Daikin WGZ030DW- Manuals
Daikin WGZ030DW– User Manual in PDF format online.
Manuals:
User Manual Daikin WGZ030DW
Summary
2 OMM 1130 - 2 Table of Contents Introduction ....................................... 3 General Description .............................. 3 Nomenclature ........................................ 3 Water Pressure Drop ............................. 3 Components ...........................................
OMM 1130 - 2 3 Introduction General Description Daikin Type WGZ water chillers are designed for indoor installations Equipment room temperature for operating and standby conditions is 40°F to 122°F (4.4°C to 50°C). They are available with water-cooled condensers (Model DW), or arranged for use with ...
4 WGZ030D through WGZ200D OMM 1130 - 2 Figure 1, Evaporator Pressure Drop, WGZ030D – WGZ200D GPM Ft L/S kPa GPM Ft L/S kPa GPM Ft L/S kPa W GZ030D A 56.3 2.6 3.5 7.7 90.0 6.3 5.6 18.8 150.0 16.6 9.4 49.7 W GZ035D B 64.9 3.6 4.1 10.8 103.8 8.8 6.5 26.3 173.0 23.2 10.8 69.4 W GZ040D C 76.3 2.9 4.8 8.6...
OMM 1130 - 2 5 Figure 2, Condenser Pressure Drop, WGZ030D – WGZ200D Unit Model Ref # Min. Flow & PD Nom. Flow & PD Max. Flow & PD IP SI IP SI IP SI GPM Ft. L/S kPa GPM Ft. L/S kPa GPM Ft. L/S kPa WGZ030D A 56.1 2.4 3.5 7.2 89.7 6.3 5.7 18.8 149.5 17.4 9.4 52.0 WGZ035D B 64.9 3.4 4.1 10.2...
6 WGZ030D through WGZ200D OMM 1130 - 2 Components Figure 3, Compressor Locations NOTE: Models WGZ150 to WGZ200 add a #5 compressor to circuit #1 and a #6 compressor to circuit #2. 4 2 3 1 Circuit 2 Circuit 1 Control Panel Evaporator Evaporator andCondenserConnections
OMM 1130 - 2 7 Unit Configuration The chiller units have two refrigerant circuits, Models WGZ 030 to WGZ 130 have two tandem scroll compressors (total of four), a single two-circuited brazed plate evaporator, a single two-circuited water-cooled condenser, interconnecting refrigerant piping and a con...
8 WGZ030D through WGZ200D OMM 1130 - 2 Field Wiring Diagrams Figure 5, WGZ030DW – WGZ200DW Field Wiring Diagram (Packaged Unit)
10 WGZ030D through WGZ200D OMM 1130 - 2 Control Panel Layout Table 1, Typical Control Panel, 4-Compressor Unit NOTES: 1. Additional space provided in the upper right section for optional multiple point power connection and optional circuit breakers. 2. Front door has a slot opening at the top for ac...
OMM 1130 - 2 11 Start-Up and Shutdown Pre Start-up 1. The chilled-water system should be flushed and cleaned. Proper water treatment is required to prevent corrosion and organic growth. 2. With main disconnect open, check all electrical connections in control panel and starter to be sure they are ti...
12 WGZ030D through WGZ200D OMM 1130 - 2 12. Start the system by setting the system switch S1 to on. 13. After running the unit for a short time, check the oil level in each compressor crankcase, rotation of condenser fans (if any), and check for flashing in the refrigerant sight glass. 14. After sys...
OMM 1130 - 2 13 11. Check that the MicroTech II controller is set to the desired chilled water temperature. 12. Check resets of all equipment protection controls. 13. Switch the unit circuit breakers to “on.” 14. Start the system by setting the system switch S1 to “on.” CAUTION Most relays and termi...
OMM 1130 - 2 15 When staging down, one compressor on each circuit will be left on until each circuit has only one compressor running. In other words, the compressor, on either circuit, with the most run-hours will stop first. The compressor with the most run-hours on the other circuit will stop next...
OMM 1130 - 2 17 MicroTech II Controller Controller Software Version This manual is based on software version WGZD20102F. The “02F” is the version descriptor. The version installed in a unit can be viewed by pressing the MENU and ENTER keys simultaneously, then pressing MENU to return to the regular ...
18 WGZ030D through WGZ200D OMM 1130 - 2 Keypad/Display A 4-line by 20-character/line liquid crystal display and 6-key keypad is mounted on the unit controller. Its layout is shown below. Figure 8, Keypad and Display in MENU Mode The four arrow keys (UP, DOWN, LEFT, RIGHT) have three modes of use. Sc...
