Summary
2 1-1. INDOOR UNIT Model name Service Ref. Service Manual No. PLA-A12/18/24/30/36/42BA PLA-A12/18/24/30/36/42BA 1 OCH420 OCB420 PCA-A24/30/36/42GA PCA-A24/30/36/42GA 2 OC368 PKA-A12/18GA PKA-A12/18GA 2 OC369 PKA-A12/18GAL PKA-A12/18GAL 2 PKA-A24/30/36FA PKA-A24/30/36FA 2 PKA-A24/30/36FAL PKA-A24/30/...
3 2 SAFETY PRECAUTION Cautions for units utilizing refrigerant R410A 2-2. CAUTIONS RELATED TO NEW REFRIGERANT Use new refrigerant pipes. Make sure that the inside and outside of refrige-rant piping is clean and it has no contaminationsuch as sulfur hazardous for use, oxides, dirt, shaving particles,...
4 Gravimeter Unit [3] Service tools Use the below service tools as exclusive tools for R410A refrigerant. No. Tool name Specifications 1 Gauge manifold ·Only for R410A ·Use the existing fitting specifications. ·Use high-tension side pressure of 5.3MPa·G or over. 2 Charge hose ·Only for R410A ·Use pr...
5 2-3. CAUTIONS FOR REFRIGERANT PIPING WORK New refrigerant R410A is adopted for replacement inverter series. Although the refrigerant piping work for R410A issame as for R22, exclusive tools are necessary so as not to mix with different kind of refrigerant. Furthermore as theworking pressure of R41...
6 3 FEATURES CHARGELESS SYSTEMPRE-CHARGED REFRIGERANT IS SUPPLIED FOR PIPING LENGTH AT SHIPMENT.(Max. 100ft, 30m (A42) / Max. 70ft, 20m (A12-36)) The refrigerant circuit with LEV(Linear Expansion Valve) and accumulator always control the optimal refrigerant levelregardless of the length (A42: 100ft,...
7 4 SPECIFICATIONS Service Ref. PUZ-A18NHA2 PUZ-A24NHA2 PUZ-A30NHA2 PUZ-A36NHA2 PUZ-A42NHA2 PUZ-A18NHA2-BS PUZ-A24NHA2-BS PUZ-A30NHA2-BS PUZ-A36NHA2-BS PUZ-A42NHA2-BS Power supply Phase Single Cycle 60Hz Voltage 208/230V MCA A 13 18 25 25 26 MOCP A 20 30 40 40 40 Breaker size A 15 25 30 30 30 Extern...
Piping Length (one way) Charged Factory Service Ref. 50ft 60ft 70ft 80ft 90ft 100ft 110ft 120ft 130ft 140ft 150ft 160ft 165ft 15m 18m 21m 24m 27m 30m 33m 37m 40m 43m 46m 49m 50m PUY-A12NHA2-BS PUY-A12NHA2 42 oz 44 oz 46 oz 48 oz 50 oz 52 oz - - - - - - - 46 oz 1.2 kg 1.2 kg 1.3 kg 1.4 kg 1.4 kg 1.5 ...
13 OUTDOOR UNIT Unit : mm<inch> PUZ-A18NHA2 PUZ-A18NHA2-BS PUY-A12/18NHA2 PUY-A12/18NHA2-BS 1/2 conduit hole 144<5-21/32> 2-ø22.2<7/8> 22<7/8> 38<1-1/2> 241<9-1/2> Min.100mm<3-15/16> Piping and wiring connection canbe made from the rear direction only. *1 In...
14 PUZ-A24/30/36NHA2 PUZ-A24/30/36NHA2-BS Unit : mm<inch> PUY-A24/30/36NHA2 PUY-A24/30/36NHA2-BS , ,,,, ,,,,,, ,,,,, ,,,,,, ,,,,, ,,, ,, ,, ,,,, , ,, , ,,,, , , ,, ,,, , ,, , ,, ,,, , , , ,, ,,, ,, ,, , , ,,, , ,, , , , , , , ,, ,, ,, , , , , , , ,,, , , , ,,, ,,,, , , ,,, , ,, , ,, ,, , , ,, ...
