Page 2 - OMEGAnet
It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations that apply. OMEGA is constantly pursuing certification of its products to the European New Approach Directives. OMEGA will add the CE markto every appropriate device upon certification. The information contained in...
Page 3 - TABLE OF CONTENTS
TABLE OF CONTENTS Part 1: Introduction ............................................................................................ 2 1.1 Description ................................................................................. 2 1.2 Safety Considerations ...........................................
Page 5 - NOTES, WARNINGS and CAUTIONS; Provides you with information that is important to successfully
NOTES, WARNINGS and CAUTIONS Information that is especially important to note is identified by following labels: • NOTE • WARNING or CAUTION• IMPORTANT• TIP NOTE: Provides you with information that is important to successfully setup and use the Programmable Digital Meter. CAUTION or WARNING: Tells y...
Page 6 - INTRODUCTION
PART 1 INTRODUCTION 1.1 Description This device can be purchased as monitor (read process value only) or asa controller. • The iSeries controller offers unparalleled flexibility in process measurement.Each unit allows the user to select the input type, from 10 thermocoupletypes (J, K, T, E, R, S, B,...
Page 7 - Safety Considerations; Do not expose this instrument to rain or moisture.; EMC Considerations; Whenever EMC is an issue, always use shielded cables.
1.2 Safety Considerations This device is marked with the international caution symbol. It is importantto read this manual before installing or commissioning this device as itcontains important information relating to Safety and EMC(Electromagnetic Compatibility). This instrument is a panel mount dev...
Page 9 - SETUP; Figure 2.1 Front Panel Display; PV; * See Part 3 Operation: Configuration Mode
PART 2 SETUP 2.1 Front Panel Figure 2.1 Front Panel Display Table 2.1 Front Panel Annunciators 1 Output 1/Setpoint 1/ Alarm 1 indicator 2 Output 2/Setpoint 2/ Alarm 2 indicator °C °C unit indicator °F °F unit indicator PV Upper Display shows the Process Value SV Lower Display shows the Setpoint 1 Va...
Page 10 - POWER; OUTPUT 2; Based on one of the following models:; OPTION; Based on one of the following models:
2.2 Rear Panel Connections The rear panel connections are shown in Figures 2.2 and 2.3. Figure 2.2 Rear Panel Power and Output Connections Figure 2.3 Rear Panel Input Connections Table 2.2 Rear Panel Connector POWER AC/DC Power Connector: All models INPUT Input Connector: All models TC, PR (Process)...
Page 11 - Electrical Installation; Do not connect power to your device until you have completed all; Figure 2.4 Main Power Connections; FUSEConnector; Power
2.3 Electrical Installation 2.3.1 Power Connections Caution: Do not connect power to your device until you have completed all input and output connections. Failure to do so may result in injury! Connect the main power connections as shown in Figure 2.4. Figure 2.4 Main Power Connections Table 2.3 Fu...
Page 12 - Figure 2.5 Thermocouple Wiring Hookup; TYPEInput Connector; Table 2.4 TC Wire Color Chart
2.3.2 Thermocouple The figure below shows the wiring hookup for any thermocouple type. Forexample, for Type K hookup, connect the yellow wire to the "2" terminal and thered wire to the "1(-)" terminal. When configuring your controller, select Thermocouple and ThermocoupleType in the ...
Page 13 - 00 ohm Wiring Hookup
9 2.3.3 Two/Three/Four-Wire RTD The figures below show the input connections and input connector jumpers(shown in bold lines) required to hookup a 2-, 3- or 4-wire RTD. Figure 2.6 a) RTD-1000 ohm and b) RTD-100 ohm Wiring Hookup 500 ohm Wiring Hookup The two-wire connection is simplest method, but d...
Page 14 - is 14 kΩ for 10 V process input.
10 2.3.4 Process Current The figure below shows the wiring hookup for Process Current 0 – 20 mA. Figure 2.7 Process Current Wiring Hookup (Internal and External Excitation) When configuring your instrument, select Process Type in the Input Type Menu(see Part 3). 2.3.5 Process Voltage The figure belo...
Page 17 - To change the color of the upper display, see; Use a jumper for GREEN or RED, never leave S1 open.; Figure 2.14 i/8 D Location of S1 and Selectable Jumper Positions
2.3.7 Dual Display Color Setup The dual display option allows the user to change the color of the upper andlower displays. To change the color of the upper display, see Section 3.2.15 (Display Color section). To change the color of the lower display follow the instructions below: The unit should be ...
