Page 4 - Preface; Getting Started; WARNING; The rated voltage for the AC motor drive must be
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED Preface Thank you for choosing DELTA’s high-performance VFD-F Series. VFD-F Series are manufactured by adopting high-quality components, material and incorporating the latest microprocessor technology available. Getting Started This manual wil...
Page 5 - TABLE OF CONTENTS; CHAPTER 1 RECEIVING AND INSPECTIONS
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED TABLE OF CONTENTS CHAPTER 1 RECEIVING AND INSPECTIONS 1.1 Nameplate Information ........................................................................ 1 - 1 1.2 Model Explanation .................................................................
Page 6 - CHAPTER 5 DESCRIPTION OF PARAMETER SETTINGS
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 4.2 KPF-CC01 ........................................................................................... 4 - 5 4.2.1 Description of the Digital Keypad KPF-CC01 ............................... 4 - 5 4.2.2 Explanation of Display Message............
Page 7 - CHAPTER 8 SUMMARY OF PARAMETER SETTINGS
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED CHAPTER 8 SUMMARY OF PARAMETER SETTINGS ............................ 8 - 1 APPENDIX A SPECIFICATIONS ................................................................ A - 1 APPENDIX B ACCESSORIES B.1 All Brake Resistors & Brake Units Used i...
Page 8 - CHAPTER 1 RECEIVING AND INSPECTION; Receiving
1 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 1-1 CHAPTER 1 RECEIVING AND INSPECTION This VFD-F AC drive has gone through rigorous quality control tests at the factory before shipment. After receiving the AC drive, please check for the following: Receiving 9 Check to make sure that the ...
Page 9 - Series Number Explanation; P r od uc t i on n um be r; P ro duc tion m od el
1 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 1-2 1.3 Series Number Explanation P r od uc t i on n um be r 3 055F43A P ro duc tion m od el 46 0V 3 -P HA SE 7. 5H P ( 5. 5k W ) If there is any nameplate information not corresponding to your purchase order or any problem, please contact y...
Page 10 - CHAPTER 2 STORAGE AND INSTALLATION; Operation
2 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 2-1 CHAPTER 2 STORAGE AND INSTALLATION 2.1 Storage The AC drive should be kept in the shipping carton before installation. In order to retain the warranty coverage, the AC drive should be stored properly when it is not to be used for an exte...
Page 11 - Installation; CAUTION
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 2-2 2.2 Installation CAUTION The control, power supply and motor leads must be laid separately. They must not be fed through the same cable conduit / trunking. High voltage insulation test equipment must not be used on cables connected to the ...
Page 12 - CHAPTER 3 WIRING; DANGER; Hazardous Voltage; Before accessing the AC drive:; Short Circuit Withstand:
3 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-1 CHAPTER 3 WIRING DANGER Hazardous Voltage Before accessing the AC drive: Disconnect all power to the AC drive. Wait five minutes for DC bus capacitors discharge. Any electrical or mechanical modification to this equipment without pri...
Page 13 - Basic Wiring Diagram
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-2 3.1 Basic Wiring Diagram Users must connect wires according to the following circuit diagram shown below. Do not plug a Modem or telephone line to the RS-485 communication port, permanent damage may result. Pins 1 & 2 are the power sou...
Page 15 - Wiring for SINK mode and SOURCE mode
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-4 Wiring for SINK mode and SOURCE mode JOG 1/2 Accel/Decel switch MI7MI8 Sw1 Si nk So urce JOG 1/2 Accel/Decel switch MI7MI8
Page 16 - Items Explanations
3 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-5 3.2 External Wiring R / L 1 S /L 2 T / L 3 U / T1 V/T 2 W /T 3 B 2 - + / B 1 E E BR VF DB BR E M I F i lt e r P o w e r S u p p l y F US E / NF B M a g n e ti c C o n t a c to r In p u t A C L i n e R e a c t o r Z e ro - p h a s e R e a...