16 TB1MCMF121S463HTH3TH4TH6TH7TH8LEV-A CY1,CY2 Terminal Block<Power Supply, Indoor/Outdoor>Motor for CompressorFan Motor Solenoid Valve (Four-Way Valve) High Pressure SwitchThermistor<Outdoor Pipe> Thermistor<Discharge>Thermistor<Outdoor 2-Phase Pipe>Thermistor<Outdoor>...
20 8 WIRING SPECIFICATIONS 8-1. INDOOR UNIT POWER SUPPLIED FROM OUTDOOR UNIT (A-control application) The following connection patterns are available.The outdoor unit power supply patterns vary on models. 1:1 System Simultaneous twin system A Outdoor unit power supply B Wiring circuit breaker or isol...
21 8-2. SEPARATE INDOOR UNIT/OUTDOOR UNIT POWER SUPPLIES The following connection patterns are available.The outdoor unit power supply patterns vary on models. 1:1 System S1S2 L1L2 GR GR 12 L1L2 S1S2S3 S3 * Affix a label B that is included with the manuals near each wiring diagram for the indoor and...
22 w The max. cable length may vary depending on the condition of installation, humidity or materials, etc. Indoor unit-Outdoor unit Outdoor power supply Max. 45m, 147ft 3 o AWG15(polar) Max. 50m, 164ft 3 o AWG13(polar) Max. 80m, 262ft 3 o AWG13(polar) and S3 separated Wire No. o Size Be sure to con...
25 9 REFRIGERANT SYSTEM DIAGRAM PUZ-A24/30/36NHA2 PUZ-A24/30/36NHA2-BS Outdoor heat exchanger Thermistor(TH3) Thermistor(TH6) Distributor Serviceport(check) Accumulator Compressor Refrigerant GAS pipe15.88 A ( { 5/8) Refrigerant LIQUID pipe9.52 A ( { 3/8) Stop valve(with service port) 4-way valve Se...
27 2. Start and finish of test run • Operation from the indoor unit Execute the test run using the installation manual for the indoor unit. • Operation from the outdoor unit By using the DIP switch SW4 on the control board of outdoor unit, test run can be started and finished, and its operation mode...
28 10 TROUBLESHOOTING <Error code display by self-diagnosis and actions to be taken for service (summary)>Present and past error codes are logged and displayed on the wired remote controller and control board of outdoor unit.Actions to be taken for service, which depends on whether or not the ...
29 [TEST] button Pipe (liquid) temperature Displays the remainingtest run time. "TEST RUN" and the currently selectedoperation mode are displayed altemately. A B C ° F 59 • In case of test run, the OFF timer will be activated, and the test run will automatically stop after 2 hours.• The room...
30 ON/OFF TEMP FAN VANE MODE CHECK LOUVER TEST RUN AUTO STOP AUTO START h min RESET SET CLOCK TEST RUN COOL 7 5 6 2 3 , 4 Test run [for wireless remote controller] Measure an impedance between the power supply terminal block onthe outdoor unit and ground with a 500V Megger and check that it isequal ...
31 10-3. HOW TO PROCEED "SELF-DIAGNOSIS" 10-3-1. When a Problem Occurs During Operation If a problem occurs in the air conditioner, the indoor and outdoor units will stop,and the problem is shown in the remote controller display. 1 [CHECK] and the refrigerant address are displayed on the tem...
33 [Procedure] 1. Press the CHECK button twice. 2. Press the temperature buttons. 3. Point the remote controller at the sensor on the indoor unit andpress the HOUR button. 4. Point the remote controller at the sensor on the indoor unit andpress the ON/OFF button. • "CHECK" lights, and refrig...
36 Error Code Abnormal point and detection method Judgment and action Eb (6845) Miswiring of indoor/outdoor unit connecting wire (converse wiring ordisconnection)Outdoor controller circuit board can automatically set the unit number of indoorunits.Abnormal if the indoor unit number cannotbe set with...
37 <Abnormalities detected while unit is operating> Error Code Abnormal point and detection method Judgment and action U1 (1302) High pressure (High-pressure switch63H worked)Abnormal if high-pressure switch 63Hworked ( w ) during compressor operation. w 4.15 MPa [602PSIG] 63H: High-pressure s...
