Page 3 - Uninterruptible Power Systems; Revision History
Installation and User Manual i Galaxy 4000 40 – 75KVA Uninterruptible Power Systems Installation and User Manual Revision History Galaxy 4000 Installation and User Manual 86-173010-00 Revision: A00 ECN#: 004540 12/2005 Copyright © 2005 MGE UPS SYSTEMS, INC.All rights reserved. Printed in U.S.A. MGE ...
Page 4 - IMPORTANT SAFETY INSTRUCTIONS
Galaxy 4000 Important Safety Instructions ii 86-173010-00 A00 IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS – This manual contains important instructions for Galaxy 4000 that must be followed during operation and maintenance of the equipment. WARNING Opening enclosures expose hazardous volta...
Page 5 - WARNING; Environment
Installation and User Manual iii 86-173010-00 A00 WARNING HIGH LEAKAGE CURRENT. Earth connection essential before connecting supply. ATTENTION COURANT DE FUITE ELEVE. Raccordement a la terre indispensable avant le raccordement au reseau. WARNUNG! Hoher Ableitstrom Vor Inbetriebnahme Schutzleiterverb...
Page 7 - C o n t e n t s; section; Section 1; Introduction; Section 2; Setup and Installation
Contents C o n t e n t s I 86-173010-00 A00 section description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iIMPORTANT SAFETY INSTRUCTIONS . . . . . . ....
Page 8 - Section 3; Display Panel; Section 4; Operation; Section 5; Maintenance
Galaxy 4000 Contents II 86-173010-00 A00 Section 2 Setup and Installation (continued) section description page 2.4 Relay Communication Card Contacts . . . . . . . . . . . . . . . . . . . . .2 — 5 2.4.1 Relay Communication Card Connections . . . . . . . . . . . . . . . . . .2 — 6 2.4.2 Characteristic...
Page 9 - Section 6; Warranty, Registration & Customer Support; description; Glossary
Installation and User Manual III 86-173010-00 A00 Section 6 Warranty, Registration & Customer Support description page MGE Warranty & Proprietary Rights for Three Phase Products . . . . . . . . . . . . . .6 – 1 MGE Standard Three Phase WarrantyProprietary Rights Statement Warranty and Produc...
Page 10 - Figures; figure description; Tables; table
Galaxy 4000 IV 86-173010-00 A00 Figures figure description page 1-1 Galaxy 4000 UPS System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 1 1-2 Galaxy 4000 UPS System - Single Line Diagram . . . . . . . . . . . . . . . . . .1 — 2 1-3 Cabinet Placement, Airflow and Recomme...
Page 11 - Symbol Usage; Section Descriptions
Installation and User Manual V 86-173010-00 A00 Symbol Usage This manual uses five icon symbols with text to convey important information and tips. WARNING Indicates information provided to protect the user and service personnel against safety hazards and/or possible equipment damage. CAUTION Indica...
Page 13 - I n t r o d u c t i o n; Scope; General Description
I n t r o d u c t i o n 1.0 Scope Provides a general description of the Galaxy 4000 systems intended use, major components, mechanical and environmental specifications. 1.1 General Description The Galaxy 4000 is the world’s first data center grade Uninterruptible Power Supply system designed specifi...
Page 14 - Major Components; Rectifier; Single Line Diagram
Galaxy 4000 1 — 2 86-173010-00 A00 1.2 Major Components Rectifier Converts AC input voltage to DC voltage. The rectifier uses IGBT (Insulated G a t eBipolar Transistor) power transistors and a Pulse Width Modulated (PWM)technique to provide input power factor correction and to minimize any harmonicr...