Page 17 - Main Circuit Connection; Terminal Explanations
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-6 3.3 Main Circuit Connection Figure 1 for the main circuit terminals R (L 1 ) S ( L 2 )T (L 3 ) R ST U (T 1 )V ( T 2 ) W ( T3 ) I M3 ~ M C E E +1 +2/B1 B2 - Brake Resis tor (Optional ) Motor Non- fuse br eaker (NFB) Figure 2 for the main ci...
Page 18 - which is made by the loose screws due to vibration.
3 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-7 Mains power terminals (R/L1, S/L2, T/L3) Connect these terminals (R/L1, S/L2, T/L3) via a non-fuse breaker or earth leakage breaker to 3-phase AC power (some models to 1-phase AC power) for circuit protection. It is unnecessary to cons...
Page 19 - external optional brake unit and brake resistor.
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-8 Terminals [+2/B1, B2] for connecting brake resistor and terminals [+2/B1, -] for connecting external brake unit B r ak e u n it (o p t io n al ) R e fe r t o Ap p e nd ix B f o r t h e u s e o fsp e cia l b ra ke re sis to r /u n it + 2/ B...
Page 20 - Control Terminals
3 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-9 3.4 Control Terminals + 2 4 V D CM SI N K / NP N M o d e M u l ti -f u n c t io nIn p u t Te rm i n a l I n t e rn a l C i r cu i t + 2 4 V D CM S O U R CE / PN P M o d e M u l t i -f u n c t io n In p u t Te rm i n a l I n t e r n a l C...
Page 21 - wind each wire 3 times or more around the core
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-10 Terminal Symbols Terminal Functions Factory Settings +10V Potentiometer power source +10V 20mA AVI Analog voltage Input 0 to +10V correspond to Max. operation frequency ACI 1/2 Analog current Input 4 to 20mA correspond to Max. operation f...
Page 22 - Specifications for Power Terminals and Control Terminals; ), it is thus necessary to use the Recognized
3 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-11 3.5 Specifications for Power Terminals and Control Terminals Frame B +1 +2 B 1 - B 2 R/L1 S/L2 T/L3 Screw Torque : Wire Gauge : 18Kgf-cm 18~10AWG U/T1 V/T2 W/T3 Power Terminals: R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, , +1, +2/B1, -, B2 Mod...
Page 25 - PLEASE READ PRIOR TO INSTALLATION.; will damage the AC drive.; Ensure there are no ground loops.; F orw ar d; required current to the AC drive.
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-14 3.6 Wiring Notes: PLEASE READ PRIOR TO INSTALLATION. 1. ! CAUTION: Do not connect the AC power to the U/T1, V/T2, W/T3 terminals, as it will damage the AC drive. 2. ! WARNING: Ensure all screws are tightened to the proper torque rating. 3...
Page 26 - Note: This drive is not intended for the use; Route the power and control wires separately, or at 90
3 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-15 13. For the single-phase rated AC drives, the AC power can be connected to any two of the three input terminals R/L1, S/L2, T/L3. Note: This drive is not intended for the use with single-phase motors. 14. Route the power and control wir...
Page 27 - Motor Operation Precautions; energy loss is greater than for an inverter duty motor.
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-16 3.7 Motor Operation Precautions 1. When using the AC drive to operate a standard 3-phase induction motor, notice that the energy loss is greater than for an inverter duty motor. 2. Avoid running a standard induction motor at low speed. Un...
Page 28 - CHAPTER 4 DIGITAL KEYPAD OPERATION; Description of the Keypad
4 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 4-1 CHAPTER 4 DIGITAL KEYPAD OPERATION This chapter describes the various controls and indicators found on the digital keypad. The information in this chapter should be read and understood before performing the start–up procedures described ...
Page 29 - Description of the Digital Keypad VFD-PU01; RUN; RESET; Display Message; Display the AC drive Master Frequency.