OMM 1130 - 2 19 Table 4, Analog Outputs # Description Output Signal Range 1 Cooling Tower Bypass Valve Position 0 to 10 VDC 0 to 100% Open 2 Cooling Tower VFD Speed 0 to 10 VDC 0 to 100% 3 Circuit #1 Electronic Expansion Valve 0 to 10 VDC 0 to 100% 4 Circuit #2 Electronic Expansion Valve 0 to 10 VDC...
20 WGZ030D through WGZ200D OMM 1130 - 2 Table 6, Continued # Description Type Load Output OFF Output ON 5 Motor Control Relay #3 = Compr#3 C1 Starter Compressor OFF Compressor ON *6 Condenser Fan #3– Water Cooled =N /Tower Fan #2-Water Cooled=Y C1 / UT Fan Contactor Fan OFF Fan ON *6 Motor Control R...
OMM 1130 - 2 21 Setpoints The following parameters are remembered during power off, are factory set to the Default value, and can be adjusted to any value in the Range column. The PW (password) column indicates the password level that must be active in order to change the setpoint. Passwords are as ...
OMM 1130 - 2 23 Automatic Adjusted Limits The following are set points that will be limited based on the option selected. Evaporator Leaving Water Temperature Mode Refrigerant Type Range Unit Mode = Cool R134a, R410A 40 to 60 ° F Unit Mode = Cool w/Glycol R134a 20 to 60 ° F Unit Mode = Cool w/Glycol...
24 WGZ030D through WGZ200D OMM 1130 - 2 Dynamic Defaults Some set points will have a particular default value loaded when another setting is changed. Refrigerant Dependent Defaults Set Point Refrigerant Type R134a R410A Low Evaporator Pressure Hold 29 psi 101 psi Low Evaporator Pressure Unload 28 ps...
OMM 1130 - 2 25 When the alarm occurs due to this trigger, it can auto reset the first two times each day, with the third occurrence being manual reset. For the auto-reset occurrences, the alarm will reset automatically when the evaporator state is Run again. This means the alarm stays active while ...
28 WGZ030D through WGZ200D OMM 1130 - 2 Alarm Log An alarm log stores the last 25 alarms and/or events to occur. When an alarm or event occurs, it is put into the first slot in the alarm log and all others are moved down one, dropping the last entry. In the alarm log, the date and time the alarm occ...
OMM 1130 - 2 29 High Condenser Pressure - Unload Event description (as shown on screen): CondPressHighUnloadN Trigger: This event is triggered if all of the following are true: • circuit state = Run • more than one compressor is running on the circuit • condenser pressure > High Condenser Pressur...
OMM 1130 - 2 31 Controller Operation Calculations The Control Band defines the temperatures around the Controlling Leaving Water Temperature set point where compressors will be staged on or off. In cool mode, the controlling leaving water temperature set point will be Evap LWT. In heat mode, the con...
32 WGZ030D through WGZ200D OMM 1130 - 2 The Stage Down temperature is calculated as: Stage Down Temperature = Heat LWT + (Control Band/2) The Heat Start up and Shutdown temperatures are calculated from the Control Band. The Start Up temperature determines when the first compressor on the unit will s...
OMM 1130 - 2 33 Parameters used: 1. Heating Leaving Water Temperature set point (Heat LWT)2. Heating Maximum Reset set point (Htg MaxRes)3. LWT Reset signal 4-20mA Reset is 0ºF and the active leaving water set point is equal to the Heat LWT set point if the reset signal is less than or equal to 4 mA...
34 WGZ030D through WGZ200D OMM 1130 - 2 Heating Mode Return Reset Heat LWT set point Htg MaxRes set point Heat LWT (–) Htg MaxRes Htg StrtResDT setpoint (range of reset action) Condenser Delta Temperature (140ºF) (10ºF) (130ºF) 0ºF ‘Active’ Heat LWT Set Point The active heating leaving water set poi...
OMM 1130 - 2 35 Evaporator Saturated Temperature Evaporator saturated temperature is calculated from the evaporator pressure for each circuit. R410a Evaporator Saturated Temperatures When R410a refrigerant is selected the refrigerant pressure will be fitted to a curve made up of 24 straight-line seg...
36 WGZ030D through WGZ200D OMM 1130 - 2 Changing the Unit Enable Set Point is accomplished according to the following table. NOTE: An “x” indicates that the value is ignored. Unit Off Input Control Source Set Point Remote Input Key- pad Entry BAS Request Unit Enable OFF X x x x OFF x SWITCHES OFF x ...
