Mitsubishi Electric OC366 - Manuals
Mitsubishi Electric OC366 – Manual in PDF format online.
Manuals:
Manual Mitsubishi Electric OC366
Summary
3 PUMY-P36NHMU PUMY-P36NHMUR1PUMY-P36NHMU-BS PUMY-P36NHMUR1-BSPUMY-P48NHMU 2 PUMY-P48NHMUR3 PUMY-P48NHMU 2 -BS PUMY-P48NHMUR3-BS • THERMISTOR has been changed. (Discharge thermistor → Compressor thermistor) • Compressor has been changed. PUMY-P48NHMU 1 PUMY-P48NHMU 2 PUMY-P48NHMU 1 -BS PUMY-P48NHMU ...
4 (4) Determine Fan Airflow setting during Indoor Thermo OFF conditions: a) These settings are done within Indoor DIPSW1-7 and DIPSW1-8, see chart below for options.b) Recommended SW1-7 OFF and SW1-8 ON will determine airflow based on "Setting on the remote controller". Fan speed setting Fan...
6 [1] Cautions for service (1) Perform service after recovering the refrigerant left in unit completely.(2) Do not release refrigerant in the air.(3) After completing service, charge the cycle with specified amount of refrigerant.(4) When performing service, install a filter drier simultaneously. Be...
8 2-3. Cautions for refrigerant piping work New refrigerant R410A is adopted for replacement inverter series. Although the refrigerant piping work for R410A is same as for R22, exclusive tools are necessary so as not to mix with different kind of refrigerant. Furthermore as the working pressure of R...
9 3 OVERVIEW OF UNITS 3-1. UNIT CONSTRUCTION Decorative panel Model Ceiling Ceiling Ceiling Concealed mounted Wall Mounted Concealed 4-way flow 2-way flow 1-way flow built-in Exposed Concealed (Fresh Air)*1 PLFY-P PLFY-P PMFY-P PEFY-P PDFY-P PKFY-P PCFY-P PFFY-P PEFY-P Capacity NCMU-E NBMU-E NLMU-E ...
11 4 SPECIFICATIONS PUMY-P36NHMU(-BS) PUMY-P36NHMUR1(-BS) Cooling Capacity Btu/h *3*3*3*3*3*3*3*3 36,000 Heating Capacity Btu/h Btu/h/W W/W 40,000 3.22 14.23/15.74 98.42.93 12.88/14.24 98.9 11.18 4.00 Input (Cool) kW Input Current (Cool)Power factor (Cool) A % % Input (Heat) kW Input Current (Heat)P...
13 5 DATA 5-1. COOLING AND HEATING CAPACITY AND CHARACTERISTICS 5-1-1. Method for obtaining system cooling and heating capacity: To obtain the system cooling and heating capacity and the electrical characteristics of the outdoor unit, first add up the ratings of all the indoor units connected to the...
16 5-3. CORRECTING COOLING AND HEATING CAPACITY 5-3-1. Correcting Changes in Air Conditions (1) The performance curve charts (Figure 1, 2) show the ratio by the temperature condition change when the rated capacity (total capacity) and the rated input are presumed 1, under standard length (7.6 m [25 ...
17 (2) Method for Obtaining the Equivalent Piping Length Equivalent length for type P48 = (length of piping to farthest indoor unit) + (0.3 o number of bends in the piping) (m) Length of piping to farthest indoor unit: 80 m [262 ft] 5-3-3. Correction of Heating Capacity for Frost and Defrosting If h...
18 6 OUTLINES AND DIMENSIONS PUMY-P48NHMU PUMY-P48NHMU-BS PUMY-P48NHMU 1 PUMY-P48NHMU 1 -BS Unit : mm <inch> Min.500mm <19-1 1/16> Min.500mm <19-1 1/16> Min.150mm <5-29/32> Min.10mm<3/8> Handle Side Air Intake Front piping cover Rear piping cover Air intake Rear Air Int...
20 7 WIRING DIAGRAM PUMY-P48NHMU PUMY-P48NHMU-BS PUMY-P48NHMU 1 PUMY-P48NHMU 1 -BS 1 2 3 4 5 6 7 8 [Example] When the compressor and SV1 are turned during cooling operation. SYMBOL NAME SYMBOL NAME SYMBOL NAME TB1 Terminal Block <Power Supply> TB3 Terminal Block <Transmission> TB7 Termin...
