Page 2 - Johnson Controls Unitary Products; SPECIFIC SAFETY RULES AND PRECAUTIONS
505309-UIM-D-0511 2 Johnson Controls Unitary Products These high efficiency, compact units employ induced combustion, reli-able hot surface ignition and high heat transfer aluminized tubular heatexchangers. The units are factory shipped for installation in upflow orhorizontal applications and may be...
Page 3 - COMBUSTION AIR QUALITY
505309-UIM-D-0511 Johnson Controls Unitary Products 3 • This furnace is not approved for installation in trailers or recre- ational vehicles. • Furnaces for installation on combustible flooring shall not be installed directly on carpeting, tile or other combustible materialother than wood flooring. ...
Page 4 - INSPECTION
505309-UIM-D-0511 4 Johnson Controls Unitary Products INSPECTION As soon as a unit is received, it should be inspected for possible dam-age during transit. If damage is evident, the extent of the damageshould be noted on the carrier’s freight bill. A separate request forinspection by the carrier’s a...
Page 5 - DUCTWORK GENERAL INFORMATION; The duct system’s design and installation must:; Handle an air volume appropriate for the served space and within; If the duct; DUCT FLANGES; Duct Attachment
505309-UIM-D-0511 Johnson Controls Unitary Products 5 SECTION II: DUCTWORK DUCTWORK GENERAL INFORMATION The duct system’s design and installation must: 1. Handle an air volume appropriate for the served space and within the operating parameters of the furnace specifications. 2. Be installed in accor...
Page 6 - COIL INSTALLATION; Place the ductwork over the coil casing flange and secure.; Horizontal Right Application; Furnace
505309-UIM-D-0511 6 Johnson Controls Unitary Products COIL INSTALLATION COIL/FURNACE ASSEMBLY - MC/FC/PC SERIES COILS FURNACE ASSEMBLY - MC & FC SERIES COILS These coils are factory shipped for installation in either upflow or down-flow applications with no conversion. Position the coil casing o...
Page 7 - it will be necessary to seal the edges of the bottom panel; The internal bottom panel must be removed for this application.; COIL SIZE; Horizontal Left or Right application (Right Shown); NOTICE; Air flow; Gas Furnace; Combustible Floor Base Accessory
505309-UIM-D-0511 Johnson Controls Unitary Products 7 Dimension “C” should be at least 2/3 of dimension “D”. See Figure 6 CRITICAL COIL PROJECTION The coil assembly must be located in the duct such that a minimum dis-tance is maintained between the top of the coil and the top of the duct.Refer to Ta...
Page 8 - HORIZONTAL APPLICATION; Horizontal Application; Typical Suspended Furnace / Crawl Space Installation; LEFT SIDE VENT
505309-UIM-D-0511 8 Johnson Controls Unitary Products HORIZONTAL APPLICATION ATTIC INSTALLATION This appliance is certified for line contact when the furnace is installedin the horizontal left or right position. The line contact is only permissiblebetween lines that are formed by the intersection of...
Page 9 - FILTER INSTALLATION; Filters must be installed external to the furnace cabinet.; SIDE RETURN; Dimensions; FRONT; RIGHT SIDE; SUPPLY END; Cabinet and Duct Dimensions; Side Return Cutout Markings
505309-UIM-D-0511 Johnson Controls Unitary Products 9 SECTION III: FILTERS FILTER INSTALLATION All applications require the use of a field installed filter. All filters andmounting provision must be field supplied. Filters must be installed external to the furnace cabinet. DO NOT attempt to install ...
Page 10 - SECTION IV: GAS PIPING; GAS SAFETY; DANGER; Gas Valve; Upflow; Drip Leg; NOTE: Ground Union maybe installed inside or outside unit.
505309-UIM-D-0511 10 Johnson Controls Unitary Products HORIZONTAL APPLICATION Horizontal Filters Any branch duct (rectangular or round duct) attached to the plenummust attach to the vertical plenum before the filter. The use of strapsand/or supports is required to support the weight of the external ...
