- 1 - CONTENTS SAFETY FOR USE ------------------------------------------------------2 A COMPLETE LINE UP ------------------------------------------------4 FEATURES-----------------------------------------------------------------5 DESCRIPTIONS----------------------------------------------------------...
SAFETY FOR USE - 2 - fire may result. If you need to have the unit Ask your dealer or specialized subcontractor for installation. For installation, conduct the work correctly byfollowing the Installation Manual. Install the unit on a spot sufficiently durable againstthe unit weight. All electric wor...
- 3 - The gas may ignite or explode when the gas leaks and collects in surround of the unit. The erroneous operation of air conditioner may beinduced by inverter equipment, independent powerdevice, medical equipment or communicationequipment. As the use for the applications other than thatdesigned o...
- 4 - A COMPLETE LINE UP Indoor unit PEH-5 kcal/h 12,400 Cooling capacity Btu/h 49,150 kW 14.4 kcal/h 12,400 Heating capacity (PEH only) Btu/h 49,150 kW 14.4 PE(H)-7 15,400 61,000 17.9 16,200 64,100 18.8 PE(H)-8 18,900 75,100 22.0 18,900 75,100 22.0 PE(H)-10 24,800 98,300 28.8 24,800 98,300 28.8 PE(...
FEATURES - 5- DESCRIPTIONS High sensible cooling capacity. The sensible cooling capacity has been significantlyimproved through balanced optimised heat exchanger design. Comfort heating. (PEH only) Highly efficient operation. The EER(Energy Efficiency Ratio) on these modelsis greatly improved by rev...
- 7 - MODEL-DESIGNATION BREAKDOWN P E - 10 M Y C 1 Design Sequence Electrical Supply Compressor Horsepower Series Number 5 = 5 HP7 = 7 HP8 = 7.5 HP 10= 10 HP15= 15 HP20= 20 HP PE = Indoor unit PEH = Indoor unit PU = Outdoor unitPUH = Outdoor unit Y = 3 phase 380~415V 50Hz 4 wires ( In case of PE(H)-...
- 8 - SPECIFICATIONS Model name Servicereference Power supply Indoor Outdoor Total cooling capacity Sensible cooling capacity kW Btu/h kcal/h % Capacity step RefrigerantRefrigerant charge kg Capillary tube Refrigerant control Indoor Unit Model name Servicereference External finish Acrylic resin coat...
Model name Servicereference Power supply Indoor Outdoor kW Btu/h kcal/h % Capacity step RefrigerantRefrigerant charge kg Capillary tube Refrigerant control Indoor Unit Model name Servicereference External finish Acrylic resin coating Munsell 5Y 8/1 Dimension Height mm Width mm Depth mm Net weight Co...
- 11 - ELECTRICAL DATA VOLT ITEM TOTAL INPUT kW TOTAL RUN CURRENT A POWER FACTOR % START CURRENT A PE-7240V PE-8 20415V COMPRESSOR INPUT kW RUN CURRENT A INDOOR FAN INPUT OUTDOOR FAN INPUT INDOOR FAN INPUT OUTDOOR FAN INPUT kW RUN CURRENT A kW RUN CURRENT A TOTAL INPUT kW TOTAL RUN CURRENT A POWER F...
- 14 - SELECTION PROCEDURE 1. Model Selection (With actual examples) First step, to select the approximate model: Based on the cooling load and the cooling capacity listed in the capacity table, select the applicable model. Notes: *1. The correct WB is required since it has a serious effect on the c...
At 26˚CDB, 19˚CWB of Indoor, Q = 21.3, SHC = 16.3, T/I = 8.3 Therefore, when air flow is 77(CMM) Q = 21.3 ✕ (1+(1.025 - 1.0) ✕ 7/10*) 21.7(kW) SHC = 16.3 ✕ (1+(1.044 - 1.0) ✕ 7/10*) 16.8(kW) T/I = 8.3 ✕ (1+(1.009-1.0)) ✕ 7/10*) 8.4(kW) Note * : 7/10 = (77-70)/(80-70) - 15 - (Step-3) Calculation of n...
OUTDOOR DB ˚C INDOOR INDOOR 2 0 .0 25.0 30.0 35.0 40.0 DB ˚ C W B ˚ C Q kW SHC kW S H F T/I kW Q k W SHC kW S H F T/I kW Q k W SHC kW S H F T/I kW Q k W SHC kW S H F T/I kW Q k W S H C k W S H F T/I kW 15 20 16 17 15 16 22 17 18 19 16 17 24 18 19 20 21 18 19 26 20 21 22 23 19 20 28 21 22 23 24 20 21...
