Page 2 - Centralized Ventilation Method; COMPARISON OF PRIMARY BUILDING VENTILATION METHODS; Energy Recovery Ventilators – Core; Lineup of LOSSNAY; CENTRALIZED CONTROLLER AG-150A; PRINCIPLES
LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certified to ARI 1060 Standard ERV-2 There are two main ventilation methods: Centralized Ventilation Method This is mainly used in large buildings, with the outside air intake being installed in one machine room. For this method, primary treatment of t...
Page 3 - Calculation of Total Energy Recovery Efficiency; air; ERV; Item; Construction; SA
ERV-3 LGH-F-RX3-E (Feb. 2009) Lossnay E RV LGH-F-RX3-E Performance Certified to ARI 1060 Standard 2.3. Calculation of Total Energy Recovery Efficiency The Lossnay ® Core’s energy recovery efficiency can be considered using the following three transfer rates: 1. Temperature (sensible heat) recovery ef...
Page 4 - Operation / Ventilation Modes; Supply side; Energy Recovery Efficiency Correction Curve; Energy Recovery; and; Bypass
LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certified to ARI 1060 Standard ERV-4 2.5. Lossnay ® Operation / Ventilation Modes Supply side Exhaust side Temperature t SA = t OA - (t OA - t RA ) x t t EA = t RA + (t OA - t RA ) x t Enthalpy i SA = i OA - (i OA - i RA ) x i i EA = i RA + (i OA - i R...
Page 5 - Automatic Ventilation Switching - Bypass Damper Operation; Effect of Automatic Ventilation Mode; use of office equipment. (Only when interlocked with CITY MULTI; Table 2 Major dust concentrations; Reference data
ERV-5 LGH-F-RX3-E (Feb. 2009) Lossnay E RV LGH-F-RX3-E Performance Certified to ARI 1060 Standard 2.6. Automatic Ventilation Switching - Bypass Damper Operation Effect of Automatic Ventilation Mode The automatic damper mode automatically provides the correct ventilation for the conditions in the roo...
Page 6 - Filter; MERV
LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certified to ARI 1060 Standard ERV-6 2.72. Calculation Table for Dust Collection Efficiency of each Lossnay ® Filter 2.7.3. Pressure Loss MERV Rating Dust Size (µm)* 6.6-8.6 6; 3.0-10.0 µm less than 49.9% * Note: MERV rating is estimation from efficien...
Page 7 - OFF; Energy Recovery Ventilation Terminology
ERV-7 LGH-F-RX3-E (Feb. 2009) Lossnay E RV LGH-F-RX3-E Performance Certified to ARI 1060 Standard Outdoor Air (OA) Air drawn from outdoors - ventilation air. Pulse Input When the control signal from an external device outputs a pulse such as the one shown at right, the pulse input control is perform...
Page 8 - MODELS AND SPECIFICATIONS; Model specifications and materials list for Lossnay
LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certified to ARI 1060 Standard ERV-8 3. LOSSNAY ® MODELS AND SPECIFICATIONS Model specifications and materials list for Lossnay ® units Model LGH-F300RX3-E Specifications Table Model LGH-F300RX3-E Dimensions Ceiling suspension Nominal Duct connecting Du...
Page 14 - Model LGH-F1200RX3-E Specifications Table; circuit board and requires two
LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certified to ARI 1060 Standard ERV-14 Model LGH-F1200RX3-E Model LGH-F1200RX3-E Model LGH-F1200RX3-E Specifications Table --Two addresses required. LGH-F1200RX 3 inches 65-7/16 48-7/16 31-1/2 40-9/16 50-1/8 8-3/4 ø14 ø13-3/4 29- 1/8 395 lb mm 1164 1230...
Page 15 - Model LGH-F1200RX3-E Characteristic Curve
ERV-15 LGH-F-RX3-E (Feb. 2009) Lossnay E RV LGH-F-RX3-E Performance Certified to ARI 1060 Standard Model LGH-F1200RX3-E * Attention 1. The defrost mode must be operated at 14°F or below. 2. The current, power consumption, and efficiency are based on the above air flow rate. 3. The sound at the air o...
Page 16 - ti; CIRCUIT BREAKER; Power; • Dotted lines represent field-supplied wire.
LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certified to ARI 1060 Standard ERV-16 E P L N A m 0 0 1 V 5 C D A 2 V 4 2 C D A m 0 0 1 V 0 2 2 C A A 2 V 0 4 2 C A N. I M X. A M tu pt u o ro ti n o m n oi ta re p O A m 0 0 1 V 5 C D A 1 V 4 2 C D A m 0 0 1 V 0 2 2 C A A 1 V 0 4 2 C A N. I M X. A M t...
Page 17 - CN16 is accessed using a PAC-715AD
ERV-17 LGH-F-RX3-E (Feb. 2009) Lossnay E RV LGH-F-RX3-E Performance Certified to ARI 1060 Standard LGH-F1200RX3-E • Dotted lines represent field-supplied wire. • Be sure to connect the ground wire. • Breaker should be provided by the customer. 0 1 0 1 ) U E n i d il a v n I( Z H 0 6 ~ V 0 2 2 Z H 0 ...
Page 18 - of hearing a conversation.
LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certified to ARI 1060 Standard ERV-18 The human ear senses differently according to frequency. However, sound generated from a vibration is not limited to one frequency but in - stead various frequencies are generated at different levels. This is expre...