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 4-2 4.1 VFD-PU01 4.1.1 Description of the Digital Keypad VFD-PU01 U F H VFD-PU01 JOG LED Displa y Display frequency, current , voltage and error, etc. Sta tus Displa y Display the driver's current status Pa rt Nu mber Left ke y moves cursor t ...
Page 31 - To sh ift d at a
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 4-4 4.1.3 Operation steps of the Digital Keypad VFD-PU01 M ODE M OD E M ODE M ODE M ODE M ODE START U F H Select ing mode START To sh ift d at a To modify data Setti ng dir ecti on o r Sett i ng p ar am ete rs U F H U F H U F H GO STA RT U F H...
Page 32 - N OT E; The AC motor drive Master Frequency Command.
4 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 4-5 4.2 KPF-CC01 For models of VFD-F (HVAC) series VFD007F43H; VFD015F43H; VFD022F43H; VFD037F43H; VFD055F43H; VFD075F43H; VFD110F43H; VFD150F43H; VFD185F43H; VFD220F43H; VFD300F43H; VFD370F43H; VFD450F43H; VFD550F43H; VFD750F43H; VFD900F43H...
Page 33 - The specified group description.
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 4-6 Display Message Description The output current present at terminals U, V, W. The specified group description. The specified parameter description and setting Copy Mode: Press MODE key for about 2~3 seconds in main page. Use UP/DOWN key to ...
Page 34 - CHAPTER 5 DESCRIPTION OF PARAMETER SETTINGS; Group 0: AC Drive Status Parameters
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-1 CHAPTER 5 DESCRIPTION OF PARAMETER SETTINGS a : This parameter can be set during operation. 5.1 Group 0: AC Drive Status Parameters Group 0 is read-only. 00 - 00 Software Version Factory setting: Read Only This parameter displays the sof...
Page 41 - Accel/Decel time unit
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-8 01-23 Accel/Decel time unit Accel/Decel time range 00 1 Sec 1~36000 Sec 01 0.1 Sec 0.1~3600.0 Sec 02 0.01 Sec 0.01~360.00 Sec
Page 42 - Group 2: Operation Method Parameters
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-9 5.3 Group 2: Operation Method Parameters 02 - 00 Source of Frequency Command a Factory Setting: 00 Settings 00: via keypad 01: via analog input AVI 02: via analog input ACI1 03: via analog input ACI2 04: via RS485 serial communication 05...
Page 44 - W D
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-11 The Carrier frequency of the PWM output has a signification influence on the electromagnetic noise, heat dissipation of the AC drive, and the acoustic noise to the motor as shown in the following chart. Carrier frequency Acoustic Noise ...
Page 47 - This feature is only enabled when Pr. 02-00 is set for 0 or 4.
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-14 If this parameter is set to 00: The AC drive will not store the last known master frequency command, after power is removed. If this parameter is set to 01: The AC drive will memorize the last known master frequency command after power of...
Page 48 - Setting Functions
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-15 5.4 Group 3: Output Function Parameters 03 - 00 Multi-function Output terminal 1 Factory Setting: 00 03 - 01 Multi-function Output terminal 2 Factory Setting: 00 03 - 02 Multi-function Output terminal 3 Factory Setting: 00 03 - 03 Multi...
Page 58 - Execute one cycle of the PLC program. Its relative parameter; step speed (sets the frequency of each step speed); Operation time setting of the 1; program off and on again.
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-25 Example 1 (Pr.05-15 = 1): Execute one cycle of the PLC program. Its relative parameter settings are: Pr.05-00 to 05-14: 1 st to 15 th step speed (sets the frequency of each step speed) Pr.04-00 to 04-07: Multi-Function Input Terminals (...