OUTDOOR DB ˚C INDOOR -5.0 0.0 5.0 10.0 15.0 DB ˚C WB ˚C Q kW SHC kW S H F T/I kW Q kW SHC kW S H F T/I kW Q kW SHC kW S H F T/I kW Q kW SHC kW S H F T/I kW Q kW SHC kW S H F T/I kW 15 20 16 17 15 16 22 17 18 19 16 17 24 18 19 20 21 18 19 26 20 21 22 23 19 20 28 21 22 23 24 20 21 30 22 23 24 PE-7MYC-...
PE-10MYC-EU PEH-10MYA-EU AIR VOLUME CMM 9 0 L /S 1,550 100 1,660 COOLING CAPACITY 1 .0 1.035 SHC 1 .0 1.037 TOTAL INPUT 1 .0 80 1,330 0.977 0.968 0.991 1.005 0.69 0.69 0.69 0.70 0.70 0.61 0.61 0.61 0.62 0.63 0.54 0.54 0.54 0.54 0.55 0.79 0.79 0.79 0.80 0.80 0.71 0.72 0.72 0.72 0.73 0.64 0.64 0.65 0....
- 36 - OPERATION RANGE The range of working temperatures is as below.Make sure which unit you are using and confirm the range of application. NoteAs an applicable humidity outside standard for both indoors and outdoors, werecommend use within a range of 35-80% relative humidity.However, it is a cond...
- 37 - FAN PERFORMANCE PEH-5MYA-EU PE-8MYC-EUPEH-8MYA-EU PE-10MYC-EUPEH-10MYA-EU 40 35 45 50 55 Recommended Range Inter nal SP 450 400 350 300 250 200 150 100 50 450 400 350 300 250 200 150 100 50 0 (Pa) T otal static pressure Air flow (CMM) Fan speed (rpm) (Pa) Fan speed (rpm) (Pa) Fan speed (rpm) ...
- 39 - Pulley outside dimensions are shown below: (Unit : mm) (1) Shape of belt groove (2) Shape of motor pulley boss (Unit : mm) e a r 1 r 3 f w L 0 r 2 r 2 K K 0 øP.C 16.5mm B type 11.0mm 40˚ Sectional plan of V-belt Shape of V-belt Nominal Dia. øP.C a (˚) L 0 W K K 0 e f r 1 r 2 r 3 V-belt thickn...
- 40 - SOUND DATA Indoor units Sound Levels OCTAVE BAND FREQ. Hz MODEL SPL 63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz 63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz 55 56 59 61 62 62 63 62 25 32 60 61 62.5 40 44 54 55 58.5 47 49 53 54 59.5 52 53.5 50 51 53 55 56.5 42.5 43.5 48 57.5 57.5 ...
- 41 - OUTLINE DIMENSIONS 131 200 199 95 152 156 AIR INLET DUCTFLANGE HOLES:24- 3.1 34 1102 104 31 130 130 130 130 130 130 130 130 31 344 20 428 15 15 70 50 530 650 130 130 42 42 40 40 HOLES:4- 12 280 70 DRAIN:Rc1 CONTROL BOX HOLES:22- 3.1 AIR OUTLET DUCTFLANGE 33 562 382 25 100 100 25 1240 55 135 4...
- 47 - In the case of installation are shown below, it is possible to use the unit by connecting the duct. However, the pressure loss must be 30Pa (3mmAg) or less. Duct work is local supply. Note: DUCT DUCT
- 48 - WIRING DIAGRAMS CR2 GRAY CH F3(3.15A) 52C CZ 30 49C 52C 15 TB5 BLUE CZ2 14 63H 51F2 CZ2 CZ 30 51C C5 C4 MC 1 2 3 BLACK RED MF3 WHITE 52C 51C 3 2 1 51F2 WHITE MF2 RED RED WHITE BLACK BLACK BLACK WHITE BLACK WHITE RED RED RED PU-7MYC1-EU PE-7MYC-EU PE 3Phase 50Hertz Power supply, 380 415Volt, C...
- 64 - PEH-5MYA-EU SPECIAL WIRING : ANTI SHORT CYCLE TIMER., ( PROTECT FOR COOL AIR BLOW. ) OUTDOOR MC OUTDOOR 52F High-pressure switch 63H Internal thermostat(indoor fan) 49F Name F1~3 51C Tr CH 51F1,2 52C MF2 MF1 MC TB1~4 Fan motor (indoor) Fuse (3.15A) Transformer Crankcase heater Contactor (fan ...