Page 20 - FAN SPEED CONTROL CONSIDERATIONS; Installation diagram; Model
LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certified to ARI 1060 Standard ERV-20 7. INSTALLATION 7.1. Installation Diagrams LGH-F300 · F470 · F600RX types LGH-F1200RX type Note: The double control board for the LGH-F1200RX has two M-NET addresses. (1) The ceiling embedded type: 300, 470, 600 an...
Page 21 - T op/bottom reverse installation; Always insulate the two ducts leading outside the
ERV-21 LGH-F-RX3-E (Feb. 2009) Lossnay E RV LGH-F-RX3-E Performance Certified to ARI 1060 Standard 7.2. Alternate Installation for Lossnay T op/bottom reverse installation Vertical installation patterns Precautions Slanted installation Special Note ® ® All LGH-RX models can be installed in top/botto...
Page 22 - Installation and maintenance; A centralized controller can also be used.
LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certified to ARI 1060 Standard ERV-22 7.3. Selecting Duct Attachment Direction Installation and maintenance Installation applications ® ® ® ® ® ® Ø condensation. Choose between two directions for the outside duct (OA, EA) piping direction for optimum i...
Page 23 - ELECTRICAL INSTALLATION; Names of components in control box; Installation of Supplementary Fan Devices After Lossnay
ERV-23 LGH-F-RX3-E (Feb. 2009) Lossnay E RV LGH-F-RX3-E Performance Certified to ARI 1060 Standard 8. ELECTRICAL INSTALLATION Names of components in control box Ground Bushing Ground Bushing Bushing With this product, the wiring installation method will vary according to the design of the system. Pe...
Page 24 - so count each unit as two Lossnay; SYSTEM CONTROL EXAMPLES; Basic System – Stand-alone Lossnay
LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certified to ARI 1060 Standard ERV-24 Use Lossnay ® M-NET remote controller PZ-52SF-E. (Do not use PZ-41SLB-E). Lossnay ® transmission connection terminal Two remote controller system with multiple Lossnay units It is also possible to operate two remot...
Page 26 - System Selection; Interlocked with external device; Interlocked with Mr. Slim; Interlocked with CITY MULTI
LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certified to ARI 1060 Standard ERV-26 System Selection ERV-22 LGH-F-RX3-E Lossnay operation when indoor unit is stopped AvailableNot available Lossnay stopping when indoor unit is operatingSelecting Lossnay fan speed When interlocked with indoor unit f...
Page 27 - Centralized Control System with CITY MULTI
ERV-27 LGH-F-RX3-E (Feb. 2009) Lossnay E RV LGH-F-RX3-E Performance Certified to ARI 1060 Standard Centralized Control System with CITY MULTI ® Indoor unit Lossnay Indoor unit Outdoor unit A-control Mr. Slim P-Series outdoor unit Mr. Slim A-control PAR- 21 MAA remote controller A-control Mr. Slim in...
Page 28 - Remote controllers for CITY MULTI; Possible System Configurations
LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certified to ARI 1060 Standard ERV-28 Remote controllers for CITY MULTI ® indoor unit Remote controllers for . Slim ® indoor unit Remote controllers for Lossnay ® unit ® ® ® ® ® ® PAR-21MAA ON/OFF FILTER CHECK OPERATION CLEAR TEST TEMP. MENU BACK DAY M...
Page 29 - Combination with CITY MULTI; Lossnay
ERV-29 LGH-F-RX3-E (Feb. 2009) Lossnay E RV LGH-F-RX3-E Performance Certified to ARI 1060 Standard Combination with CITY MULTI ® --Independent Lossnay ® System with Lossnay ® AG-150A Centralized controller ® ® ® ® ® ® ® ® ® Lossnay ® M-NET remote Lossnay ® M-NET remote Lossnay ® M-NET remote Lossnay...
Page 30 - Not used to control
LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certified to ARI 1060 Standard ERV-30 Item Details Centralized controller MA remote controller ME remote controller Lossnay ® M- NET remote controller Local Remote Model ® OOO O O O O O O O O O o O o O o O o O o O OO O O O O O O Number of Lossnay ® rem...
Page 33 - Indoor Unit
ERV-33 LGH-F-RX3-E (Feb. 2009) Lossnay E RV LGH-F-RX3-E Performance Certified to ARI 1060 Standard MA Remote Controller/ME Remote Controller in Combination with LossnayM-NET Remote Controller Indoor Unit Lossnay LGH-RX type O O CENTRALIZED CONTROLLER AG-150A z AG-150A z
Page 34 - A mixed system including the CITY MULTI can also be configured.
LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certified to ARI 1060 Standard ERV-34 A mixed system including the CITY MULTI can also be configured. CENTRALIZED CONTROLLER AG-150A z AG-150A CENTRALIZED CONTROLLER AG-150A z AG-150A
Page 35 - Contents; When Using the LonWorks; Compatible Adaptor (LMAP03U) to Connect to LonWorks; • For specifications and functions of the LO; LonWorks
ERV-35 LGH-F-RX3-E (Feb. 2009) Lossnay E RV LGH-F-RX3-E Performance Certified to ARI 1060 Standard O Contents Individual Lossnay (Lossnay not set for interlocked operation) Interlocked Lossnay (Lossnay set for interlocked opera- tion with City Multi) When Using the LonWorks ® Compatible Adaptor (LMA...