Page 11 - HIGH ALTITUDE GAS ORIFICE CONVERSION; SECTION V: ELECTRICAL POWER; ELECTRICAL POWER CONNECTIONS; Nominal Manifold Pressure - High Fire; Use copper conductors only.
505309-UIM-D-0511 Johnson Controls Unitary Products 11 GAS ORIFICE CONVERSION FOR PROPANE (LP) This furnace is constructed at the factory for natural gas-fired operation,but may be converted to operate on propane (LP) gas by using a factory-supplied LP conversion kit. Follow the instructions supplie...
Page 12 - SUPPLY VOLTAGE CONNECTIONS; Electrical Entry
505309-UIM-D-0511 12 Johnson Controls Unitary Products Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes.The furnace ...
Page 13 - Thermostat Chart - Single Stage AC with Single Stage PSC Furnaces; Two Stage Air Conditioner - Two Stage PSC Furnace
505309-UIM-D-0511 Johnson Controls Unitary Products 13 For additional connection diagrams for all Johnson Controls Unitary Products’ equipment refer to “Low Voltage System Wiring” document availableon-line at www.upgnet.com in the Product Catalog Section. FIGURE 18: Thermostat Chart - Single Stage A...
Page 14 - Thermostat Chart - Two Stage HP with Two Stage PSC Furnace
505309-UIM-D-0511 14 Johnson Controls Unitary Products FIGURE 19: Thermostat Chart - Two Stage HP with Two Stage PSC Furnace HP 22A O Reversing Valve Energized in Cool C 24 – Volt Common R 24 – Volt Hot W1 OUT First Stage Heat W2 OUT Second Stage Heat Y2 OUT Second Stage Compressor Y1 Single Stage C...
Page 15 - Typical Twinned Furnace Application; Vent Pipe
505309-UIM-D-0511 Johnson Controls Unitary Products 15 ACCESSORY CONNECTIONS The furnace control will allow power-switching control of various accessories. ELECTRONIC AIR CLEANER CONNECTION Two 1/4” (6.4 mm) spade terminals (EAC and NEUTRAL) for electronicair cleaner connections are located on the c...
Page 16 - Twinning Instructions; SECTION VII: CONDENSATE PIPING AND; CONDENSATE DRAIN LOCATION; Tee
505309-UIM-D-0511 16 Johnson Controls Unitary Products Twinning Instructions Connect the control wiring as shown in Figure 21. 1. Connect the low voltage wiring from the wall thermostat to the termi- nal strip on the control board of Furnace #1. 2. Connect a wire from the TWIN terminal of Furnace #1...
Page 17 - CONDENSATE DRAIN TERMINATION; Typical. Combustion Pipe Drain Tee; Connect to Drain
505309-UIM-D-0511 Johnson Controls Unitary Products 17 The condensate will flow to the drain better if an open stand pipe isinstalled in the drain line. See Figure 22. If evaporator coil or humidifier drains are combined with the furnacedrain, then the open stand pipe could be raised higher, above t...
Page 18 - Upflow Configuration; If rerouting hoses - excess length should be cut of; For 100, 120K input furnaces, the condensate drain is
505309-UIM-D-0511 18 Johnson Controls Unitary Products FIGURE 24: Upflow Configuration INDUCER ROT A TED FOR LEFT SIDE VENTING UPFLOW AS RECEIVED INDUCER ROT A TED FOR RIGHT SIDE VENTING When drain hose routing changes are required, be sure to cap all un-used openings. If rerouting hoses - excess le...
Page 19 - Downflow Configuration; AIRFLOW
505309-UIM-D-0511 Johnson Controls Unitary Products 19 FIGURE 25: Downflow Configuration AIRFLOW AIRFLOW Move rain gutter hose to this position. DOWNFLOW - INDUCER ROT A TED FOR LEFT SIDE VENTING DOWNFLOW - INDUCER ROT A TED FOR RIGHT SIDE VENTING Move pressure switch hose to this position. NOTE: Ma...