- 71 - ELECTRICAL OPERATION FLOW CHARTS START POWER ON 52C ONMC OPERATEMF2, 3 OPERATE SERVICE CALL 23WA ON? SAFETY DEVICE OFF? NO YES YES 30FZ,30CZ ON (SELF HOLD) FZ ON YES 52F ONMF1 OPERATE NO NO 30CZ OFF CH ON SW1 ON? CZ1,2 ON CH OFF 52C OFFMC STOP MF2,3 STOP MF1 Note CH ON START POWER ON 52C ONMC...
Strainer Evaporator Ball valve Strainer High pressure switch Check joint 4-Way valve Accumulator Muffler Check joint Check valve Strainer Ball valve Strainer Check valve Condenser Inter connecting refrigerant piping Capillary Tube OUTDOORPUH INDOORPEH Capillary Tube Compressor Service port (by other...
- 75 - SAFETY & CONTROL DEVICES ITEM NO. PE-7MYC-EU PU-7MYC 1 -EU PE-8MYC-EU PU-8MYC 1 -EU PE-10MYC-EU PU-10MYC 1 -EU COMPRESSOR OVER CURRENT RELAY 51C 19.0A 22.0A 31.0A COMPRESSOR INTERNAL THERMOSTAT 49C 105 ± 5 ˚C OFF 83 ± 11 ˚C ON HIGH PRESSURE SWITCH 63H 2.94MPa OFF INDOOR FAN MOTOR OVER CUR...
- 77 - SPECIAL ORDER Description PEH-5MYA PEH-5MYA-EU - - PEH-7MYA PEH-7MYA-EU PE-7MYC PE-7MYC-EU PEH-8MYA PEH-8MYA-EU PE-8MYC PE-8MYC-EU PEH-10MYA PEH-10MYA-EU PE-10MYC PE-10MYC-EU PEH-15MYA PEH-15MYA-EU PE-15MYC PE-15MYC-EU PEH-20MYA PEH-20MYA-EU PE-20MYC PE-20MYC-EU Anti corrosion(Service referen...
- 78 - PHYSICAL DATA PRODUCT] PACKAGE AIR COOLED HEATPUMP UNITS Product type PE SERIES Product number : Indoor unit Outdoor unit Cooling capacity (AS1861) Sensible Cooling capacity (AS1861) Cooling power consumption (Input) Basic temperature condition cooling 27 DB/19 WB Basic temperature condition ...
- 87 - INSTALLATION Space required around unit. Indoor unit 1. Dimension of the unit and space necessary for sevicing. Outdoor unit Secure enough space necessary for servicing, installing, and for proper function of the unit.To prevent short-cycling, remove obstacles as much as possible. (2) Relatio...
2. Preparation before installing Please use the specified hanging bolt in any case.Hanging bolt is local supply.Please use the method below or use the angle and therectangular lumber, etc. and install the hanging bolt. Insert etc100-150kg Hanging bolt M10 (PEH-5,PE(H)-7,8,10)M12 (PE(H)-15,20) Reinfo...
- 93 - Piping connection Please follow the following procedures, during the piping connection work is carried out.If the procedures are not followed properly, the refrigerant and valve sheet might gush out from the ball valve.It might cause the injury. Warning. In case of Brazing type 1. Open the ba...
- 94 - In case of Flare, Flange type (1) Open the ball valve cap before cutting the by-pass tube.(Fig.1) (2) Check the ball valve section is completely closed.(Fig.2) (3) Cut two parts of the by-pass tube.(Fig.4) (4) Remove the connection pipe assy.(Fig.5) Throw away the packing.Do not brazing the p...
- 97 - •Incline the drain piping to the outside (drain side) as shown in the figure below.•The outlet of the indoor unit drain pipe is Rc1.•After completion of piping, confirm that drainage is good and that there are no leaks. Indoor unit drain piping Install thermal insulation to prevent dew The dr...
- 98 - Construct the earth connection.All electrical work must be carried out by a suitable qualified electrical trades-person and inaccordance with local supply authority requirements and associated regulators.The outdoor unit is to be wired directly from an electrical distribution board either by ...
- 99 - Control module of outdoor unit PU(H)-7, 8, 10 Control module of outdoor unit PU-15 Upper blow PUH only PUH only PUH only Terminal block forconnection wires toIndoor unit Terminal block forpower supply wires Band for wires Screw for earthconnection Control module of outdoor unit PUH-15,20 52C2...