38 WGZ030D through WGZ200D OMM 1130 - 2 Off Pumpdown Auto T1 T4 T3 T2 Power On Unit State Diagram Evaporator Water Pump State Control (Evap State) The state-transition diagram shown below controls operation of the evaporator pump. Off Run Start Unit State=Auto OREvap Water Freeze Alarm Unit State = ...
OMM 1130 - 2 39 Primary/Standby Pump Staging The pump designated as primary will start first. If the evaporator state is start for a time greater than the recirculate timeout set point and there is no flow, then the primary pump will shut off and the standby pump will start. When the evaporator is i...
40 WGZ030D through WGZ200D OMM 1130 - 2 8-Fan Remote Condenser, R22, R407C Stage Fans Operating on Circuit 1 Fans Operating on Circuit 2 1 Fan 1 Fan 2 2 Fans 1, 3 Fans 2, 4 3 Fans 1, 3, 5 Fans 2, 6, 8 4 Fans 1, 3, 5, 7 Fans 2, 4, 6, 8 8-Fan Remote Condenser, R410A Stage Fans Operating on Circuit 1 F...
OMM 1130 - 2 41 When stage down occurs or the saturated temperature rises back within the Stage Down dead band the Stage Down Error Accumulator is reset to zero. Forced Fan Stage at Start Fans may be started simultaneously with the compressor based on outdoor ambient temperature. When the compressor...
OMM 1130 - 2 43 Additional stages can turn on (up to the number specified by the Tower Stages set point) when above conditions are met for the next stage plus the following condition: VFD Speed is > the Stage Up @ set point (only if Valve/VFD Control set point = VFD Stage OR Valve SP/VFD Stage) D...
44 WGZ030D through WGZ200D OMM 1130 - 2 Valve Stage Mode This mode is only operational when the Valve/VFD Control set point is set to Valve Stage. In this mode the valve output is controlled as for Valve Set Point mode (above) except that the active set point for the controlled parameter is selected...
OMM 1130 - 2 45 Stage Down Now The Stage Down Now flag is set based on the following tests: If Unit Mode = Cool AND LWT error < -0.5 * Control band AND More than one compressor running AND Stage down timer expired THEN Stage Down Now = True If Unit Mode = Cool AND LWT error < (-0.5 * Control b...
46 WGZ030D through WGZ200D OMM 1130 - 2 compressor will shutdown if the evaporator pressure gets down to 5.0 psi. For R410a, the absolute limit for low evaporator pressure is 20.0 psi. When the Low OAT Start Timer has expired, if the evaporator pressure is greater than or equal to the Low Evaporator...
OMM 1130 - 2 47 Hold Clear Reset Value = High Pressure Unload set point – [“Initial Offset” + [“Step-Increase” x [“number of occurrence”-1]]] Initial Offset & Step Increase Condenser Configuration No. of Compressors R410A R22, R407C R134a Step Increase Water-Cooled 4 40 psi 30 psi 30 psi 10 psi ...
48 WGZ030D through WGZ200D OMM 1130 - 2 Network Limit The maximum unit capacity can be limited by a network signal. This function is only enabled if the unit control source is set to network. The maximum unit capacity stage is based on the network limit value received from the BAS, and is determined...
OMM 1130 - 2 49 • A normal stage down occurs, and only one compressor on the circuit is running • Unit mode = Ice AND the ice set point is reached Pump Down Procedure • If both compressors are running, shut off the appropriate compressor based on sequencing logic • With one compressor left running, ...
OMM 1130 - 2 51 Using the Controller Getting Started There are two basic procedures to learn in order to utilize the MicroTech II controller: • Navigating through the menu matrix to reach a desired menu screen and knowing where a particularscreen is located. • Knowing what is contained in a menu scr...
52 WGZ030D through WGZ200D OMM 1130 - 2 Figure 9, Display in the Shortcut (SCROLL) Mode and Keypad Layout ENTER Key Pressing the ENTER key changes the function of the ARROW keys to the editing function as shown below: LEFT key Default, changes a value to the factory-set default value. RIGHT key Canc...
OMM 1130 - 2 53 Figure 10, Menu Matrix “ MENU ” “ VIEW ” MENUS UNIT CIRCUITS REFRIGERANT FANS EVENTS VIEW UNIT STATUS (1) VIEW UNIT TEMP (1) VIEW CIRC #1 STATUS (1) VIEW CIRC #2 STATUS (1) VIEW REFRIGERANT CIRCUIT #1 (1) VIEW REFRIGERANT CIRCUIT #2 (1) VIEW FAN/TOWER (1) VIEW EVENT (1) VIEW UNIT STA...
