Page 2 - GENERAL HAZARD WARNING:; CONTENTS; The State of California requires the following warning:; L’etat de Californie exige les avertissement siuvants.
2 Enerco | enerRadiant® XL Series Heater Operating Instructions and Owner’s Manual WARNING: FIRE, BURN, INHALATION, AND EXPLOSION HAZARD. KEEP SOLID COMBUSTIBLES, SUCH AS BUILDING MATERIALS, PAPER OR CARDBOARD, A SAFE DISTANCE AWAY FROM THE HEATER AS RECOMMENDED BY THE INSTRUCTIONS NEVER USE THE HEA...
Page 3 - • Clearance between the heater and its vent
3 Operating Instructions and Owner’s Manual Enerco | enerRadiant® XL Series Heater SEC TION 1 Introduction Ener-Radiant ERXL models are low-cost, field assembled infrared heaters that are easy to install and require only minimal maintenance. They are designed to provide years of economical operation...
Page 4 - National Electrical Code,; Hazardous; Critical Considerations; Don’t
4 Enerco | enerRadiant® XL Series Heater Operating Instructions and Owner’s Manual • When installed over hoists, minimum clearances to combustibles must be main-tained from the uppermost point on the hoist. Electrical: The heater must be electrically grounded in accordance with the National Electric...
Page 5 - ACCESSORY pARTS LIST; Stock Number
5 Operating Instructions and Owner’s Manual Enerco | enerRadiant® XL Series Heater ACCESSORY pARTS LIST Stock Number Description 10371 ................................... Thermostat 24 volt 10392 ................................... Thermostat 120 volt 17370 ................................... Chain ...
Page 6 - Clearances To Combustibles; Minimum Clearances to Combustibles (; Reflector Type; Standard Reflector; FIRE OR EXPLOSION HAZARD
6 Enerco | enerRadiant® XL Series Heater Operating Instructions and Owner’s Manual Clearances To Combustibles TABLE 1: Minimum Clearances to Combustibles ( Use Figure 1 on page 10 as a Guide) Reflector Type position ERXL-60 ERXL-80 ERXL-100 ERXL-125 ERXL-150 ERXL-175 Standard Reflector A 6” 6” 6” 6”...
Page 7 - Clearances To Combustibles (; Refer to TABLE 1 on page 9
7 Operating Instructions and Owner’s Manual Enerco | enerRadiant® XL Series Heater Clearances To Combustibles FIGURE 1: Clearances To Combustibles ( Refer to TABLE 1 on page 9 ) Standard Reflector A A C F A C F A C F E A F C B B D E C D 45° Reflector Tilt “U”-Tube, Standard “U”-Tube, Opposite 45° Fr...
Page 8 - parts List for packaged Ener-Radiant XL Tube Heaters; Item; TURBULATOR BAFFLE 10’
8 Enerco | enerRadiant® XL Series Heater Operating Instructions and Owner’s Manual parts List for packaged Ener-Radiant XL Tube Heaters Item Stock# Description Number Required 1 F107400XL ERXL-60 NG COMP / 20’ X 2 F107401XL ERXL-60 LP COMP / 20’ X 3 F107402XL ERXL-80 NG COMP / 30’ X 4 F107403XL ERXL...
Page 9 - Figure “A” - Assembly
9 Operating Instructions and Owner’s Manual Enerco | enerRadiant® XL Series Heater 18 22 9 10 11 12 24 21 19 21 23 24 18 24 21 24 21 22 18 20 21 24 21 21 23 13 14 21 23 11 12 Figure “A” - Assembly Model ERXL-60, ERXL-80S Figure “B” - Assembly Model ERXL-80 Figure “C” - Assembly Model ERXL-100s
Page 10 - TRANSITION TUDE ASSEMBLY
10 Enerco | enerRadiant® XL Series Heater Operating Instructions and Owner’s Manual parts List for packaged Ener-Radiant XL Tube Heaters Item Stock# Description Number Required 1 F107404XL ERXL-100 NG COMP / 40’ X 2 F107405XL ERXL-100 LP COMP /40’ X 3 F107406XL ERXL-125 NG COMP / 50’ X 4 F107407XL E...
Page 11 - Figure “D” - Assembly
11 Operating Instructions and Owner’s Manual Enerco | enerRadiant® XL Series Heater 28 28 27 26 28 27 26 27 30 27 29 21 19 20 22 30 27 29 21 22 30 27 29 19 20 18 17 26 15 16 17 18 Figure “D” - Assembly Model ERXL-100, ERXL-125S Figure “E” - Assembly Model ERXL-125, ERXL-150, ERXL-175 Figure “F” - As...
Page 12 - SEC TION 3; HANGER
12 Enerco | enerRadiant® XL Series Heater Operating Instructions and Owner’s Manual SEC TION 3 Installation & Assembly FIGURE 2: Ener-Radiant XL Overview Key Burner Housing Must always be installed horizontally. Tube and Reflector Hanger Install immediately after first coupling. Turbulator Assem...
Page 14 - TURBUL ATOR BAFFLE ASSEMBLY; FIGURE 3: Coupling Assembly
14 Enerco | enerRadiant® XL Series Heater Operating Instructions and Owner’s Manual Assemble the heater components as shown in Figures 2a, 2b, 2c, 2d, 2e, and 2f. Optional reflector configurations are shown in (Figure 1). Install appropriated suspension hardware, beam clamps, chain or rod at predete...