Page 59 - PLC Forward/Reverse Motion
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-26 Example 3 (Pr.05-15 = 3) Execute one cycle step by step: The example below shows how the PLC can perform one cycle at a time, within in a complete cycle. Each step will use the accel/decel times in Pr.01-09 to Pr.01-16. It should be notic...
Page 62 - Time Unit Settings
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-29 05-05 Frequency Mast er Speed 05-00 05-01 05-02 05-03 05-04 05-06 05-07 05-08 05-09 05-10 05-11 05-12 05-13 05-14 01-19 JOG Freq. 2 3 4 5 6 7 8 9 10 11 12 131415 O F F O F F O F F O F F OFF O N O N ON O N O N O N O N O N O N O N O N O N...
Page 63 - Group 6: Protection Function Parameters
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-30 5.7 Group 6: Protection Function Parameters 06 - 00 Over-voltage Stall Prevention Factory Setting: 390.0/780.0 Settings 230V series: 330.0 ~ 410.0VDC 460V series: 660.0 ~820.0VDC 00: Disable This parameter selects the voltage level for th...
Page 68 - Parameter Protection Password Setting
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-35 This parameter allows the user to enter their password to unlock the Parameter Protection feature. The password entered must match the value entered into Pr.6-17. After three invalid password attempts, the drive will no longer allow any...
Page 69 - Group 7: AC Drive and Motor Parameters
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-36 5.8 Group 7: AC Drive and Motor Parameters 07 - 00 Identity Code of AC Drive Factory Setting: ## Settings Display by model type This parameter displays the AC drive model code. This parameter is read-only. 07 - 01 Rated Current of AC Driv...
Page 73 - DC Br ak i ng Tim e; Momentary Power Loss Operation Selection
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-40 Outp ut freq uen cy Time DC Br ak i ng Tim e O N O FF Run/Stop DC brak ingc urren tle ve l DC b rak ingtime durings topp in g Mini mum ou tpu tfreq ue nc y Stop p oin t f orDC brak ing time du rings topping 01 -05 08 -03 08 - 04 Momentary...
Page 78 - Communication Parameters
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-45 5.10 Group 9: Communication Parameters 09 - 00 Communication Address a Factory Setting: 01 Settings 01-254 00: Disable If the AC drive is controlled by RS-485 serial communication, the communication address for this drive must be set vi...
Page 80 - ASCII
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-47 If you set BB action by this parameter and you also need to disable BB action by this parameter. There is a built-in RS-485 serial interface, marked (RJ-11 jack) on the control terminal block. The pins are defined below: 6 1 1: EV2: GND...
Page 81 - Ev e n
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-48 (7 , E , 1 : 9-04=0, 9-05=04) 0 1 2 3 4 5 6 St ar t bit Ev e n p ar i ty St op bit 7-bit cha ract er 1 0-bit c har acter fr ame (7 , O , 1 : 9-04=0, 9-05=05) 0 1 2 3 4 5 6 St ar t bit O dd p ar i ty St op bit 7-bit cha ract er 10- bit...
Page 92 - The explanation of exception codes:; Exception
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-59 The explanation of exception codes: Exception code Explanation 01 Illegal function code: The function code received in the command message is not available for the AC motor drive. 02 Illegal data address: The data address received in th...
Page 96 - Group 11: Fan and Pump Control Parameters; V / F C u rv e D i ag ra m
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-63 5.12 Group 11: Fan and Pump Control Parameters 11 - 00 V/f Curve Selection Factory Setting: 00 Settings 00: Determined by group 1 01: 1.5 power curve 02: 1.7 power curve 03: 2 power curve 04: cube curve This parameter is to set V/f curv...
Page 98 - VFD-F is able to drive 4 motors under PID control mode by turns.
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-65 When Pr. 11-01 is set to 02 “Fixed Amount Circulation” and adding relay card “RY-00”, VFD-F is able to drive 4 motors under PID control mode by turns. System powers up, VFD-F drives 1st motor as PID control mode. If VFD-F output frequen...