OMM 1130 - 2 55 This menu gives the status of digital inputs (D.I.), 1=ON, 0=OFF. Numbers are 1 through 18. See Table 5 on page 19 for number reference. VIEW UNIT STATUS (6) Analog Output(volts x 100) 1 = 000.0 2 = 000.0 VIEW UNIT STATUS (7) Analog Output(volts x 100) 3 = 000.0 4 = 000.0 VIEW UNIT S...
56 WGZ030D through WGZ200D OMM 1130 - 2 VIEW UNIT TEMP (3)Control Temps Start Up XX.X ° F Stage Up XX.X ° F VIEW UNIT TEMP (4)Control Temps Stage Down XX.X ° F Shut Down XX.X ° F TGZ Unit Only in Cool Mode TGZ Unit Only in Heat Mode VIEW UNIT TEMP (5) VIEW UNIT TEMP (5) Cond LWT XX.X ° F Cond LWT XX...
OMM 1130 - 2 59 Water Cooled = Y Only or TGZ Unit (R134a) VIEW TOWER (2) Bypass Valve = XXX% VFD Speed = XXX% The Bypass Valve value shall be “None” (in place of XXX%) if the Valve/VFD Control setpoint = None or VFD Stage. The VFD Speed value shall be “None” if the Valve/VFD Control setpoint = None,...
60 WGZ030D through WGZ200D OMM 1130 - 2 Screen Definitions – EVENT LOG EVENT LOG (X)Event DescriptionTime Date Screen Definitions – SET Set Unit Setpoints SET UNIT SPs (1)Unit Enable = OFF Unit Mode = COOL Source = KEYPAD Unit Enable settings can be OFF and ON as determined from the Unit Enable setp...
OMM 1130 - 2 61 SET UNIT SPs (4) Start Delta= XX.X ° F Stop Delta= XX.X ° F Demand Limit = ON See page 13 for an explanation of compressor staging. WGZ Units Only TGZ Units Only (R134a) SET UNIT SPs (5) Max Pulldn=X.X ° F/min Evap Recirc= XXX sec Evap Pump = #1 Only SET UNIT SPs (5) Max Pulldn=X.X °...
OMM 1130 - 2 63 WGZ Unit (R22,R407C,R410A) TGZ Unit (Refrig = 134a) SET UNIT SPs (17) SET UNIT SPs (17) ENTER PASSWORD: XXXX Clg ResType = X Active Password Clg MaxRes = XX.X º F Level: None Clg StrtRes = XX.X º F TGZ Unit in Cooling Mode . TGZ Unit in Heat Mode. SET UNIT SPs (17) SET UNIT SPs (17) ...
64 WGZ030D through WGZ200D OMM 1130 - 2 # of Compressors = 4 # of Compressors = 6 SET COMP SPs (3) SET COMP SPs (3) Comp 1 = Enable Comp 1 = Enable Comp 3 = Enable Comp 3 = EnableComp 5 = Enable # of Compressors = 4 # of Compressors = 6 SET COMP SPs (4) SET COMP SPs (4) Comp 2 = Enable Comp 2 = Enab...
OMM 1130 - 2 65 The last action to take place is the shutoff of all compressors running when the LowEvPrStop setting is reached (default is 58 psi). Reducing these time intervals will increase detrimental compressor cycling. It is recommended that these settings not be changed. SET ALARM LMTS (2) Hi...
OMM 1130 - 2 67 Bypass valve position is > the Stage Up @ setpoint (only if Valve/VFD Control setpoint = Valve Stage) Additional stages can turn on (up to the number specified by the Tower Stages setpoint) when above conditions are met for the next stage plus the following condition: VFD Speed is...
68 WGZ030D through WGZ200D OMM 1130 - 2 Wa t e r - c o o l e d = Y SET TOWER SPs (4) Valve/VFD Control= ValveSP/VFDStage Valve Type=NC to Twr Valve/VFD Control settings are None, Valve Setpoint, Valve Stage, VFD Stage, or ValveSP/VFDStage. Default is None which results in no control of the tower fro...
OMM 1130 - 2 69 Figure 11, Initial Valve Position Operation After Start When the condenser pump is in the RUN state, the valve output shall be controlled in one of two modes as specified by the Valve/VFD Control setpoint. The controlled parameter shall be the condenser entering water temperature. Wh...
70 WGZ030D through WGZ200D OMM 1130 - 2 TEST The test screens are only available when the unit is in TEST mode. Using these screens, any digital output can be controlled manually. R 2 2 , R 4 0 7 C R 4 1 0 A TEST UNIT (1) TEST UNIT (1) Alarm Signal =OFF Alarm Signal =OFF Evap Pump 1 = OFF Evap Pump ...