Page 20 - Horizontal Left Configuration
505309-UIM-D-0511 20 Johnson Controls Unitary Products FIGURE 26: Horizontal Left Configuration HORIZONT AL - LEFT INDUCER ROT A TED HORIZONT AL - LEFT INDUCER AS RECEIVED AIRFLOW AIRFLOW Move pressure switch hose to this position. NOTE: May require the longer hose that is provided with wider cabine...
Page 21 - Horizontal Right Configuration
505309-UIM-D-0511 Johnson Controls Unitary Products 21 FIGURE 27: Horizontal Right Configuration AIRFLOW HORIZONT AL - RIGHT INDUCER ROT A TED HORIZONT AL - RIGHT INDUCER AS RECEIVED Move rain gutter hose to this position. Move pressure switch hose to this position. Change condensate drain connectio...
Page 22 - SECTION VIII: COMBUSTION AIR AND; COMBUSTION AIR AND VENT SAFETY; The following rules must also be followed:; Model Input
505309-UIM-D-0511 22 Johnson Controls Unitary Products SECTION VIII: COMBUSTION AIR AND VENT SYSTEM COMBUSTION AIR AND VENT SAFETY This Category IV, dual certified direct vent furnace is designed for resi-dential application. It may be installed without modification to the con-densate system in a ba...
Page 23 - COMBUSTION AIR AND VENT PIPING ASSEMBLY; Fitting; FURNACE VENT CONNECTION SIZES
505309-UIM-D-0511 Johnson Controls Unitary Products 23 Dimensions are those required in Standard ASTM D-3311. Example: An 80,000 BTUH furnace requires 32 feet of pipe and five 90º elbows.Using 2" pipe and standard elbows, the total equivalent length will be: This exceeds the 65 foot maximum equi...
Page 24 - VENT CLEARANCES; Home Layout; Direct Vent Terminal Clearances
505309-UIM-D-0511 24 Johnson Controls Unitary Products VENT CLEARANCES † A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings. †† 12” (30.5 cm) up from the bottom edge of the structure for Two-pipe (direc...
Page 25 - VENT SYSTEM
505309-UIM-D-0511 Johnson Controls Unitary Products 25 VENT SYSTEM This furnace is certified to be installed with one of two possible ventconfigurations. 1. Horizontal vent system. This vent system can be installed com- pletely horizontal or combinations of horizontal, vertical, or offsetusing elbow...
Page 26 - DOWNWARD VENTING; OUTDOOR COMBUSTION AIR:; Outdoor Combustion Air; Combustion Air Intake/Vent Connections; Ambient Combustion Air Supply
505309-UIM-D-0511 26 Johnson Controls Unitary Products DOWNWARD VENTING In some applications, it may be necessary to run the vent pipe and airintake downwards. If this is to be done, the following rules must be fol-lowed. • A condensate trap hose must be connected to both the air intake pipe and the...
Page 27 - unconfined space; Combustion Air Source From Outdoors; Air Supply Openings and Ducts
505309-UIM-D-0511 Johnson Controls Unitary Products 27 An unconfined space is not less than 50 cu.ft (1.42 m 3 ) per 1,000 Btu/ hr (0.293 kW/h) input rating for all of the appliances installed in thatarea. Rooms communicating directly with the space containing the appli-ances are considered part of ...
Page 28 - Combustion Air Source from Outdoors; Specially Engineered Installations; VENT BLOWER ROTATION; Be sure to instruct the owner not to block this intake pipe.
505309-UIM-D-0511 28 Johnson Controls Unitary Products Combustion Air Source from Outdoors 1. Two permanent openings, one within 12” (30.5 cm) of the top and one within 12” (30.5 cm) of bottom of the confined space, Two per-manent openings, shall communicate directly or by means of ductswith the out...