Page 18 - OPERATION: Configuration Mode; Turning your Controller On for the First Time; RST; Table 3.1 Button Function in Configuration Mode; will reset the instrument prior to resuming Run Mode.
14 PART 3 OPERATION: Configuration Mode 3.1 Introduction The instrument has two different modes of operation. The first, Run Mode, isused to display values for the Process Variable, and to display or clear Peakand Valley values. The other mode, Menu Configuration Mode, is used tonavigate through the...
Page 20 - ERRo
16 3.2.1 ID Number SEE ID MENU SELECTION IN CONFIGURATION SECTION FORENABLE/DISABLE OR CHANGE ID CODE. If ID Code is Disabled or set as Default (0000) the menu will skip ID step to Setpoint Menu. If ID Code is set to Full Security Level and user attempts to enter the Main Menu, they will be prompted...
Page 22 - Figure 3.2 Flow Chart for Configuration Menu; Enter Configuration Menu:; CNFG; Figure 3.3 Flow Chart for Input Type Menu
18 3.2.3 Configuration Menu Figure 3.2 Flow Chart for Configuration Menu Enter Configuration Menu: Press a 1) Press a , if necessary, until CNFG prompt appear. Press d 2) Display advances to INPT Input Menu. Press a 3) Pressing and releasing a to scroll through all available menus of Configuration s...
Page 24 - ENTER INPUT TYPE MENU:
20 Input Type (RTD) ENTER INPUT TYPE MENU: Press a 1) Press a , if necessary, until CNFG prompt appears. Press d 2) Display advances to INPT Input Menu. Press d 3) Display flashes T.ç , RTD or PROC (Thermocouple, RTD or Process). If the displayed input type is RTD , press a to skip to step 6 ( RTD s...
Page 25 - Figure 3.4 Flow Chart for Reading Configuration Menu
21 Input Type (Process) ENTER INPUT TYPE MENU: Press a 1) Press a , if necessary, until CNFG prompt appears. Press d 2) Display advances to INPT Input Menu. Press d 3) Display flashes T.ç , RTD or PROC (Thermocouple, RTD or Process). If the displayed input type is PROC , press a to skip to step 6 ( ...
Page 27 - Reading Configuration (If Process was selected)
23 Reading Configuration (If Process was selected) INPUT/READING (SCALE AND OFFSET) SUBMENU: Input Voltage or Current can be converted or scaled into values appropriate forthe process or signal being measured. So, a reading may be displayed, forexample, in units of weight or velocity instead of in a...
Page 28 - Table 3.2 Conversion Table; RANGE
24 Conversion number is a coefficient of conversion between input valuesand real full display range (10000 counts shown as 9999). See Table 3.2below for proper conversion number. Table 3.2 Conversion Table RANGE CONVERSION NUMBER 100 mV 10000 / (100 x 1) = 100 1 V 10000 / (1000 x 1) = 10 10 V 10000 ...
Page 29 - Figure 3.5 Flow Chart for Alarm 1
25 3.2.6 Alarm 1 This unit is equipped with two physical outputs that can only be configured asfollows: Alarm 1 & Alarm 2, Alarm 1 & Output 2, Output 1 & Alarm 2, Output 1 & Output 2, Analog Out 1 & Alarm 2, Analog Out 1 & Output 2 . Analog Out available only if Analog Output...
Page 32 - ALARM 1 LOW VALUE SUBMENU:; ALARM 1 HI VALUE SUBMENU:
28 ALARM ENABLE/DISABLE AT POWER ON: Press d 15) Display flashes previous selection. Press b to ENBL enable or DSBL disable. Press d 16) Display shows STRD stored message. momentarily and then advances to ALR.L only if it was changed, otherwise press a to advance to the ALR.L Alarm 1 Low Value Subme...
Page 33 - ENTER ANALOG OUTPUT MENU:
29 3.2.7 Analog Output (Retransmission) Analog Output can be configured as Retransmission or Control outputs.In this section we will discuss Retransmission Output. This unit is equipped with two physical outputs that can only be configured asfollows: Alarm 1 & Alarm 2, Alarm 1 & Output 2, Ou...
Page 36 - Alarm must be DISABLED if Ramp is ENABLED.; Figure 3.7 Flow Chart for Alarm 2; DSBL; Disabled; LOOP; Enabled
32 3.2.8 Alarm 2 This unit is equipped with two physical outputs that can only be configured asfollows: Alarm 1 & Alarm 2, Alarm 1 & Output 2, Output 1 & Alarm 2, Output 1 & Output 2, Analog Out 1 & Alarm 2, Analog Out 1 & Output 2 . Analog Out available only if Analog Output...