72 WGZ030D through WGZ200D OMM 1130 - 2 BAS Interface The BAS interface will use the supervisor port on the controller as a connection point. Protocols Supported The following building automation system (BAS) protocols are supported. It is possible to change the building automation interface without...
OMM 1130 - 2 73 Table continued Type Index I/O Description LONworks BACnet Modbus I 11 O Active alarms 11 x x x I 12 O Active alarms 12 x x x I 13 O Active alarms 13 x x x I 14 O Active alarms 14 x x x I 15 O Active alarms 15 x x x I 16 O Active alarms 16 x x x I 17 I Network chiller mode set point ...
74 WGZ030D through WGZ200D OMM 1130 - 2 Chiller Mode Applies to Integer 17 and Integer 19. Network Chiller Mode Set Point and Active Chiller Mode use the same numbering scheme to represent ice mode or cool mode. The output representing the mode is shown below for each protocol. Mode LONworks BACnet ...
OMM 1130 - 2 75 setting is checked. If this is set low, then the defaults for BAS cool set point, network limit, unit enable, and unit mode will be loaded. If the setting is set high, then no defaults are loaded and the status of the BAS enable set point is restored to the original value. Other Digi...
76 WGZ030D through WGZ200D OMM 1130 - 2 Compressor Motor protection Module The 20, 26, and 30 HP compressors are equipped with an module that provides protection against: • High motor temperature • High scroll temperature • Phase missing • Phase reversal • Low control circuit voltage The module also...
78 WGZ030D through WGZ200D OMM 1130 - 2 Optional Controls Phase/Voltage Monitor (Optional) The phase/voltage monitor is a device that provides protection against three-phase electrical motor loss due to power failure conditions, phase loss, and phase reversal. Whenever any of these conditions occur,...
OMM 1130 - 2 79 System Maintenance General To provide smooth operation at peak capacity and to avoid damage to package components, a program of periodic inspections should be set up and followed. The following items are intended as a guide to be used during inspection and must be combined with sound...
80 WGZ030D through WGZ200D OMM 1130 - 2 POE Lubrication PO E type oil is used for compressor lubrication. This type of oil is extremely hygroscopic, which means it will quickly absorb moisture if exposed to air and may form acids that can be harmful to the chiller. Avoid prolonged exposure of POE oi...
OM 1130- 2 81 Maintenance Schedule I. Compressor A. Performance Evaluation (Log & Analysis) * O B. Motor • Meg. Windings X • Ampere Balance (within 10%) X • Terminal Check (tight connections, porcelain clean) X • Motor Cooling (check temperature) X C. Lubrication System • Oil Level O X • Oil App...
82 OM 1130- 2 System Service DANGER Service on this equipment is to be performed only by qualified refrigeration personnel. Causes for repeated tripping of equipment protection controls must be investigated and corrected. Disconnect all power before doing any service inside the unit or serious perso...
OM 1130- 2 83 Table 8, Thermostatic Expansion Valve Note: Superheat will vary with compressor unloading, but should be approximately as follows: between 8°F and 12°F (4.4°C and 6.7°C) at full load; between 6°F and 10°F at part load. Water-cooled Condenser The condenser is of the shell-and-tube type ...
84 OM 1130- 2 Troubleshooting Chart PROBLEM POSSIBLE CAUSES POSSIBLE CORRECTIVE STEPS Compressor Will Not Run 1. Main switch, circuit breakers open. 2. Fuse blown. 3. Thermal overloads tripped or fusesblown. 4. Defective contactor or coil. 5. System shut down by equipmentprotection devices. 6. No co...
Daikin Manuals
-
Daikin 3MXS68G2V1B
Installation Manual
-
Daikin 3P207257-3
Installation Manual
-
Daikin 4MKS75F2V1B
User Manual
-
Daikin 2AMX50G3V1B
Installation Manual
-
Daikin ACEF 3AV1-(C)(H)
User Manual
-
Daikin ACEF 3AVE
User Manual
-
Daikin ACEF 4AV1-(C)(H)
User Manual
-
Daikin 4MXS68F2V1B
User Manual
-
Daikin AGZ 130D
Installation Manual
-
Daikin AGZ 140D
User Manual
-
Daikin AH123E35AX
User Manual
-
Daikin AGZ030EH
Installation Manual
-
Daikin AGZ 040D
Installation Manual
-
Daikin Altherma HT
Installation Manual
-
Daikin AKZJ8Series
User Manual
-
Daikin Altherma Large Monobloc
User Manual
-
Daikin ARC423A17
User Manual
-
Daikin ARC433B46
User Manual
-
Daikin ARC433B47
User Manual
-
Daikin Altherma LT
User Manual