Page 15 - FIGURE 5: Typical Suspension Details; ) After both set screws are snug, turn each; FIGURE 8: Burner Box / Transition Tube Detail
15 Operating Instructions and Owner’s Manual Enerco | enerRadiant® XL Series Heater FIGURE 5: Typical Suspension Details Chain kit - Stk. #17370 One chain kit will suspend one 10 ft. section of tube and one 10 ft. section of reflector. FIGURE 6: Tube and Reflector Hanger FIGURE 7: Mounting Flange / ...
Page 16 - SEC TION 4; General Requirements; Alternative Arrangements / Optional Equipment for Venting
16 Enerco | enerRadiant® XL Series Heater Operating Instructions and Owner’s Manual SEC TION 4 Venting / Ducting General Requirements Heater must be vented in accordance with specification ANSI Z223.1 - latest revisions. Partial information relating to this specification is provided in this section ...
Page 17 - FIGURE 12: Unvented Operation
17 Operating Instructions and Owner’s Manual Enerco | enerRadiant® XL Series Heater streams of combustion gases. Outside Air Supply a) See procedure and diagram on page ??. FIGURE 12: Unvented Operation 36” 36” A 1) Ventilation equal to 4 CFM per 1,000 BTU/hr. firing rate must be provided in unvente...
Page 18 - FIGURE 15: Common Roof Venting; Approved Vent Cap; SIDE VIEW
18 Enerco | enerRadiant® XL Series Heater Operating Instructions and Owner’s Manual FIGURE 15: Common Roof Venting COMMON VENTING - (2) Heaters Model # H = 6 f t. H = 8 f t. H = 15 f t. ERXL-60 D = 7” D = 6” D = 6” ERXL-80 D = 8” D = 7” D = 6” ERXL-100 D = 8” D = 8” D = 7” ERXL-125 D = 10” D = 10” D...
Page 19 - Outside Combustion Air Supply; SEC TION 6
19 Operating Instructions and Owner’s Manual Enerco | enerRadiant® XL Series Heater Outside Combustion Air Supply The Ener-Radiant XL heater is approved for installation with an outside air supply system. Some compounds such as halogenated hydrocarbons or other corrosive chemicals in the air can be ...
Page 20 - FIGURE 18a: Line Voltage Thermostat Wiring; FIGURE 19: Wiring of Low Voltage Thermostat and Relay
20 Enerco | enerRadiant® XL Series Heater Operating Instructions and Owner’s Manual SEC TION 6 Wiring Heaters are normally controlled by thermostats. Line voltage thermostats are wired directly (see Figure 18a), the recommended 24V thermostats use a relay (see Figure 18b). Heaters must be grounded i...
Page 21 - SEC TION 7; Sequence of Operation
21 Operating Instructions and Owner’s Manual Enerco | enerRadiant® XL Series Heater SEC TION 7 Operation & Maintenance Sequence of Operation 1. Turn the thermostat up. When the thermostat calls for heat, blower motor will energize. 2. When the motor approaches nominal running RPM, the air provin...
Page 22 - Honeywell Valve LED Status; LED
22 Enerco | enerRadiant® XL Series Heater Operating Instructions and Owner’s Manual Natural outlet pressure should be 3.5” LP inlet pressure should be 11.0” LP outlet pressure should be 10.25” 3. Check for proper orifice and air plate. Burner Does Not 1. Check ground wire continuity. Stay Lit: 2. Ch...
Page 24 - SEC TION 9; TOP VIEW; Item part Number Description
24 Enerco | enerRadiant® XL Series Heater Operating Instructions and Owner’s Manual SEC TION 9 Replacement parts 11 10 9 5 6 4 7 8 3 2 TOP VIEW SIDE VIEW 1 11 10 9 5 6 4 7 8 3 2 TOP VIEW SIDE VIEW 1 Item part Number Description 1 02731 Hot Surface Igniter 2 02730 Flame Sensor 3 10413A Air Sensing Sw...
Page 25 - Engineering Specifications
25 Operating Instructions and Owner’s Manual Enerco | enerRadiant® XL Series Heater SEC TION 10 Engineering Specifications The total heating system supplied shall be design certified by the American Gas Association and the Canadian Gas Association. A. Burner & Burner Controls 1. Burners shall be...
Page 26 - Burner Side View; Reflector
26 Enerco | enerRadiant® XL Series Heater Operating Instructions and Owner’s Manual Minimum Total Length (see chart below) Burner Side View XL 13.75” 17.75” 9.25” Burner Rear View FIGURE 25: Ener-Radiant XL Dimensions & Suggested Mounting Heights Minimum Total Length (see chart below) Model # Mi...
Page 27 - THIS pAGE INTENTIONALLY LEFT BL ANK.
27 Operating Instructions and Owner’s Manual Enerco | enerRadiant® XL Series Heater THIS pAGE INTENTIONALLY LEFT BL ANK.
Page 28 - FOR INFORMATION REGARDING SERVICE OR pARTS:; Contact your local heating service technician or dealer.; FOR ADDITIONAL INFORMATION:; LIMITED WARRANTY; OpERATING INSTRUC TIONS AND OWNER’S MANUAL; HEATSTAR
28 Enerco | enerRadiant® XL Series Heater Operating Instructions and Owner’s Manual WARNING: USE ONLY MANUFACTURER’S REPLACEMENT PARTS. USE OF ANY OTHER PARTS COULD CAUSE INJURY OR DEATH. REPLACEMENT PARTS ARE ONLY AVAILABLE DIRECT FROM THE FACTORY AND MUST BE INSTALLED BY A QUALIFIED SERVICE AGENCY...