Page 37 - Figure 3.8 Flow Chart for Loop Break Time/Field Calibration; ENTER LOOP BREAK TIME MENU:; Loop Break; is completed successfully, otherwise; LOOP BREAK TIME VALUE SUBMENU:; Loop Break Time Value; allows the user to determine the time interval in MM:SS (from; READING ADJUST SUBMENU:; advances to
33 3.2.9 Loop Break Time/Field Calibration Figure 3.8 Flow Chart for Loop Break Time/Field Calibration ENTER LOOP BREAK TIME MENU: Press a 1) Press a , if necessary, until CNFG prompt appears. Press d 2) Display advances to INPT Input Menu. Press a 3) Press a , if necessary, until Display advances t...
Page 38 - Reading Offset Adjust; allows the user to fine tune a minor error of the transducer,; SETPOINT DEVIATION ENABLE/DISABLE SUBMENU:; ENBL; Submenu, if “enabled”, allows changes to Setpoint 1 to be made; THERMOCOUPLE FIELD CALIBRATION SUBMENU:; only
34 3.2.9 Loop Break Time/Field Calibration (continued) Reading Offset Adjust allows the user to fine tune a minor error of the transducer, however some applications may require a large offset adjust. (Displayed Process Value = Measured Process Value ± R.ADJ). Reading Adjust is adjustable between -19...
Page 39 - , Output 1 is automatically; Figure 3.9 Flow Chart for Output 1; is required that you put
35 3.2.10 Output 1 Alarm 1 and Output 1 or Analog Output (Retransmission) share the same contactson the rear panel connector. If Alarm 1 or Analog Output (Retransmission) is Enabled , Output 1 is automatically Disabled . Figure 3.9 Flow Chart for Output 1 It is required that you put the controller i...
Page 41 - PID
37 MAXIMUM/PERCENT HIGH SUBMENU: Specify in percent, the maximum value (99) for control output. If the output is analog proportional (Current or Voltage), then the maximum voltage or current, in percent, is specified. If the output is time proportional (Relay, SSR, or Pulse), then the maximum duty-c...
Page 45 - DAMPING FACTOR SUBMENU:; DEAD
41 DAMPING FACTOR SUBMENU: Press d 42) Display flashes the previous “Damping Factor” selection. Press b 43) Scroll through the available selections: 0000 , 0001 , 0002 , 0003 , 0004 , 0005 , 0006 , 0007 . Press d 44) Display flashes STRD stored message and then advances to OUT2 only, if it was chang...
Page 46 - Figure 3.10 Flow Chart for Output 2; CONTROL TYPE SUBMENU:
42 3.2.11 Output 2 Output 2 and Alarm 2 share the same contacts on the rear panel connector. IfAlarm 2 is Enabled , Output 2 is automatically Disabled . Figure 3.10 Flow Chart for Output 2 ENTER OUTPUT 2 MENU: Press a 1) Press a , if necessary, until CNFG prompt appears. Press d 2) Display advances ...
Page 49 - Figure 3.11 Flow Chart for Ramp and Soak; ENTER RAMP AND SOAK MENU:
45 3.2.12 Ramp & Soak Alarm must be DISABLED if Ramp is ENABLED. Figure 3.11 Flow Chart for Ramp and Soak ENTER RAMP AND SOAK MENU: Press a 1) Press a , if necessary, until CNFG prompt appears. Press d 2) Display advances to INPT Input Menu. Press a 3) Press a , if necessary, until Display advan...
Page 51 - Figure 3.12 Flow Chart for ID Code
47 3.2.13 ID CODE Figure 3.12 Flow Chart for ID Code ENTER ID CODE MENU: Press a 1) Press a , if necessary, until CNFG prompt appears. Press d 2) Display advances to INPT Input Menu. Press a 3) Press a , if necessary, until Display advances to ID ID Code Menu. ENTERING OR CHANGING YOUR (NON-DEFAULT)...
Page 52 - FULL SECURITY LEVEL SUBMENU:
48 ENTERING OR CHANGING YOUR (DEFAULT) ID CODE: Enter ID menu (Repeat steps from 1 to 3). Press d 10) Display advances to CH.ID Change ID Code Submenu. Press d 11) Display shows 0000 message with flashing 1 st digit. If you want to change your default “ID Code” you can do it now,otherwise press a an...
Page 53 - . For complete instructions on; Figure 3.13 Flow Chart for Communication Option
49 3.2.14 COMMUNICATION OPTION Purchasing the controller with Serial Communications permits an instrument to be configuredor monitored from an IBM PC compatible computer using software available from the website or on the CD-ROM enclosed with your shipment . For complete instructions on the use of t...