40 Error Code Abnormal point and detection method Judgment and action UL (1300) Low pressure (63L worked)Abnormal if 63L is worked (under-0.03MPa) during compressor operation.63L: Low-pressure switch (A42N only) 1 Stop valve of outdoor unit isclosed during operation. 2 Disconnection or loose connect...
43 A6 (6606) Communication error with communica-tion processorDefective communication between unitprocessor and transmission processorNote) The address and attribute display at remote controller indicate the con-troller that detected abnormality. 1 Data of transmission proces-sor or unit processor i...
44 5. If displayed address or attribute is FRESH MASTER, Indoor unit detects abnormality whenindoor unit transmitted to FRESH MAS-TER and there was no reply (ACK). 1 During sequential operation ofindoor unit and FRESH MAS-TER of other refrigerant sys-tem, if indoor unit transmits toFRESH MASTER whil...
45 10-5. TROUBLESHOOTING BY INFERIOR PHENOMENA Phenomena Factor Countermeasure 1. Remote controller display does not work. 2. “PLEASE WAIT” display is remained on the remote controller. 3. When pressing the remote controller operation switch the OPERATIONdisplay is appeared but it will beturned off ...
48 AC 187V to AC 253V? AC 187V to AC 253V? AC 187V to AC 253V? DC 12V to DC 16V? DC 12V to DC 16V? NO YES NO YES NO YES YES NO YES NO Check the voltage between S1 and S2 on the terminal block (TB4) of the indoor unit. Check the voltage among L1 and L2 on the terminal block (TB1) of the outdoor power...
49 AC 187V to AC 253V? Are there looseness or disconnection of the indoor/ outdoor connecting wire? Is anything displayed? DC 17V to DC 28V? Is “E8” displayed? Can all the indoor unit be operated? Check the voltage between S2 and S3 on the terminal block of the outdoor unit. NO YES Not lighting. Bli...
57 Thermistor R0 = 15k ' ± 3% B constant = 3480 ± 2% t ( : ): R t =15exp{3480( 273+t – 273 )} T (˚F): R T =15exp{3480( 273+(T– 32)/1.8 – 273 )} 10-7. HOW TO CHECK THE COMPONENTS <Thermistor feature chart> Low temperature thermistors • Thermistor <Outdoor pipe> (TH3)• Thermistor <Outdo...
58 <Output pulse signal and the valve operation> (2) Linear expansion valve operation A B C Open Extra tightning (about 32 pulse) Pulse number 500 pulseOpening a valveall the way Close V alve position (capacity) Opening a valve : 8 → 7 → 6 → 5 → 4 → 3 → 2 → 1 → 8 Closing a valve : 1 → 2 → 3 → ...
62 10-8. EMERGENCY OPERATION (1) When the error codes shown below are displayed on outdoor unit or microcomputer for wired remote controller or indoor unit has a failure, but no other problems are found, emergency operation will be available by setting the emergency opera-tion switch (SWE) to ON and...
63 (5) Operation data during emergency operation During emergency operation, no communication is performed with the indoor unit, so the data items needed for operationare set to the following values: Operation data Intake temperature (TH1) Indoor fluid pipe temperature (TH2) Indoor 2-phase pipe temp...
70 N1 Non-connect lo Connect to the outdoor power circuit board(TABN2) L1, L2 Connect tothe DCL(Reactor) P Connect to the outdoor power circuit board(TABP2) + DCL L1 L2 ACTM P Io N1N2 (+) (–) Load Active filter modulePUZ-A30/36/42NHA2 PUZ-A30/36/42NHA2-BS PUY-A30/36/42NHA2 PUY-A30/36/42NHA2-BS N2 No...
73 Special function(a) Low-level sound priority mode (Local wiring) Unit enters into Low-level sound priority mode by external signal input setting.Inputting external signals to the outdoor unit decreases the outdoor unit operation sound 3 to 4 dB lower than that of usual. Adding a commercial timer ...