Page 99 - Previous routine repeats to 3rd motor; automatically set the corresponding output motor.
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-66 When Pr. 11-01 is set to 03 “Fixed Amount Control” and adding relay card “RY-00”, VFD-F is able to drive 1 motor under PID control mode and another 4 motors as full power running. System powers up, VFD-F drives 1st motor as PID control mo...
Page 100 - Multiple Motors Control; Time Circulation Time Setting
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-67 11 - 02 Multiple Motors Control Factory Setting: 01 Settings 01~04 When this parameter is set to multiple motors control, multi-function terminals 03-00 to 03-07 will automatically set to suitable value. Users need to connect output ter...
Page 101 - Motor Switch Delay Time
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-68 If multi-function input terminals (04-00 to 04-07) are set to 27 to 31, the corresponding output terminals will skip and not activate. The following diagram is the action schedule of time circulation when motor 3 is disabled. The motor, w...
Page 102 - Commer cial power; Settings
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-69 After power supply of motor is not from AC drive, the motor will coast to stop according to loading characteristics. Users need to set 11-06 motor switch frequency and 11-04 delay time of circulation control according to actual situatio...
Page 106 - CHAPTER 6 MAINTENANCE AND INSPECTIONS; Wait at least 10 minutes; Periodic Inspection; Disconnecting AC power before processing!
6 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 6-1 CHAPTER 6 MAINTENANCE AND INSPECTIONS Modern AC drives are based on solid state electronics technology, preventive maintenance is required to operate this AC drive in its optimal condition, and to ensure a long life. It is recommended to...
Page 107 - This page intentionally left blank.
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED This page intentionally left blank.
Page 108 - CHAPTER 7 Troubleshooting and Fault Information; Common Problems and Solutions:
7 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 7-1 CHAPTER 7 Troubleshooting and Fault Information The AC drive has a comprehensive fault diagnostic system that includes several different alarms and fault messages. Once a fault is detected, the corresponding protective functions will be ...
Page 109 - Fault
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 7-2 Fault Name Fault Descriptions Corrective Actions The AC drive temperature sensor detects excessive heat. 1. Ensure that the ambient temperature falls within the specified temperature range. 2. Make sure that the ventilation holes are not o...
Page 113 - Return to the factory.
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 7-6 Fault Name Fault Descriptions Corrective Actions Fan 1, 2, 3 fault (150~300HP) Remove any foreign objects on the heatsinks and check for possible dirty heat sink fins. Fan 1, 2 fault (150~300HP) Remove any foreign objects on the heatsinks ...
Page 114 - CHAPTER 8 PARAMETER SUMMARY; Group 0 AC Drive Status Parameter; Read only
8 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-1 CHAPTER 8 PARAMETER SUMMARY Group 0 AC Drive Status Parameter Parameters Functions Settings Factory Setting Customer 00-00 Software Version Read only 00-01 AC Drive Status Indication 1 00: No Fault occurred 01: oc (over current) 02: ov (...
Page 116 - Group 1 Basic Parameter (Twice the value for 460V class)
8 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-3 Group 1 Basic Parameter (Twice the value for 460V class) Parameters Functions Settings Factory Setting Customer 01-00 Maximum Output Frequency 50.00~120.00Hz 60.00 01-01 Maximum Voltage Frequency (Base Frequency) 0.10~120.00 Hz 60.00 01-...
Page 117 - Group 2 Digital Output/Input Parameter
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-4 Group 2 Digital Output/Input Parameter Parameters Functions Settings Factory Setting Customer a 02-00 Source of Frequency Command 00: via keypad 01: via analog input AVI 02: via analog input ACI1 03: via analog input ACI2 04: via RS485 ser...
Page 119 - Group 3 Output Function Parameters
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-6 Group 3 Output Function Parameters Parameters Functions Settings Factory Setting Customer 03-00 Multi-function Output terminal 1 00 03-01 Multi-function Output terminal 2 00 03-02 Multi-function Output terminal 3 00 03-03 Multi-function Ou...
