Page 3 - Ethernet Communication Module DVPEN01-SL; DVP-PLC Operation Manual; Warning; on the device or injuries to staff.; Table of Contents
Ethernet Communication Module DVPEN01-SL DVP-PLC Operation Manual 1 Warning 3 Please read this instruction carefully before use and follow this instruction to operate the device in order to prevent damages on the device or injuries to staff. 3 Switch off the power before wiring. 3 RTU-DNET is an OPE...
Page 5 - Introduction
Ethernet Communication Module DVPEN01-SL DVP-PLC Operation Manual 3 1 Introduction Thank you for choosing DVPEN01-SL module. To correctly install and operate DVPEN01-SL, please read the manual carefully before using the module. DVPEN01-SL is an Ethernet communication module for remote setting and co...
Page 6 - Product Profile & Outline; Profiles
Ethernet Communication Module DVPEN01-SL DVP-PLC Operation Manual 4 Item Specification Storage: -25 ° C ~ 70 ° C (temperature), 5 ~ 95% (humidity) Vibration/ Shock Resistance Standard: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea) Electrical specifications Item Specificat...
Page 7 - Indicators; Installation & Wiring
Ethernet Communication Module DVPEN01-SL DVP-PLC Operation Manual 5 2.3 LED Indicators Indicator Color Indication POWER Green Power indication RS-232 Red Communication status of the series port 100M Orange Network connection status LINK Green Network communication speed 2.4 RJ-45 PIN Definition RJ-4...
Page 8 - Control
Ethernet Communication Module DVPEN01-SL DVP-PLC Operation Manual 6 Connect DVPEN01-SL to the Network: Connect DVPEN01-SL to the Ethernet Hub by twisted pair cable CAT-5e. DVPEN01-SL has Auto MDI/MDIX function; therefore, DVPEN01-SL does not need to use a crossing cable between the PC and DVPEN01-SL...
Page 10 - Explanations on CR
Ethernet Communication Module DVPEN01-SL DVP-PLC Operation Manual 8 CR# HW LW Attribute Content Explanation #115 R/W Modbus TCP trigger Setting up whether to send out data in Modbus TCP mode #116 R/W Modbus TCP status Displaying current status of Modbus TCP mode #118 #117 R/W Modbus TCP destination ...
Page 11 - Data Exchange
Ethernet Communication Module DVPEN01-SL DVP-PLC Operation Manual 9 C R # 7 ~ 8 : Status of E-Mail 1 ~ 4 Explanations: 1. CR#7_b0 ~ b7: current status of E-Mail 2; CR#7_b8 ~ b15: current status of E-Mail 1. 2. CR#8_b0 ~ b7: current status of E-Mail 4; CR#8_b8 ~ b15: current status of E-Mail 3. 3. Ta...
Page 13 - Sending Modbus TCP Instruction
Ethernet Communication Module DVPEN01-SL DVP-PLC Operation Manual 11 C R # 8 3 : Read Length for Data Exchange Explanations: Setting up the Modbus address of the register for Master data exchange. C R # 8 4 : Written-in Address for Data Exchange Explanations: Setting up manually the Modbus address o...
Page 15 - RTU Mapping
Ethernet Communication Module DVPEN01-SL DVP-PLC Operation Manual 13 C R # 2 5 1 : Error Code Explanations: Table of error code: Bit No. Error b0 The network is not yet connected. b1 Incorrect IP setting b2 CR#13 is set as “transmitting data”, but the data exchange is forbidden. b3 CR#13 is set as “...
Page 16 - Setting up Software; Setting up Communication & Searching for Modules; Communication settings; Open DCISoft in your PC and click on “Communication Setting”.
Ethernet Communication Module DVPEN01-SL DVP-PLC Operation Manual 14 5 Setting up Software This section gives instructions on how to set up DVPEN01-SL by DCISoft and explanations on each setup page. Before you start a setup page, you have to select “Ethernet” in the communication setting. Next, you ...