Page 29 - ADJUSTMENTS; GAS PIPING LEAK CHECK; HOT SURFACE IGNITION SYSTEM
505309-UIM-D-0511 Johnson Controls Unitary Products 29 SECTION IX: START-UP AND ADJUSTMENTS The initial start-up of the furnace requires the following additionalprocedures: When the gas supply is initially connected to the furnace, the gas pipingmay be full of air. In order to purge this air, it is ...
Page 31 - ADJUSTMENT OF MANIFOLD GAS PRESSURE &; INLET GAS PRESSURE RANGE
505309-UIM-D-0511 Johnson Controls Unitary Products 31 ADJUSTMENT OF MANIFOLD GAS PRESSURE & INPUT RATE Inlet and manifold gas pressure may be measured by connecting the“U” tube manometer to the gas valve with a piece of tubing. Follow theappropriate section in the instructions below. Refer to F...
Page 32 - ADJUSTMENT OF TEMPERATURE RISE; MANIFOLD PRESSURE “U” TUBE CONNECTION; Furnace Control Board
505309-UIM-D-0511 32 Johnson Controls Unitary Products ADJUSTMENT OF TEMPERATURE RISE After about 5 minutes of operation, determine the furnace temperaturerise. Take readings of both the return air and the heated air in the ducts,about six feet (1.83 m) from the furnace where they will not be affect...
Page 33 - Models
505309-UIM-D-0511 Johnson Controls Unitary Products 33 NOTES: 1.Airflow expressed in standard cubic feet per minute (CFM).2.Return air is through side opposite motor (left side).3.Motor voltage at 115 V.4.Airflow through across motor side (right side) may be slightly less than the data shown above. ...
Page 34 - SECTION X: SAFETY CONTROLS; Continuous Blower
505309-UIM-D-0511 34 Johnson Controls Unitary Products SECTION X: SAFETY CONTROLS CONTROL CIRCUIT FUSE A 3-amp fuse is provided on the control circuit board to protect the 24-volt transformer from overload caused by control circuit wiring errors.This is an ATO 3, automotive type fuse and is located ...
Page 35 - FURNACE CONTROL DIAGNOSTICS; LED STEADY OFF
505309-UIM-D-0511 Johnson Controls Unitary Products 35 FURNACE CONTROL DIAGNOSTICS The furnace has built-in, self-diagnostic capability. A blinking LED lighton the control board can flash red, green or amber to indicate variousconditions. The control continuously monitors its own operation and theop...
Page 36 - DIAGNOSTIC FAULT CODE STORAGE AND; SECTION XII: REPLACEMENT PARTS LIST; REPLACEMENT PART CONTACT INFORMATION
505309-UIM-D-0511 36 Johnson Controls Unitary Products DIAGNOSTIC FAULT CODE STORAGE AND RETRIEVAL The control in this furnace is equipped with memory that will store up tofive error codes to allow a service technician to diagnose problemsmore easily. This memory will be retained even if power to th...
Page 37 - SECTION XIII: WIRING DIAGRAM; Wiring Diagram; LEGEND; LEGENDE; Wiring
505309-UIM-D-0511 Johnson Controls Unitary Products 37 SECTION XIII: WIRING DIAGRAM FIGURE 43: Wiring Diagram LEGEND DSDoorswitch MOTCirculatin g motor LSLimitswitch ROSRolloutswitch IDMInducermotor HUMHumidif ier XFMRTransformer EACElectronic aircleaner FSFlames enso r HSIHotsurfaceigniter GVGas va...
Page 38 - Copyright
Subject to change without notice. Published in U.S.A. 505309-UIM-D-0511 Copyright © 2011 by Johnson Controls, Inc. All rights reserved. Supersedes: 505309-UIM-C-0910 Johnson Controls Unitary Products 5005 York Drive Norman, OK 73069