Page 2 - Quick Installation Guide; Rosemount 3095 MultiVariable; Emerson Process Management GmbH & Co. OHG; IMPORTANT NOTICE; Explosions could result in death or serious injury:; when power is applied to the unit.; Process leaks may cause harm or result in death.; leads can cause electrical shock.
Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable 2 © 2009 Rosemount Inc. All rights reserved. All marks property of owner. Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc. Rosemount Inc. 8200 Market BoulevardChanhassen, MN USA...
Page 3 - RANSMITTER
Quick Installation Guide 00825-0100-4716, Rev DAOctober 2009 Rosemount 3095 MultiVariable 3 T RANSMITTER E XPLODED V IEW Housing O-ring Cover Housing Locking Screw RTD Connector Process Adapter O-ring Electronics Board Nameplate Module O-ring Sensor Module Drain/Vent Valve Flange Adapter O-ring Opti...
Page 4 - TEP; Liquid Flow Applications; valves are oriented upward.; Gas Flow Applications; Panel Mount; Pipe Mount
Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable 4 S TEP 1: M OUNT THE T RANSMITTER Figure 1. Using a Mounting Bracket Liquid Flow Applications 1. Place taps to the side of the line.2. Mount beside or below the taps.3. Mount the transmitter so that the drain...
Page 5 - Consider Housing Rotation; To improve field access or to better view the optional LCD display:; Field Installation; Mount the transmitter; Bolt Material
Quick Installation Guide 00825-0100-4716, Rev DAOctober 2009 Rosemount 3095 MultiVariable 5 S TEP 2: T RANSMITTER I NSTALLATION Consider Housing Rotation To improve field access or to better view the optional LCD display: 1. Loosen the housing rotation set screw. 2. Rotate the housing clockwise to t...
Page 6 - fieldbus devices), which is located on the front of; HART Electronics Board; fieldbus Electronics Board
Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable 6 S TEP 2 CONTINUED ... 3. Set the Failure Mode Alarm (HART devices), which is located on the front of the electronics board inside the electronics housing cover. The Alarm Jumper position determines if the ou...
Page 7 - • Installing a Shielded 3095 RTD Cable (See Figure 4); • Installing a ATEX/IECEx Flameproof 3095 RTD Cable (See Figure 5); Check all process connections for leaks.
Quick Installation Guide 00825-0100-4716, Rev DAOctober 2009 Rosemount 3095 MultiVariable 7 S TEP 2 CONTINUED ... • Installing a Shielded 3095 RTD Cable (See Figure 4) Note: Shielded cable is intended for use in a conduit.a. Fully engage the black cable connector to the 3095 RTD Connector.b. Tighten...
Page 8 - Bolting Considerations; Use the following bolt installation procedure:; Coplanar Flange
Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable 8 S TEP 2 CONTINUED ... Bolting Considerations If the transmitter installation requires assembly of the process flanges, manifolds, or flange adapters, follow these assembly guidelines to ensure a tight seal f...
Page 9 - O-rings with Flange Adapters; WARNING
Quick Installation Guide 00825-0100-4716, Rev DAOctober 2009 Rosemount 3095 MultiVariable 9 S TEP 2 CONTINUED ... Figure 7. Torque values for the flange and flange adapter bolts O-rings with Flange Adapters WARNING Whenever the flanges or adapters are removed, visually inspect the o-rings. Replace t...
Page 10 - 095 Engineering Assistant (EA) for HART Software Installation
Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable 10 S TEP 3: S OFTWARE I NSTALLATION The 3095 Engineering Assistant (EA) for HART and 3095 Engineering Assistant (EA) for FOUNDATION Fieldbus software programs can be installed on the same computer. The applica...
Page 11 - Installing the HART Modem; Fieldbus
Quick Installation Guide 00825-0100-4716, Rev DAOctober 2009 Rosemount 3095 MultiVariable 11 S TEP 3 CONTINUED ... Installing the HART Modem After installing the 3095 Engineering Assistant, the HART modem configuration window automatically appears when the 3095 Engineering Assistant is opened. If th...
Page 12 - Use the following steps to wire the transmitter:; NOTE; conduit connections and the transmitter housing.
Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable 12 S TEP 4: C ONNECT W IRING AND P OWER U P (HART) S TEP 4: C ONNECT W IRING AND P OWER U P (HART) Use the following steps to wire the transmitter: 1. Remove the housing cover on the side marked FIELD TERMINAL...
Page 13 - Do not attach shield to ground.; Approval Option Code
Quick Installation Guide 00825-0100-4716, Rev DAOctober 2009 Rosemount 3095 MultiVariable 13 S TEP 4: C ONNECT W IRING AND P OWER U P (F IELDBUS ) Use the following steps to wire the transmitter: 1. Remove the housing cover labeled “Field Terminals.” Terminals are not polarity sensitive.2. Connect t...