Page 121 - Group 4 Input Function Parameters
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-8 Group 4 Input Function Parameters Parameters Functions Settings Factory Setting Customer 04-00 Multi-function Input terminal 1 01 04-01 Multi-function Input terminal 2 02 04-02 Multi-function Input terminal 3 03 04-03 Multi-function Input ...
Page 123 - Group 5 Multi-step Speed Frequency Parameters
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-10 Group 5 Multi-step Speed Frequency Parameters Parameters Functions Settings Factory Setting Customer a 05-00 1 st Step Speed Frequency 0.00~120.00 Hz 0.00 a 05-01 2 nd Step Speed Frequency 0.00~120.00 Hz 0.00 a 05-02 3 rd Step Speed Frequ...
Page 124 - Time Duration Step 12
8 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-11 Parameters Functions Settings Factory Setting Customer 05-28 Time Duration Step 12 0.0 to 65500 Sec 0.0 05-29 Time Duration Step 13 0.0 to 65500 Sec 0.0 05-30 Time Duration Step 14 0.0 to 65500 Sec 0.0 05-31 Time Duration Step 15 0.0 to...
Page 127 - Group 7 AC Drive and Motor Parameters
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-14 Group 7 AC Drive and Motor Parameters Parameters Functions Settings Factory Setting Customer 07-00 Identity Code of AC Drive Display by model type ## 07-01 Rated Current of AC Drive Display by model type ## a 07-02 Full-load Current of Mo...
Page 128 - Group 8 Special Parameters (Twice the value for 460V class)
8 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-15 Group 8 Special Parameters (Twice the value for 460V class) Parameters Functions Settings Factory Setting Customer 08-00 DC Brake Current Level 00~100% 00 08-01 DC Brake Time during Start-up 0.0~60.0 Sec 0.0 08-02 DC Brake Time during S...
Page 129 - Group 9 Communication Parameters
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-16 Group 9 Communication Parameters Parameters Functions Settings Factory Setting Customer a 09-00 Communication Address 01-254 00:Disable 01 a 09-01 Transmission Speed (Baud Rate) 00: Baud rate 4800 01: Baud rate 9600 02: Baud rate 19200 03...
Page 131 - Group 10 PID Controls
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-18 Group 10 PID Controls Parameters Functions Settings Factory Setting Customer 10-00 Input Terminal for PID Feedback 00: No function 01: Input via AVI 02: Input via ACI1 03: Input via ACI2 04: Input via External Reference 00 10-01 PID Contr...
Page 132 - Group 11 Fan and Pump Control Parameters
8 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-19 Group 11 Fan and Pump Control Parameters Parameters Functions Settings Factory Setting Customer 11-00 V/F Curve Selection 00: Determined by group 01 01: 1.5 power curve 02: 1.7 power curve 03: 2 power curve 04: 3 power curve 00 11-01 Ci...
Page 134 - Specifications; General Specifications
A VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED A-1 Specifications Voltage Class 230V Class Model Number VFD-_ _ _F23_ 007 015 022 037 055 075 110 150 185 220 300 370 Max. Applicable Motor Output (kW) 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 Max. Applicable Motor Output (HP) 1.0 2.0 3...
Page 136 - ACCESSORIES; B.1 All Brake Resistors & Brake Units Used in AC Motor Drives
B VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-1 ACCESSORIES B.1 All Brake Resistors & Brake Units Used in AC Motor Drives Note: Please only use DELTA resistors and recommended values. Other resistors and values will void Delta’s warranty. Please contact your nearest Delta represen...
Page 137 - NOT E
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-2 NOT E 1. Please select the brake unit and/or brake resistor according to the table. “-“ means no Delta product. Please use the brake unit according to the Equivalent Resistor Value. 2. If damage to the drive or other equipment is due to th...