76 <Outdoor unit operation monitor function>[When option part ‘A-Control Service Tool(PAC-SK52ST)’ is connected to outdoor controller board(CNM)]Digital indicator LED1 displays 2 digit number or code to inform operation condition and the meaning of error code by controlling DIP SW2 on ‘A-Contr...
82 SW2 setting Display detail Explanation for display Unit 1 ON 2 3 4 5 6 Pulse LEV-A opening pulse on error occurring0~480 0~480(When it is 100 pulse or more, hundreds digit, tens digit and ones digit are displayed by turns.) (Example) When 130 pulse; 0.5 secs. 0.5secs. 2 secs. ˚F Indoor room tempe...
85 ● Reduces maintenance work drastically. ● Enables you to check operation data of the indoor and outdoor units by remote controller.Furthermore, use of maintenance stable-operation control that fixes the operating frequency, allows smooth inspection, evenfor inverter models. 11-1.MAINTENANCE MODE ...
86 ● Data measurementWhen the operation is stabilized, measure operation data as explained below. (4) Press the [TEMP] buttons ( and ) to select the desired refrigerant address. [Screen B ] (5) Select the type of data to be displayed. After selecting, go to step (6). Compressor information MENU butt...
87 11-2.GUIDE FOR OPERATION CONDITION Inspection item Result Power supply Loose con- nection Breaker Good Retightened Terminal block Outdoor Unit Good Retightened Indoor Unit Good Retightened (Insulation resistance) M " (Voltage) V 1 Accumulated operating time Time 2 Number of ON/OFF times Times...
88 12 FUNCTION SETTING Function Settings Mode No. Setting No. : Initial setting (when sent from the factory) Remarks Power failure automatic recoveryIndoor temperature detecting LOSSNAY connectivity Power supply voltageAuto mode(only for PUZ)Frost prevention temperatureHumidifier control Change of d...
90 6 Select mode No. 02 (room temperature detection position). 7 Select setting No. 03 (remote controller fixed). (Use F and G .) 8 Enter the setting. (Press E .) Finished 0 End function display. (Press A and B at the same time.) Example:Selecting room temperaturedetection position YES YES NO NO 9 S...
93 12-2. FUNCTION SELECTION OF REMOTE CONTROLLER The setting of the following remote controller functions can be changed using the remote controller function selection mode.Change the setting when needed. Item 1 1.Change language("CHANGE LANGUAGE")2.Function limit("FUNCTION SELECTION"...
95 12-3. Function selection of wireless remote controllerTEMPERATURE DISPLAY : : / -- F SETTING (Change of temp mode from -- F to : : ) 1 Press the set button with something sharp at the end. MODEL SELECT blinks. 2 Press the button. “F:” blinks. 3 Press the button. “C:” blinks. 4 Press the set butto...
96 13-1. HOW TO "MONITOR THE OPERATION DATA" • Turn on the [Monitoring the operation data] A D C B (1) (2) (3) (4) (5) (6) (7) (1) Press the TEST button for 3 seconds so that [Maintenance mode] appears on the screen (at A ). (2) Press the CHECK button for 3 seconds to switch to [Maintenance ...
106 14 DISASSEMBLY PROCEDURE OPERATING PROCEDURE PHOTOS PUZ-A18NHA2 PUZ-A18NHA2-BS 1. Removing the top panel, service panel, front panel and back panel (1) Remove the top panel fixing screws (4 ✕ 10), one from the right and two from the left side, and detach the top panel. (2) Remove 1 service panel...
107 Electrical parts box Controller circuitboard (C.B.) Electrical parts box fixingscrew Terminal block(TB1) OPERATING PROCEDURE PHOTOS 4. Removing the thermistor <Outdoor 2-phase pipe> (TH6) and thermistor <Outdoor pipe> (TH3) (1) Remove the service panel. (See photo 1.)(2) Remove the t...
108 OPERATING PROCEDURE PHOTOS 5. Removing the thermistor <Outdoor> (TH7) (1) Remove the service panel. (See photo 1.)(2) Remove the top panel. (See photo 1.)(3) Disconnect the connector TH7 (red) on the controller circuit board in the electrical parts box. (4) Loosen the clamp for the lead wi...