- 100 - Method for connecting electric wire Please do the wiring after consulting the electric powercompany of jurisdiction beforehand in the instruction. (1) The entire wiring diagram of unit. a. b. c. d. e. Power supply Main switch/fuse (field supply) Outdoor unit (2) Power supply construction and...
- 101 - (3) Indoor unit and remote controller.(OPTION:PAC-204RC) TB4 CZ1 FZ 24V A C(N) COMP1 F A N HI 2 3 TB4 1 F2(3.15A) GRAY GRAY TB3 CZ 1-1 CZ 1-2 FZ 24V A C (N) COMP1 COMP2 F A N HI 2 3 4 TB3 1 F2(3.15A) GRAY GRAY AC24V AC220 240V Tr Tr 24V A C(L) 24V A C(L) 5 4 AC24V AC220 240V Connect the wire...
8. Before starting the Trial run. Check items Perform trial operation after completion of the above items. (1) Check to see wheter there are refrigerant leakage, and slack power or transmission cable. (2) Conform that 500V megohmmeter shows 1.0M ohm or more between power supply terminal and ground. ...
- 103 - INSTRUCTIONS FOR USE 1.Check points for operation. Check the following points before you operate your air conditioner. (1)Check that there is nothing blocking the flow of air from the air outlet into the air inlet. Indoor unit Outdoor unit (2)Make sure the air conditioner is properly grounde...
- 104 - 2.Caution for use. Keep the following points in mind to safeguard against failures and breakdowns. (1) This air conditioner does not restart within 3min. after shut down. (These models have a crankcase heater in the compressor. If the air conditioner is shut down for a short time, please do ...
- 105 - 3.3 Cleaning the Outdoor Unit Heat Exchanger If you use your air conditioner for prolonged periods, the outdoor heat exchanger will become dirty, impairing its function and reducing air conditioners performance. Consult your equipment supplier or air conditioning contractor on how to clean t...
- 108 - HOW TO OPERATE (OPTION PAC-204RC) For purposes of explanation, all the displays on this page are shownin their lit condition. This configuration does not occur in the actual unit. Operation mode Displays the status of operation.[Checking] Display This displays indication when some abnormalit...
- 109 - 1 A Operation mode display A 1-2 Selecting operation When selecting operation Press the [MODE] button Consecutive press of the [MODE] button switches the operation over to "FAN", "COOL", "HEAT" and "AUTO". For the contents of operation,check the display. For f...
- 111 - 1-6.Trouble shooting Before you ask for repair service, check the following points: Error Display State of Machine Cool air or warm air does not come out. Cause Remote Controller Air flows out but it does not cool enough or heatenough. It does not run Troubleshooting The liquid crystal displ...
- 112 - SPECIFICATION GUIDELINES Due to continuous product development, these guidelines are subject to change. Air to air reverse cycle split air conditioning system. The systems shall operate at out door ambient temperatures as high as . The system shall have a total cooling capacity of kW or grea...
HEAD OFFICE DENKI BLDG., MARUNOUCHI,TOKYO 100-0005,TELEX J24532 CABLE MELCO TOKYO MITSUBISHI ELECTRIC CORPORATION Issuued in Dec. 1999 MEE99K014 New publication effective Dec. 1999. Specifications subject to change without notice. DATA BOOK PE,PEH
Mitsubishi Electric Manuals
-
Mitsubishi Electric WD-73835
Manual
- Mitsubishi Electric SW2D5C-GTWK2-E Manual
-
Mitsubishi Electric WD-57734
Manual
-
Mitsubishi Electric E-20TP
Manual
-
Mitsubishi Electric A1SJ71E71N-B2
Manual
-
Mitsubishi Electric CK-35308
Manual
-
Mitsubishi Electric WS-65411
Manual
-
Mitsubishi Electric HS-S8300E(BRS)
Manual
-
Mitsubishi Electric DX-PC25EA
Manual
-
Mitsubishi Electric XL5980LU
Manual
-
Mitsubishi Electric XL6500U
Manual
-
Mitsubishi Electric 1770G
Manual
-
Mitsubishi Electric WT-42413
Manual
-
Mitsubishi Electric WD-57831
Manual
-
Mitsubishi Electric MSH-A18ND
Manual
-
Mitsubishi Electric WD-60C8
Manual
-
Mitsubishi Electric XL650U
Manual
-
Mitsubishi Electric HL2750U
Manual
-
Mitsubishi Electric MSZ-GE09NA
Manual
-
Mitsubishi Electric P40
Manual