Page 138 - B.1.1 Dimensions and Weights for Brake Resistors; TYPE L1
B VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-3 B.1.1 Dimensions and Weights for Brake Resistors (Dimensions are in millimeter) Order P/N: BR080W200, BR080W750, BR300W070, BR300W100, BR300W250, BR300W400, BR400W150, BR400W040 TYPE L1 L2 H D W MAX. WEIGHT(g) BR080W200 140 125 20 5.3 60...
Page 143 - AC Drives; General precaution
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-8 B.2 AMD-EMI Filter Cross Reference AC Drives EMI Model Number VFD007F23A/H, VFD015F23A/H, VFD022F23A/H, VFD037F23A/H 26TDT1W4C VFD110F23A/H, VFD055F23A/H, VFD075F23A/H, VFD185F43A/H 50TDS4W4C VFD150F23A/H, VFD220F43A/H, VFD300F43A/H, VFD37...
Page 144 - Saddle on both ends
B VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-9 Remove any pa in t on metal saddle for go od gr ound co ntac t wi th the plate and shielding. sadd le the plate with gr ounding Saddle on both ends Saddle on one end
Page 145 - AC Input Reactor Recommended Value
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-10 B.3 AC Reactor AC Input Reactor Recommended Value 460V, 50/60Hz, 3-Phase Inductance (mh) KW HP Fundamental Amps Max. Continuous Amps 3% impedance 5% impedance 0.75 1 4 6 9 12 1.5 2 4 6 6.5 9 2.2 3 8 12 5 7.5 3.7 5 8 12 3 5 5.5 7.5 12 18 2...
Page 146 - AC Output Reactor Recommended Value
B VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-11 AC Output Reactor Recommended Value 230V, 50/60Hz, 3-Phase Inductance (mH) kW HP Fundamental Amps Max. continuous Amps 3% impedance 5% impedance 0.75 1 8 12 3 5 1.5 2 8 12 1.5 3 2.2 3 12 18 1.25 2.5 3.7 5 18 27 0.8 1.5 5.5 7.5 25 37.5 0...
Page 147 - Model Recommended
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-12 B.4 Non-fuse Circuit Breaker Chart The fuse should comply with UL248 and the breaker should comply with UL489. The current rating of the breaker shall be within 2~4 times maximum input current rating. 3-phase Model Recommended non-fuse br...
Page 148 - B.5 Fuse Specification Chart; Smaller fuses than those shown in the table are permitted.
B VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-13 B.5 Fuse Specification Chart Smaller fuses than those shown in the table are permitted. Line Fuse Model I (A) Input I (A) Output I (A) Bussmann P/N VFD007F23A 5.7 5.0 10 JJN-10 VFD007F43A/H 3.2 2.7 5 JJS-6 VFD015F23A 7.6 7.0 15 JJN-15 V...
Page 149 - P U
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-14 B.6 PU06 B.6.1 Description of the Digital Keypad VFD-PU06 U FH VFD-PU06 JOG RUN RESET STOP L ED Di sp l a y Indi cates f requency, volt age, current , user defi ned unit s, read, and save, et c. Sta tu s Disp la y Di spl ay the dri v er's...
Page 150 - XXXXX; VFD-P U06 Operati on Flow Chart
B VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-15 Display Message Descriptions The specified parameter setting. The actual value stored in the specified parameter. External Fault “End” displays for approximately 1 second if the entered input data have been accepted. After a parameter v...
