Installation 2 309920D Installation 1. Before installing air line components, blow out the pipe line to remove debris. Be sure air to the regula-tor is clean. Erratic operation or loss of regulation is usually caused by dirt in the regulator. 2. Install the Air Drying System as close as possible to ...
Shop Air Piping Layout 309920D 3 Minimum Pipe Size Recommendations Compressor Main Air Line Size Capacity Length Size 1-1/2 - 2 HP 6 - 9 CFM any 3/4” (19 mm) 3 - 5 HP 12 - 20 CFM Up to 200 ft. (61 m) 3/4” (19 mm) Over 200 ft. (61 m) 1” (25.4 mm)) 5 - 10 HP 20 - 40 CFM Up to 100 ft. (30.5) 3/4” (19 m...
Operation 4 309920D Operation 1. Attach air hose(s) to air regulator outlet valve 289165. 2. Open main shut-off valve 288798. 3. Turn the T-hand adjusting screw in or out to adjust regulator to desired setting. 4. Open outlet valve 289165 to supply air to spray guns or tool. 5. With air flowing, rea...