Pressure Drop Data FSD-M211 This pressure drop testing was conducted in accordance with AMCA Standard 500-D using the three configurations shown. All data has been corrected to represent standard air at a density of 1.201 kg/m3. Actual pressure drop found in any HVAC system is a combination of many ...
AMCA 5.2 Pressure Drop FSD-M211 5D 6D 5D D = 4 (W) (H ) 3.14 Figure 5.3 Figure 5.2 Figure 5. 5 NNYNN NNYNN NNYNN NNYNN NNYNN 13&4463&%3011 "4$"-4 '"$&7&-0$*5:.&5&344&$0/% ".$" 7&-0$*5:7413&4463&%301 Y Y Y Y Y 305mm x 305mm Velocity (m/s) Pr...
305mm x 305mm Velocity (m/s) Pressure Drop (Pa) 2.4 5 5.1 22 7.8 52 10.3 92 12.9 145 15.4 209 17.7 274 20.8 379 610mm x 610mm Velocity (m/s) Pressure Drop (Pa) 2.5 3 5 10 7.7 22 10.3 40 12.8 62 15.5 92 17.9 122 20.8 167 914mm x 914mm Velocity (m/s) Pressure Drop (Pa) 2.5 3 5.1 8 7.6 15 10.1 27 12.8 ...