Page 55 - MODBUS PROTOCOL SUBMENU:
51 STOP BIT SUBMENU: Press d 15) Display flashes previous selection for “Stop Bit”. Press b 16) Scroll through the available selections: 1-BIT, 2-BIT. Press d 17) Display shows STRD stored message momentarily and then advances to BUS.F only, if it was changed, otherwise press a to advance to BUS.F B...
Page 58 - TRANSMIT TIME INTERVAL SUBMENU:
54 TEMPERATURE UNIT SUBMENU: Includes a byte in the data string to indicate whether reading is in Celsius orFahrenheit. Press d 50) Display flashes previous selection for UNIT . Press b 51) Scroll through the available selections: NO, YES. Press d 52) Display shows STRD stored message momentarily an...
Page 59 - Figure 3.14 Flow Chart for Display Color Selection; ENTER DISPLAY COLOR SELECTION MENU:
55 3.2.15 DISPLAY COLOR SELECTION This submenu allows the user to select the color of the display. Figure 3.14 Flow Chart for Display Color Selection ENTER DISPLAY COLOR SELECTION MENU: Press a 1) Press a , if necessary, until CNFG prompt appears. Press d 2) Display advances to INPT Input Menu. Pres...
Page 61 - The instrument automatically resets after the last menu of
57 Example 3: Output 1 = Analog Output (Alarm 1 disabled), Setpoint 1 = 300,Output 2 = Relay, Setpoint 2 = 200Alarm 1 & 2 Setup: Deviation, Band, “ALR.H” = 10Color Display Setup: “N.CLR” = Green, “1.CLR” = Amber, “2.CLR” = Red Display Colors change sequences: RED RED RED GREEN RED • ➤ ----------...
Page 62 - SPECIFICATIONS; Dual slope
58 PART 4 SPECIFICATIONS Accuracy ±0.5°C temp; 0.03% reading process Resolution 1°/0.1°; 10 µV process Temperature Stability 1) RTD: 0.04°C/°C2) TC @ 25°C (77°F): 0.05°C/°C - Cold Junction Compensation3) Process: 50 ppm/°C NMRR 60 dB CMRR 120 dB A/D Conversion Dual slope Reading Rate 3 samples per s...
Page 64 - No CE compliance above 60 Hz
60 EXCITATION(optional in place of Communication) 24 Vdc @ 25 mANot available for Low Power Option INSULATIONPower to Input/Output 2300 Vac per 1 min. test 1500 Vac per 1 min. test ( Low Voltage/Power Option) Power to Relays/SSR Outputs 2300 Vac per 1 min. test Relays/SSR to Relay/SSR Outputs 2300 V...
Page 65 - Table 4.1 Input Properties; TC
61 J K T E R S B C N L RTD RTD Table 4.1 Input Properties TC Input Type Range Accuracy* Iron-Constantan -210 to 760°C 0.4°C -346 to 1400°F 0.7°F -270 to -160°C 1.0°C CHROMEGA ® - -160 to 1372°C 0.4°C ALOMEGA ® -454 to -256°F 1.8°F -256 to 2502°F 0.7°F -270 to -190°C 1.0°C Copper-Constantan -190 to 4...
Page 66 - FACTORY PRESET VALUES; Table 5.1 Factory preset value; MENU ITEMS
62 PART 5 FACTORY PRESET VALUES Table 5.1 Factory preset value MENU ITEMS FACTORY PRESET VALUES NOTES Set Point 1 (SP1) 000.0 Set Point 2 (SP2) 000.0 Input: Input Type (INPT) TC, type K Reading Configuration (RDG): Decimal Point (DEC.P) FFF.F Temperature unit (TEMP) °F Filter value (FLTR) 0004 Alarm...
Page 68 - CE APPROVALS INFORMATION; Isolated RS232 to Inputs:; Measurement Category I; *Units configured for external low power dc voltage, 12-36Vdc
64 PART 6 CE APPROVALS INFORMATION This product conforms to the EMC directive 89/336/EEC amended by93/68/EEC, and with the European Low Voltage Directive 72/23/EEC. Electrical Safety EN61010-1:2001 Safety requirements for electrical equipment for measurement, control and laboratory. Double Insulatio...
Page 69 - NOTES
Page 71 - RETURN REQUESTS/INQUIRIES
WARRANTY/ DISCLAIMER OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of one (1) year from the date of purchase. In addition to OMEGA’s standard warranty period, OMEGA Engineering will extend the warrantyperiod for four (4) additional years i...