23 CNDC (PIN) CNAF (WHT) CN2 (WHT) CN3 (WHT) CN4 (WHT) CN5 (RED) CNAC2 (RED) E I E2 CN5 (RED) CN52C (BLK) CNAC1 (WHT) LO NO L I N I TABP2 TABU TABW TABN2 TABN1 TABV TH8 IPM CE TABNTABP TABP1 TABT DS3 DS2 TABS RED BLU BLU BLU WHT WHT 52C RED RED BLK BLK BLK WHT RED RED RED RED RED WHT YLW YLW P. B. N...
24 0 1 2 3 4 5 67 89 0 1 2 3 4 5 67 89 0 1 2 3 4 5 67 89 0 1 2 3 4 5 67 89 0 1 2 3 4 5 67 89 0 1 2 3 4 5 67 89 051 0 1 2 3 4 5 67 89 0 1 2 3 4 5 67 89 056 001 0 1 2 3 4 5 67 89 0 1 2 3 4 5 67 89 010 101 1 0 1 2 3 4 5 67 89 0 1 2 3 4 5 67 89 0 1 2 3 4 5 67 89 0 1 2 3 4 5 67 89 002 102 104 154 11 1 1 ...
28 B. Example of a group operation system with 2 or more outdoor units and a M-NET remote controller. (Shielding wires and address settings are necessary.) Examples of T ransmission Cable Wiring M1M2 S M1 M2 S TB7 TB3 IC (51) M1 M2 S TB5 RC (01) IC M1 M2 S TB5 (03) IC M1 M2 S TB5 (02) IC M1 M2 S TB5...
29 • Name, Symbol, and the Maximum Units for Connection Permissible Length Prohibited items • Longest length via outdoor units : L 1 +L 2 +L 3 +L 4, L 1 +L 2 +L 3+ L 5, L 1 +L 2 +L 6 +L 7 [ 500 meters [1640 ft] (1.25 mm 2 [AWG16]) • Longest transmission cable length : L 1, L 3 +L 4 , L 3+ L 5 , L 6,...
33 • Name, Symbol, and the Maximum Units for Connection Permissible Length Prohibited items • Never connect together the terminal blocks (TB5) for transmission wires for indoor units (IC) that have been connected to different outdoor units (OC). • M-NET remote controller and MA remote controller can...
34 9 TROUBLESHOOTING NOTE 1 : If error code appears on remote controller or remote controller malfunction , refer to “ 9-1-3. Countermeasures for Error During Run”.NOTE 2 : During test run operation 2-hours off timer activates automatically and remaining time is on remote controller and test run sto...
37 9-1-3. Countermeasures for Error During Test Run • If a problems occurs during test run, a code number will appear in the temperature display area on the remote controller (or LED on the outdoor unit), and the air conditioning system will automatically cease operating. Determine the nature of the...
42 on 2 1 3 4 5 6 7 8 Overvoltage or voltage shortage Abnormal if any of followings are detected during compressor operation; • Decrease of DC bus voltage to 310V• Instantaneous decrease of DC bus voltage to 200V.• Increase of DC bus voltage to 400V.• Decrease of input current of outdoor unit to 0.5...
43 5101 Display Abnormal point and detecting method Causes Check points Room temperature thermistor (TH21) When controller detects short (high temp.)/open (low temp.) in thermistor during the operation, the operation stops and the operation changes to protect mode of restarting in 3 minutes. If the ...
44 5102 Liquid pipe temperature thermistor (TH22) When the thermistor detects short/open during the operation, the operation stops and the operation changes to protect mode of restarting in 3 minutes. If the thermistor does not recover in 3 minutes, the operation stops due to detecting abnormality. ...
48 6603 Transmission bus busy error Over error by collision The transmission processor cannot betransmitted since a short cycle voltage of the noise etc. mixes on the transmission line consecutively. Check whether the transmission line of the indoor unit, fresh master, lossnay and remote controller ...