Page 152 - INSULATOR
B VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-17 PCB-SUPPORT PCB-SUPPORT CONTROL-BOARD PCB-SUPPORT INSULATOR RELAY-CARD SCREW M3*P0.5TORQUE=2~4Kgf-cm PCB-SUPPORT SCREW M3*P0.5TORQUE=2~4Kgf-cm CONTROL-BOARD RELAY-CARD INSULATOR
Page 153 - Note; The table above gives approximate
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-18 B.8 Zero Phase Reactor (RF220X00A) Dimensions are in millimeter and (inch) Recommended Wire Size (mm 2 ) Cable type ( Note ) AWG mm 2 Nominal (mm 2 ) Qty. Wiring Method ≦ 10 ≦ 5.3 ≦ 5.5 1 Diagram A Single- core ≦ 2 ≦ 33.6 ≦ 38 4 Diagram B...
Page 154 - DIMENSIONS; Frame B
C VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-1 DIMENSIONS Frame B H W1 D H1 W D1 S2 S1 UNIT: mm [inch] Frame W W1 H H1 D D1 S1 S2 B1 150.0 [5.91] 135.0 [5.32] 260.0 [10.24] 244.3 [9.63] 160.2 [6.31] 4.0 [0.16] 8.0 [0.32] 6.5 [0.26] N OT E Frame B(B1): VFD007F23A; VFD007F43A; VFD007F4...
Page 155 - Frame C
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-2 Frame C W1 W H1 H S2 D D2 D1 S1 UNIT: mm [inch] Frame W W1 H H1 D D1 D2 S1 S2 C1 200.0 [7.88] 185.6 [7.31] 323.0 [12.72] 303.0 [11.96] 183.2 [7.22] 76.5 [3.01] 3.0 [0.12] 7.0 [0.28] 7.0 [0.28] N OT E Frame C(C1): VFD055F23A; VFD055F43B; VF...
Page 156 - Frame D
C VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-3 Frame D W W1 H H1 D S1 D2 D1 UNIT: mm [inch] Frame W W1 H H1 D D1 D2 S1 D1 250.0 [9.84] 226.0 [8.90] 403.8 [15.90] 384.0 [15.12] 205.4 [8.08] 110.0 [4.33] 8.0 [0.31] 10.0 [0.39] N OT E Frame D(D1): VFD150F23A; VFD185F23A; VFD185F43A; VFD...
Page 157 - Frame E
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-4 Frame E W1 W H1 H2 H D S2 D1 S1 D2 S3 UNIT: mm [inch] Frame W W1 H H1 H2 D D1 D2 S1 S2 S3 E1 370.0 [14.57] 335.0 [13.19] - 589.0 [23.19] 560.0 [22.05] 260.0 [10.24] 132.5 [5.22] 18.0 [0.71] 13.0 [0.51] 13.0 [0.51] 18.0 [0.71] E2 370.0 [14....
Page 158 - Frame G; Frame
C VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-5 Frame G W1 W H1 H D1 H2 D2 S2 H JOG U RUN MODE PROG RESET STOP DATA JOG RUN STOP RE V VFD-PU01 FWD F S1 D S3 S4 UNIT: mm [inch] Frame W W1 H H1 H2 D D1 D2 S1 S2 S3 S4 G1 425.0 [16.73] 381.0 [15.00] 850.0 [33.46] 819.5 [32.26] 746.0 [30.0...
Page 159 - Frame H
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-6 Frame H W1 W H1 H D1 H2 D2 S2 H JOG U RUN MODE PROG RESET STOP DATA JOG RUN STOP RE V VFD-PU01 FWD F S1 D S3 S4 UNIT: mm [inch] Frame W W1 H H1 H2 H3 D D1 S1 S2 S3 H1 547.0 [21.54] 480.0 [18.90] 1357.6 [53.45] 1150.0 [45.28] 1119.0 [44.06]...
Page 160 - STOP
C VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-7 VFD-PU01 Unit: mm (inches) 6. 5 [0 .2 6] 19.0 [0.75] 11 0. 0 [4 .3 3] 73.0 [2.87] 97 .0 [3 .8 2] 44.0 [1.73] 77 .0 [ 3. 0 3] M4* 0.7(2X) DATA PROG STOP MODE RUN JOG ? 40 .0[ 1.5 8]