Page 17 - Broadcast search; displays the device list of all models.
Ethernet Communication Module DVPEN01-SL DVP-PLC Operation Manual 15 Broadcast search 1. Click broadcast icon in DCISoft to search for all Delta Ethernet products on the network. The window on the left hand side shows the models found, and the window on the right hand side displays the device list...
Page 18 - Designating model to search
Ethernet Communication Module DVPEN01-SL DVP-PLC Operation Manual 16 3. You will see the basic setup page as follow. Designating model to search 1. Right click “Ethernet” on the left hand side window and select “Configure” to designate a model to search for.
Page 20 - Searching by IP address; Click “IP Search” icon to start searching for the designated IP.
Ethernet Communication Module DVPEN01-SL DVP-PLC Operation Manual 18 Searching by IP address 1. Set the communication type to “Ethernet” and enter the IP address. Click “OK”. 2. Click “IP Search” icon to start searching for the designated IP. 3. The DVPEN01-SL module found will be displayed in the...
Page 22 - Settings; Setting up DVPEN01-SL basics; Module
Ethernet Communication Module DVPEN01-SL DVP-PLC Operation Manual 20 5.2 Basic Settings The basic settings include parameters as module name, language, enabling Modbus TCP and time correction. Setting up DVPEN01-SL basics 1. Module Name: There can be many DVPEN01-SL modules in the network. Thus, y...
Page 23 - Setting up static IP of the PC; Enter Control Panel
Ethernet Communication Module DVPEN01-SL DVP-PLC Operation Manual 21 7. Time Zone: A time zone is a region of the Earth that has adopted the same standard time, usually referred to as the local time. Most adjacent time zones are exactly one hour apart, and by convention compute their local time as a...
Page 25 - Setting up DVPEN01-SL Network
Ethernet Communication Module DVPEN01-SL DVP-PLC Operation Manual 23 Setting up DVPEN01-SL Network 1. IP configuration: There are two types of IP, static IP and DHCP. Static IP: Preset or manually modified by the user. DHCP: Automatically updated by the server. There has to be a server in the LAN....
Page 26 - Setting up DVPEN01-SL mail; continuous addresses of registers.
Ethernet Communication Module DVPEN01-SL DVP-PLC Operation Manual 24 5.4 Setting up E-Mails E-mail is the abbreviation of electronic mail, which transmits mails through the network. DVPEN01-SL has E-Mail functions for the user to pre-save a segment of text messages, which can be a descriptive messag...
Page 27 - Exchange; Setting up DVPEN01-SL data exchange
Ethernet Communication Module DVPEN01-SL DVP-PLC Operation Manual 25 E-Mail will be sent to the designated recipients when the E-Mail is triggered. To trigger E-Mail, set the value is CR#3 ~ CR#6 as “1”. 6. See “Application Examples Section 6.8” for more details. Notes: To correctly send out E-Mails...
Page 28 - The settings; enabled according to the settings.
Ethernet Communication Module DVPEN01-SL DVP-PLC Operation Manual 26 receiving register In data exchange, DVPEN01-SL will execute Write ( Æ ) first before Read ( Å ). Quantity: A slave is able to send and receive at the same time maximum 100 consecutive data. f For data exchange, D register is parte...
Page 29 - Filter; Setting up IP filter; Check the box to enable IP filter.; ARP
Ethernet Communication Module DVPEN01-SL DVP-PLC Operation Manual 27 of every slave: Digital I/O points (RX+RY): 256 Analog (Read) register: 64 Analog (Write) register: 64 5.7 IP Filter IP filter is used for restricting the connection of the network in case some uncertain IP will cause errors. Only ...