49 6607 No ACK (Acknowledgement) Abnormality which controller of the sending side detects when there is no answer (ACK) from other side though data was transmitted once. It is detected 6 times every 30seconds continuously. Factor that does not related to origin Turn off power supply of outdoor unit,...
53 Transmission data from remote controllerTransmission data on transmission path When the number of data errors is "02": · MA remote controller is equipped with the diagnosis function If the air conditioner cannot be operated from the remote controller, diagnose the remote controller as exp...
54 ON/OFF CENTRALLY CONTROLLED ERROR CODE CLOCK ON OFF °C CHECK CHECK MODE FILTER TEST RUNFUNCTION °C 1Hr. NOT AVAILABLE STAND BY DEFROST FILTER CHECK TEST TEMP. TIMER SET “ ” indicator: Appears when current is carried. (M-NET Remote controller) (1) For M-NET remote controller systems Symptom or ins...
61 Check method of multi controller board Normal LED1 LED2 Fuse checkCheck the fuse on Multi controller board Did the fuse (F500) blow? Replace Multi board and fan motor. *See DC fan check Did the fuse (F1 and F2) blow? Check the SV1 and 21S4 and wiring. 7seg LED is lit? (SW1 : all off) 280V to 350V...
62 Check method of power board Normal Is the voltage of main incoming power 208/230V AC ? *Check the breaker and power supply Is the voltage to the compressor(U-V,U-W and V-W) balanced ? *To check the voltage of the parts on this board with a tester is difficult due to its location. Test points are ...
63 Check method of noise fi lter circuit board Normal Is the voltage of main incoming power 208/230V±10% AC ? *Check the breaker and power supply Is the voltage of CNAC (RED) on multi board CNAC (RED) 208/230V±10% AC? *Check wiring*Replace noise filter board Is the voltage of CNDC(PNK) on multi boar...
64 Check method of ACTM Normal Is the voltage of main incoming power 208/230V ± -10% AC? *Check the breaker and power supply *To check the voltage of the parts on this board with a tester is difficult due to its location. Test points are limited. Is the voltage of CNDC(PNK) on multi board 330 - 350V...
65 Check method of M-NET transmission power board Normal 24-30V DC ? *Correct the short circuit point on the M-NET transmission line. 24-30V DC ? Is the incoming main voltage208/230V ±10% AC ? *Check wiring*Replace M-NET transmission power board *Check breaker and incoming power supply*Check noise f...
66 0 10 20 30 40 50 -20 -10 0 10 20 30 40 50 -4 -14 32 50 68 86 104 122 °F Temperature Resistance (k ) 500 400 300 200 100 0 25 50 75 100 120 77 122 167 212 248 °F Temperature Resistance (k ) <Thermistor feature chart> Low temperature thermistors • Thermistor <Outdoor pipe> (TH3)• Thermi...
72 Active filter modulePUMY-P48NHMUPUMY-P48NHMU-BSPUMY-P48NHMU 1 PUMY-P48NHMU 1 -BS DCL L1 L2 ACTM P I N1N2 (+) (- ) Load + Connection and internal circuit diagram L1, L2Connect to the DCL(Reactor) Connect to the 52C Connect to the outdoor power circuit board (TABN1) + – INot used N2Connect to the o...
74 9-10. OUTDOOR UNIT FUNCTIONS SW:setting 0....OFF 1....ON 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 SW1 setting 12345678 00000000 10000000 01000000 11000000 00100000 10100000 01 100000 11 100000 00010000 10010000 01010000 11010000 001 10000 101 10000 01 110...
75 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 SW1 setting 12345678 1111 1000 00000100 10000100 01000100 11000100 00100100 10100100 01 100100 11 100100 00010100 10010100 01010100 11010100 001 10100 101 10100 01 11 0100 1111 0100 00001 100 IC1 operation mode IC2 operation mode IC3 ...
76 64 65 66 67 69 70 71 72 73 74 75 76 77 78 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 SW1 setting 12345678 00000010 10000010 01000010 11 000010 10100010 01 100010 11 100010 00010010 10010010 01010010 11 010010 001 10010 101 10010 01 110010 00001010 10001010 01001010 11 001010 00101010 1010...