Page 14 - Setting the Loop to Manual; Configure; Step through the Flow Configuration wizard.; Configuration Properties; Basic Setup; Basic Configuration Parameters; Fast Key Sequence
Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable 14 S TEP 5: C ONFIGURE THE T RANSMITTER (HART) Setting the Loop to Manual Set the process application loop to manual when preparing to send or request data that would disrupt the loop or change the output of t...
Page 16 - Send the Configuration to the Transmitter; To configure the AI Block; AI Block configuration parameters; Parameters
Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable 16 S TEP 5: C ONFIGURE THE T RANSMITTER (F IELDBUS ) Each F OUNDATION fieldbus host or configuration tool has a different way of displaying and performing configurations. Some use Device Descriptions (DD) or D...
Page 17 - Zero Trim; Using the Field Communicator; Follow the commands to perform a zero trim.; Using the Foundation Fieldbus AI Block; not; Fast Keys
Quick Installation Guide 00825-0100-4716, Rev DAOctober 2009 Rosemount 3095 MultiVariable 17 S TEP 6: T RIM THE T RANSMITTER NOTE Transmitters are shipped from Emerson Process Management fully calibrated and configured for the application when C2 Option is ordered. Without C2 Option, configuration w...
Page 18 - RODUCT; Approved Manufacturing Locations; Emerson Process Management complies with the ATEX Directive.; Rosemount 3095 HART Hazardous Locations Certifications; North American Certifications
Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable 18 P RODUCT C ERTIFICATIONS Rosemount 3095 with HART Approved Manufacturing Locations Rosemount Inc. — Chanhassen, Minnesota USAEmerson Process Management GmbH & Co. — Wessling, GermanyEmerson Process Mana...
Page 19 - European Certifications; II 1 G; Special Conditions for Safe Use
Quick Installation Guide 00825-0100-4716, Rev DAOctober 2009 Rosemount 3095 MultiVariable 19 Canadian Standards Association (CSA) C Explosion Proof for Class I, Division 1, Groups B, C, and D. Dust-Ignition Proof for Class II/Class III, Division 1, Groups E, F, and G. CSA enclosure Type 4X suitable ...
Page 20 - II 3 G; II 1 D
Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable 20 G ATEX Type n Certificate Number: BAS98ATEX3360X II 3 G Ex nL IIC T5 (T amb = –45 °C to 40 °C) Ex nL IIC T4 (T amb = –45 °C to 70 °C) U i = 55V The apparatus is designed for connection to a remote temperatu...
Page 21 - INMETRO Certifications; Group
Quick Installation Guide 00825-0100-4716, Rev DAOctober 2009 Rosemount 3095 MultiVariable 21 The capacitance and either the Inductance or the Inductance to Resistance Ratio (L/R) of the load connected to the 4-pin connector must not exceed the following values: NOTE 1. The external circuit contains ...
Page 22 - 095 Series transmitter with temperature sensor have; The temperature of process medium should be less than 121 °C.
Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable 22 China (NEPSI) Certifications 2 China Intrinsic SafetyEx ia IIC T4 Special conditions for safe use (x): 1. 3095 Series transmitter with temperature sensor have not been certified. 2. The temperature of proce...
Page 23 - medium is as following.; Maximum Temperature of
Quick Installation Guide 00825-0100-4716, Rev DAOctober 2009 Rosemount 3095 MultiVariable 23 11.When installation, use and maintenance transmitter, observe the following standards GB3836.13-1997 “Electrical apparatus for explosive gas atmospheres Part 13: Repair and overhaul for apparatus used in ex...
Page 24 - Combinations of Certifications; Rosemount 3095 with Fieldbus; Ordinary Location Certification for Factory Mutual
Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable 24 Combinations of Certifications Stainless steel certification tag is provided when optional approval is specified. Once a device labeled with multiple approval types is installed, it should not be reinstalle...
Page 25 - FM Approvals
Quick Installation Guide 00825-0100-4716, Rev DAOctober 2009 Rosemount 3095 MultiVariable 25 Rosemount 3095 Fieldbus Hazardous Locations Certifications North American Certifications FM Approvals A Explosion Proof for Class I, Division 1, Groups B, C, and D. Dust-Ignition Proof for Class II/Class III...
Page 27 - FISCO
Quick Installation Guide 00825-0100-4716, Rev DAOctober 2009 Rosemount 3095 MultiVariable 27 P ATEX DustCertificate Number: KEMA02ATEX2321 II 1 D T90°C (-50°C T amb 80°C) Vmax = 55 Vdc Imax = 23 mA IP66 1180 IECEx Certifications (Fieldbus) 4/Y IECEx Intrinsic SafetyCertificate Number: IECEx BAS0...
Page 28 - A and J combination
Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable 28 7 IECEx FlameproofCertificate Number: IECEx KEM 06.0018Zone 0/1 Ex d IIC T6 (-20°C T a 65°C) Zone 0/1 Ex d IIC T5 (-20°C T a 80°C) V max = 55 Vdc I max = 23 mAdc 8 IECEx DustCertificate Number: IECE...