Page 15 - Galaxy 4000 Standard Cabinets; OR –; Preparation for Operation; First; Forth; Cabinet Placement
Installation and User Manual 1 — 3 86-173010-00 A00 1.4 Galaxy 4000 Standard Cabinets The Galaxy 4000 individual cabinet dimensions are: ◗ UPS cabinet: 72.1in (1831mm) H x 33.5in (851mm) W x 35.6in (904mm) D. ◗ External battery cabinet: 72.1in (1831mm) H x 26.5in (673mm) W x 33.5in (851mm) D OR – ◗ ...
Page 16 - Cabinet Clearances; Conduit Plate Locations for Bottom Entry; UPS cabinet; FRONT VIEW
Galaxy 4000 1 — 4 86-173010-00 A00 Figure 1-3: Cabinet Placement, Airflow and Recommended Clearances. Table 1-1: Heat Rejection Data. N O T E : To provide for adequate ventilation, a minimum of 36 inches clearance shouldbe maintained above the top of the Galaxy 4000 cabinet. 1.8 Cabinet Clearances T...
Page 17 - Conduit Plate Locations for Top Entry
Installation and User Manual 1 — 5 86-173010-00 A00 Figure 1-4: Configuration for Bottom Entry. 1.10 Conduit Plate Locations for Top Entry The UPS cabinet for the Galaxy 4000 is capable of accepting power input and output cables through a top entry. The conduit plate on the top of the cabinet provid...
Page 19 - S e t u p a n d I n s t a l l a t i o n
S e t u p a n d I n s t a l l a t i o n 2.0 Scope Guides the user through tools and equipment required for unpacking and performing connections required for initial installation. Included are the electrical specifications, environmental recommendations and connection details. 2.1 Installation Steps ...
Page 20 - Electrical Specifications; Electrical Connections; CAUTION
2.2.2 Electrical Specifications Table 2-1: Electrical Specifications for the Galaxy 4000. NOTE: Interrupted Transfer to Bypass Source: If the bypass source is beyond the conditions stated below, the UPS will make an interrupted transfer (not more than 100 msec. in duration). 1. Bypass voltage greate...
Page 21 - UPS Connections; IMPORTANT; AC Output Connections
Installation and User Manual 2.3.1 UPS Connections Electrical connections and cabinet interconnection will vary depending upon the configuration and options selected with your Galaxy 4000 UPS system. Refer to the installation drawings supplied with your equipment. Connecting Power Cable Connections:...
Page 22 - Battery Control Connections
Figure 2-1: Typical Power Connections. 2.3.5 Battery Connections The connections to be made are the positive, negative, and ground cables from the battery cabinet to the UPS. The battery cables are terminated at the positive, negative, and ground busbars. See Figure 2-1. 2.3.6 Remote Emergency Power...
Page 23 - Relay Communication Card Contacts
Installation and User Manual 2.3.8 External Maintenance Bypass Control Connections (optional) The external maintenance bypass (MBP) control connections are made with the MBP control cable from the external MBP to the UPS terminal block TB4-9 to TB4-10. See Figure 2-1. ELECTRICAL These wires carry HI...
Page 24 - Relay Communication Card Connections
CAUTION Isolate and lock-out all power sources for this card before making c o n n e c t i o n s . Never connect ELSV (extra low safety voltage) and non-ELSV circuits to the different outputs of the same card. 2.4.1 Relay Communication Card Connections Refer to Figure 2-3 for relay communication car...
Page 27 - D i s p l a y P a n e l; MAIN MENU KEY
D i s p l a y P a n e l 3.0 Scope Describes the operator display panel, interface screens, keys, and mimic diagram. 3.1 Operator Interface Keys and Indicators The operator interface screens contained on the Galaxy 4000 display panel provide an easy to use method to access and control the Galaxy 4000...
Page 29 - Display Menu Structure
Installation and User Manual 3.2 Display Menu Structure This display menu structure is provided below for the Galaxy 4000 system in Figure 3-4. Figure 3-4: UPS Display Menu Structure. UPS MAIN MENU MEASUREMENTS MIMIC DIAGRAMS STATUS SETTINGS COMMANDS STARTUP PROCEDURE STARTUP PROCEDURE STARTUP UPS S...