77 Display of target subcool step data Display of indoor SC/SH data Display of discharge superheat data Display of all control target data Display of detection data from high-pressure sensor and each thermistor Display of actual frequency at time of abnormality delay Display of fan step number at ti...
79 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 192 193 195 196 197 198 199 200 201 202 203 204 206 207 208 209 210 SW1 setting 12345678 1111 01 01 00001 101 10001 101 01001 101 11 001 101 00101 101 10101 101 01 101 101 11 101 101 00 0111 01 1001 1101 0101 1101 1101 11 01 00 1111 01 1...
80 21 1 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 SW1 setting 12345678 11 00101 1 0010101 1 1010101 1 01 10101 1 11 10101 1 0001 101 1 1001 101 1 0101 101 1 1101 101 1 001 11 01 1 101 1101 1 01 111 01 1...
81 10 ELECTRICAL WIRING 10-1. OVERVIEW OF POWER WIRING 10-2. WIRE DIAMETER AND MAIN POWER SWITCH CAPACITY 10-2-1. Wiring diagram for main power supply 10-2-2. Power supply wire diameter and capacity This chapter provides an introduction to electrical wiring for the CITY MULTI-S series, together with...
82 10-3. DESIGN FOR CONTROL WIRING Please note that the types and numbers of control wires needed by the CITY MULTI-S series will depend on the remote con-trollers and whether they are linked with the system. 10-3-1. Selection number of control wires 10-3-3. M-NET Remote controller wiring 10-3-2. Co...
83 (3) Method of obtaining system power factor Use the following formula and the total power and current obtained in parts 1 and 2 in the above table to calculate the system power factor. System power factor = (Total system power consumption) (Total system current x voltage) o 100% 10-6-2. Applying ...
84 11 REFRIGERANT PIPING TASKS Line-Branch Method Connection Examples(Connecting to 4 Indoor Units) Liquid Line Gas Line Piping Diameter (mm [inch]) Model PUMY-P36,48 Liquid Line (mm [inch]) Gas Line (mm [inch]) W 15.88 [5/8] W 9.52 [3/8] Liquid Line Gas Line Liquid Line Gas Line Piping Diameter (mm...
87 Indoor unit The smallest room The second smallest room Outdoor unit Ventilation apparatus Indoor unit Opening Wall Outdoor unit (Situation in which there are no door openings or in which there are open- ings above and blow doors that occupy at least 0.15% of the floor area) Indoor unit Outdoor un...
88 12 DISASSEMBLY PROCEDURE OUTDOOR UNIT :PUMY-P36NHMU(-BS) PUMY-P36NHMUR1(-BS)PUMY-P48NHMU(-BS) PUMY-P48NHMU 1 (-BS) PUMY-P48NHMU 2 (-BS) PUMY-P48NHMUR3(-BS) Continued to the next page. OPERATING PROCEDURE PHOTOS & ILLUSTRATION 1. Removing the service panel and top panel (1) Remove 3 service pa...
89 OPERATING PROCEDURE PHOTOS & ILLUSTRATION Photo 4 (6) Remove electrical parts box fixing screw (4 × 10) and detach the electrical parts box by pulling it upward. The electrical parts box is fixed with 2 hooks on the left and 1 hook on the right. Electrical parts box Electrical parts box fixin...
90 4-way valve coil (21S4) 7. Removing the 4-way valve coil (21S4) (1) Remove the service panel. (See Figure 1)(2) Remove the top panel. (See Figure 1) [Removing the 4-way valve coil] (3) Remove 4-way valve solenoid coil fixing screw (M4 × 6).(4) Remove the 4-way valve coil by sliding the coil towar...
91 OPERATING PROCEDURE PHOTOS 9. Removing bypass valve coil (SV1) and bypass valve (1) Remove the service panel. (See Figure 1)(2) Remove the top panel. (See Figure 1)(3) Remove 5 right side panel fixing screws (5 × 12) in the rear of the unit and remove the right side panel. (4) Remove the bypass v...
92 Accumulator OPERATING PROCEDURE PHOTOS 12. Removing the compressor (MC) (1) Remove the service panel. (See Figure 1)(2) Remove the top panel. (See Figure 1)(3) Remove 2 front cover panel fixing screws (5 × 12) and remove the front cover panel. (See Photo 3) (4) Remove 2 back cover panel fixing sc...
