling of the generator is vital to maintain performance and prevent equipment failure. Blockedcabinet openings or other airflow obstructions arepotential fire hazards and can cause failures.Periodically inspect generator cabinet openings and theengine oil cooler for blockages. D...
Page 28 - SYMPTOM
200-2667 28 T T T T R R R R O O O O U U U U B B B B L L L L E E E E S S S S H H H H O O O O O O O O T T T T II II N N N N G G G G SYMPTOM POSSIBLE CAUSE CORRECTIVE ACTION Engine does not crank Loose battery cables • Check all battery cable connections. Defective battery • Test battery. Replace as ne...
Page 31 - Powermate Corporation, Product; EXCLUSIONS AND LIMITATIONS:
31 200-2667 POWERSTATION® Automated Power System Limited Warranty Warranty: Powermate Corporation warrants to the original consumer purchaser in the U.S. or Canada that it will repair or replace any parts or components found to be defective in material or workmanship. Theproduct must be properly ins...