Page 30 - Battery Measurements Screen
3.3 Main Menu Screen The Main Menu screen allows the operator to access many displays to monitor the operating performance of Galaxy 4000, obtain alarm information, change operational settings as well as issue software based commands. The Main Menu conveniently displays groups of items according to ...
Page 31 - NOTE; Power Measurements Screen
Installation and User Manual ◗ Battery temperature does not stay within ±10°C from the starting temperature point. ◗ Communication fault. ◗ Input current 0 amps or > 100% load current. ◗ Rectifier or inverter overload. ◗ Mains 1 or Mains 2 failure. In case the BPI cannot be done, a simplified aut...
Page 33 - Mimic Diagrams
Installation and User Manual 3.5 Mimic Diagrams The Mimic Diagrams screen is unlike any of the other screens we have examined. This screen is actually two screens in one. The top half of the screen contains a single line representation of the current operating condition of the Galaxy 4000 unit. Thro...
Page 35 - Commands Screen
Installation and User Manual 3.8 Commands Screen The Commands screen presents options that impact the operation of the UPS system. Extreme care should be exercised when selecting ANY of these menu options. See Figure 3-15. The Commands screen provides the following: Fault reset Allows the user to re...
Page 37 - O p e r a t i o n; Preparing for Startup; Pre-Startup Safety Check List
O p e r a t i o n 4.0 Scope Provides startup, shutdown, and normal operation of the Galaxy 4000 UPS. Included are pre and post startup safety checklists. The Galaxy 4000 system is simple to operate and yet provides a wealth of continuous monitoring and diagnostic features to ensure the proper operat...
Page 39 - Normal Startup Procedure
Installation and User Manual 4.2 Normal Startup Procedure With all of the initial safety check lists verified, the Galaxy 4000 UPS system can now be powered. The following startup procedure should be performed during the initial startup following installation and commis- sioning of the system (typic...
Page 41 - M a i n t e n a n c e; IMPORTANT SAFETY INSTRUCTIONS FOR SERVICING BATTERIES
M a i n t e n a n c e 5.0 Scope Describes maintenance and safety information on servicing batteries for the Galaxy 4000. 5.1 Servicing Batteries IMPORTANT SAFETY INSTRUCTIONS FOR SERVICING BATTERIES Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and ...
Page 44 - Warranty and Product Registration; User Information
Galaxy 4000 Warranty, Registration, & Customer Support 6 — 2 86-173010-00 A00 Warranty and Product Registration Thank you for choosing MGE UPS SYSTEMS, INC. for your power protection, distribution, and qualityrequirements. We are pleased to have you join our increasing family of users. In order ...
Page 47 - G l o s s a r y
G l o s s a r y Term used Definition / Meaning @ At. / And/or. +/- Plus or Minus. ≤ Equal to or less than. # Number. °C Degree Celsius. °F Degree Fahrenheit. Ø Phase angle. Ω Ohm; unit of resistance. ® Trade Mark. 2nd Second. ABC Normal sequence of phases in three phase power. AC or ac Alternating c...
Page 51 - R e o r d e r F o r m; Use this form
R e o r d e r F o r m 1660 Scenic Avenue Costa Mesa, CA 92626 Use this form to report any errors, omissions, or other problems you have experienced, or to order additional hardcopies of this document. A free copy of this document may be downloaded from the proprietary MGE Rep Website. Please contact...
Page 56 - Contact MGE; United States
w w w . m g e u p s . c o m 1660 Scenic Avenue, Costa Mesa, California 92626 • (714) 557-1636 Contact MGE United States MGE UPS SYSTEMS 1660 Scenic Ave.Costa Mesa, CA 92626 Tel: (714) 557-1636Fax: (714) 557-9788email: [email protected]: mgeups.com Canada MGE UPS SYSTEMS #9, 2789 Thamesgate DriveMis...