93 1 2 3 4 5 6 7 8 6 9 11 10 12 13 13-1. STRUCTURAL PARTSPUMY-P48NHMU PUMY-P48NHMU-BSPUMY-P48NHMU 1 PUMY-P48NHMU 1 -BS Part No. Part Name Specification No. Wiring Diagram Symbol Recom- mended Q , ty PUMY-P48 NHMU(-BS) PUMY-P48 NHMU 1 (-BS) Remarks (Drawing No.) 1 2 3 4 5 6 7 8 9 10 11 12 13 1 2 1 1 ...
95 Part No. Part Name Specification No. Wining Diagram Symbol Recom- mended Q , ty Remarks (Drawing No.) Q,ty/set 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 2 2 2 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 : 2.5 : 0.8 1000mm [ : (3...
96 26 25 27 29 28 21 24 23 22 1 2 3 10 11 12 13 14 15 16 17 18 19 20 4 7 8 9 5 6 18 14-1. FUNCTIONAL PARTSPUMY-P36NHMU(-BS) PUMY-P36NHMUR1(-BS)PUMY-P48NHMU 2 (-BS) PUMY-P48NHMUR3(-BS) 14 RoHS PARTS LIST
97 Part No. Part Name Specification No. RoHS Wining Diagram Symbol Recom- mended Q'ty Remarks (Drawing No.) Q'ty/set 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G 2 2 2 2 1 1 1...
98 1 2 3 4 5 6 7 8 6 9 11 10 12 13 14 14-2. STRUCTURAL PARTSPUMY-P36NHMU(-BS) PUMY-P36NHMUR1(-BS)PUMY-P48NHMU 2 (-BS) PUMY-P48NHMUR3(-BS) Part No. Part Name Speci- fication No. RoHS Wiring Diagram Symbol Recom- mended Q’ty PUMY-P36 NHMU(-BS) PUMY-P36 NHMUR1(-BS) PUMY-P48 NHMU 2 (-BS) PUMY-P48 NHMUR3...
99 15 OPTIONAL PARTS CMY-Y62-G-ECMY-Y64-G-E NUMBER OF BRANCHING POINTS 2 4 CMY-Y68-G-E 8 BRANCH PIPE (Joint) Part No. DRAIN SOCKET Part No. PAC-SG61DS-E AIR OUTLET GUIDE Part No. PAC-SG59SG-E DRAIN PAN Part No. PAC-SG64DP-E w Need 2 pieces. AIR GUIDE Part No. PAC-SH63AG-E w Need 2 pieces.
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO100-8310, JAPAN c Copyright 2006 MITSUBISHI ELECTRIC ENGINEERING CO., LTD. Distributed in Dec. 2010 No. OC366 REVISED EDITION-FDistributed in Sep. 2010 No. OC366 REVISED EDITION-E PDF 5Distributed in Nov. 2009 No. OC366 REVISED EDITION-D...
Mitsubishi Electric Manuals
-
Mitsubishi Electric WD-73835
Manual
- Mitsubishi Electric SW2D5C-GTWK2-E Manual
-
Mitsubishi Electric WD-57734
Manual
-
Mitsubishi Electric E-20TP
Manual
-
Mitsubishi Electric A1SJ71E71N-B2
Manual
-
Mitsubishi Electric CK-35308
Manual
-
Mitsubishi Electric WS-65411
Manual
-
Mitsubishi Electric HS-S8300E(BRS)
Manual
-
Mitsubishi Electric DX-PC25EA
Manual
-
Mitsubishi Electric XL5980LU
Manual
-
Mitsubishi Electric XL6500U
Manual
-
Mitsubishi Electric 1770G
Manual
-
Mitsubishi Electric WT-42413
Manual
-
Mitsubishi Electric WD-57831
Manual
-
Mitsubishi Electric MSH-A18ND
Manual
-
Mitsubishi Electric WD-60C8
Manual
-
Mitsubishi Electric XL650U
Manual
-
Mitsubishi Electric HL2750U
Manual
-
Mitsubishi Electric MSZ-GE09NA
Manual
-
Mitsubishi Electric P40
Manual