Page 30 - Setting up static ARP table; Destination IP address in data transmission.; Setting up Password; Setting up DVPEN01-SL password
Ethernet Communication Module DVPEN01-SL DVP-PLC Operation Manual 28 Therefore, if you do not know the MAC address, you will have to spend some time looking up the MAC address. If you want to enhance the transmission efficiency, use static ARP table to save time. For example, assume IP: 192.168.0.1 ...
Page 31 - Returning to Default Setting; DVPEN01-SL returning to default setting
Ethernet Communication Module DVPEN01-SL DVP-PLC Operation Manual 29 1. Modify: Check the box to modify the password. 2. New Password: Maximum 4 characters are allowed. Leave the column “blank” to disable the password protection function. 3. Confirm Password: Enter the new password again. 4. See “Ap...
Page 32 - Application; Setting up IP and Communicating through WPLSoft
Ethernet Communication Module DVPEN01-SL DVP-PLC Operation Manual 30 Check “Default Setting” box and click on “Yes”. Note: If you set up DVPEN01-SL by RS-232, you can return the setting to default setting whether the password is locked or not. It takes approximately 10 seconds to return to default s...
Page 35 - Connecting the PC with DVPEN01-SL through LAN; Application
Ethernet Communication Module DVPEN01-SL DVP-PLC Operation Manual 33 8. Enter IP address: 192.168.0.4; Netmask: 255.255.255.0; Gateway: 192.168.0.1. Press “OK” to complete the setup, and WPLSoft will automatically search for DVPEN01-SL. 9. The IP of DVPEN01-SL has been modified into the new setting ...
Page 36 - Open “Communication Setting” in WPLSoft.
Ethernet Communication Module DVPEN01-SL DVP-PLC Operation Manual 34 PC H ub D HC P Se r v er PC D VP- P LC D VPE N 01 2. Open “Communication Setting” in WPLSoft. 3. Select “Ethernet” and press “OK”.
Page 39 - Setting up Password and Clearing Password
Ethernet Communication Module DVPEN01-SL DVP-PLC Operation Manual 37 6.3 Setting up Password and Clearing Password Application Setting up and clearing password by WPLSoft Network requirement (1) Set password in DVPEN01-SL (2) Unlock DVPEN01-SL (3) Clear the password in DVPEN01-SL 1. See 6.1 for the ...
Page 42 - IP Filter Protection
Ethernet Communication Module DVPEN01-SL DVP-PLC Operation Manual 40 2. Check the “Default Setting” box and the “Warning” dialog box will appear. Click on “Yes” to return to default setting (in approx. 5 ~ 10 seconds), and the password will be cleared as well. 3. After the searching, all the paramet...
Page 44 - Setting up Static ARP Table
Ethernet Communication Module DVPEN01-SL DVP-PLC Operation Manual 42 6.6 Setting up Static ARP Table Application Setting up static ARP table Network requirement (1) MAC address of equipment 192.168.1.6 is 00:18:23:10:00:35 (2) MAC address of equipment 192.168.1.1 is 00:18:23:10:00:04 1. See 6.1 for ...
Page 53 - The data received every one second are written into D0 ~ D6.
Ethernet Communication Module DVPEN01-SL DVP-PLC Operation Manual 51 END M1013 K100 K1 K100 K100 K1 M2 M1 M1 SET M1 TOP K28 TOP TOP K100 TOP SET M2 M1 RST K100 K1 M2 K14 D14 RST M2 RST M2 = D14 K2 = D14 K3 FROM K1 K100 K1 TOP K100 TOP K1 K1 K0 K0 K26 K25 K29 K14 K13 D100 K7 H4 HC0A8 D100 T D R M1000...
Page 55 - Application of Modbus TCP Master
Ethernet Communication Module DVPEN01-SL DVP-PLC Operation Manual 53 • Write “0” into CR#28, and PLC_B will use CR#25 ~ CR#26 as the IP address of the destination PLC. • Write the IP address of PLC_A into CR#25 and CR#26. The first two IP codes (192.168 = H’C0A8) should be written into CR#26, and th...