109 9. Removing linear expansion valve (1) Remove the service panel. (See photo 1.)(2) Remove the top panel. (See photo 1.)(3) Remove the front panel. (See photo 1.)(4) Remove the conduit cover and cord cover. (See photo 2.)(5) Remove the back panel. (See photo 1.)(6) Remove the electrical parts box...
110 OPERATING PROCEDURE PHOTOS Photo 13 Photo 14 Compressor(MC) Valve bed Separator Separatorfixing screw Compressorfixing nut Accumulator Accumulator Outlet Inlet 12. Removing the compressor (MC) (1) Remove the service panel. (See photo 1.)(2) Remove the top panel. (See photo 1.)(3) Remove the fron...
111 OPERATING PROCEDURE PHOTOS & ILLUSTRATION PUZ-A24/30/36NHA2 PUZ-A24/30/36NHA2-BS 1. Removing the service panel and top panel (1) Remove 3 service panel fixing screws (5 ✕ 10) and slide the hook on the right downward to remove the service panel. (2) Remove screws (3 for front, 3 for rear/5 ✕ ...
112 OPERATING PROCEDURE PHOTOS 4. Removing the thermistor <Outdoor 2-phase pipe> (TH6) (1) Remove the service panel. (See figure 1.)(2) Remove the top panel. (See figure 1.)(3) Disconnect the connectors, TH6 and TH7 (red), on the controller circuit board in the electrical parts box. (4) Loosen...
114 OPERATING PROCEDURE PHOTOS 10. Removing the bypass valve (1) Remove the service panel. (See figure 1.)(2) Remove the top panel. (See figure 1.)(3) Remove the electrical parts box. (See photo 3.)(4) Remove 3 right side panel fixing screws (5 ✕ 10) in the rear of the unit and remove the right side...
116 OPERATING PROCEDURE PHOTOS & ILLUSTRATION PUZ-A42NHA2 PUZ-A42NHA2-BS 1. Removing the service panel and top panel (1) Remove 3 service panel fixing screws (5 ✕ 10) and slide the hook on the right downward to remove the service panel. (2) Remove screws (3 for front, 3 for rear/5 ✕ 10) of the t...
117 OPERATING PROCEDURE PHOTOS Photo 4 4. Removing the thermistor <Outdoor 2-phase pipe> (TH6) (1) Remove the service panel. (See figure 1.)(2) Remove the top panel. (See figure 1.)(3) Disconnect the connectors, TH6 and TH7 (red), on the controller circuit board in the electrical parts box. (4...
119 OPERATING PROCEDURE PHOTOS 11. Removing the reactor (DCL) and capacitor (CE) (1) Remove the service panel. (See figure 1.)(2) Remove the top panel. (See figure 1.)(3) Remove the electrical parts box. (See photo 3.)<Removing the reactor>(4) Remove 4 reactor fixing screws (4 ✕ 10) and remove...
Mitsubishi Electric Manuals
-
Mitsubishi Electric WD-73835
Manual
- Mitsubishi Electric SW2D5C-GTWK2-E Manual
-
Mitsubishi Electric WD-57734
Manual
-
Mitsubishi Electric E-20TP
Manual
-
Mitsubishi Electric A1SJ71E71N-B2
Manual
-
Mitsubishi Electric CK-35308
Manual
-
Mitsubishi Electric WS-65411
Manual
-
Mitsubishi Electric HS-S8300E(BRS)
Manual
-
Mitsubishi Electric DX-PC25EA
Manual
-
Mitsubishi Electric XL5980LU
Manual
-
Mitsubishi Electric XL6500U
Manual
-
Mitsubishi Electric 1770G
Manual
-
Mitsubishi Electric WT-42413
Manual
-
Mitsubishi Electric WD-57831
Manual
-
Mitsubishi Electric MSH-A18ND
Manual
-
Mitsubishi Electric WD-60C8
Manual
-
Mitsubishi Electric XL650U
Manual
-
Mitsubishi Electric HL2750U
Manual
-
Mitsubishi Electric MSZ-GE09NA
Manual
-
Mitsubishi Electric P40
Manual