Daikin VAM 2000GJVE- Manuals
Daikin VAM 2000GJVE– User Manual in PDF format online.
Manuals:
User Manual Daikin VAM 2000GJVE
Summary
VAM-FA E E D E N 1 1 - 2 0 5 Ventilation H e a t R e c l a i m V e n t i l a t i o n Technical Data
• Ventilation • Heat Reclaim Ventilation 1 • HRV • VAM-FA TABLE OF CONTENTS VAM-FA 1 External appearance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2 Model series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 2 10 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133 Reducing operating sound . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 3 1 External appearance HR V VA M- FA He at R ec la i Ve nt il at io n 2 Model series VAM150FA VAM250FA VAM350FA VAM500FA VAM650FA VAM800FA VAM1000FA VAM1500FA VAM2000FA 3 Nomenclature VAM150FA VAM250FA VAM350FA VAM500FA VAM650FA VAM800FA VAM10...
• Ventilation • Heat Reclaim Ventilation 4 • HRV • VAM-FA 4 Structures VAM150-1000FA VAM1500,2000FA (HC0238) Ceiling hock Duct connection flange Damper Exhaust fan Air filter (Long life filter) Maintenance cover Switch box Name plate SA(Supply air)[Feed air to room] Air supply fan RA(Return air)[Exh...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 5 5 Features 5 - 1 Interlocked operation with VRV (SkyAir) 1. Simultaneous ON / OFF with the indoor unit by the indoor unit remote control.2. HRV independent operation during air conditioning off season by the indoor unit remote control.3. Auto...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 6 5 Features 5 - 2 Energy Saving Note: 1. The total heating / cooling load may vary depending on the climate or the other environmental conditions. HRV unit recovers the thermal energy during cooling / heating operation of air conditioner. HRV ...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 7 5 Features 5 - 3 FRESH-UP operation Both the excessive supply mode and the excessive exhaust mode are selectable. This function creates a more comfortable air environment. 5 - 4 Element (HEP element) Material The heat exchanger element adopts...
• Ventilation • Heat Reclaim Ventilation 8 • HRV • VAM-FA 5 Features 5 - 5 Easy Installation and service maintenance Downsized Total volume is reduced to 68% of EJ series and the unit fits into a small space. Parallel air flow system (Daikin) Cross air flow system This system prevents misconnection ...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 9 6 Selection Procedures 6 - 1 Based on inhabitants Various methods are used to calculate the required ventilating airflow rate according to CO2 generated by inhabitants in a room, waste gas generated by use of fire, and other conditions of a r...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 10 6 Selection Procedures 6 - 2 Based on Room size <Table 3> Criteria for Model Selection Required ventilating AFR per person (m 3 / h / person) Area per person (m 2 / person) Model Name Frequency Air Flow Rate Application area (m 2 ) Hz ...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 12 7 Product Specification 7-1 Technical Specifications VAM150FA VAM250FA VAM350FA VAM500FA VAM650FA VAM800FA VAM1000A VAM1500A VAM200FA Power input - 50Hz Heat exchange mode Nom. Ultra high kW 0.116 0.141 0.194 0.212 0.380 0.451 0.469 0.864 0....
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 14 7 Product Specification Notes: (1) Operation sound is measured at 1.5m below the center of the body. (2) Air flow rate can be changed to Low mode or High mode. (3) Normal amplitude, input and efficiency depend on the mentioned conditions. (4...
• Ventilation • Heat Reclaim Ventilation 15 • HRV • VAM-FA 7 Product Specification 7 - 2 Optional accessories Installation example (FR ESH A IR F ROM OU TDOORS) OA ROUND S H APE H O O D (F IELD SU PPLY) A GR ADIENT OF MOR E TH A N O N E IN FI FT Y IN SP EC TI ON H O LE (F IE LD SU PP LY ) NO M INA L...
• Ventilation • Heat Reclaim Ventilation 17 • HRV • VAM-FA 7 Product Specification 7 - 2 Optional accessories 7-2-1 BRC301B61: Remote control 7-2-1-1 Remote control mounting instructions 1. Remove the upper part of remote control. Insert minus screwdriver into the slots in the lower part of remote c...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 18 7 Product Specification 7 - 2 Optional accessories 7-2-1 BRC301B61: Remote control 7-2-1-1 Remote control mounting instructions Change the MAIN/SUB changeover switch setting as described below. 3. Wire the HRV unit. Connect the terminals on ...
• Ventilation • Heat Reclaim Ventilation 19 • HRV • VAM-FA 7 Product Specification 7 - 2 Optional accessories 7-2-2 KRP50-2: Wiring adapter for remote contact / HumidifierKRP50-2A90: Installation box for adapter PCB Components Installation guide 1 The KRP50-2 can be connected to HRV units as follows...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 20 7 Product Specification 7 - 2 Optional accessories 7-2-3 KRP2A51, KRP2A61: Wiring adapter for electrical appendices KRP2A51 (For Europe) KRP2A61 (For General) Accessories Check the following accessories are included in the kit before the ins...
• Ventilation • Heat Reclaim Ventilation 21 • HRV • VAM-FA 7 Product Specification 7 - 2 Optional accessories 7-2-3 KRP2A51, KRP2A61: Wiring adapter for electrical appendices Notes: Individual indoor units connected to the centralized line cannot be displayed individually. Names of parts and functio...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 22 7 Product Specification 7 - 2 Optional accessories 7-2-3 KRP2A51, KRP2A61: Wiring adapter for electrical appendices Installation Ceiling mounted corner cassette (HC0118) 4-way blow ceiling mounted cassette Note: To install the adapter.Box fo...
• Ventilation • Heat Reclaim Ventilation 23 • HRV • VAM-FA 7 Product Specification 7 - 2 Optional accessories 7-2-3 KRP2A51, KRP2A61: Wiring adapter for electrical appendices 2-way blow ceiling mounted cassette Note: A separate plate is needed to installthe adapter PCB. (HC0247) Wall mounted unit (H...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 24 7 Product Specification 7 - 2 Optional accessories 7-2-3 KRP2A51, KRP2A61: Wiring adapter for electrical appendices Concealed ceiling unit (large) (HC0248) (V0219) Ceiling suspended unit Note: A separate plate is needed to install the adapte...
• Ventilation • Heat Reclaim Ventilation 25 • HRV • VAM-FA 7 Product Specification 7 - 2 Optional accessories 7-2-3 KRP2A51, KRP2A61: Wiring adapter for electrical appendices (Concealed) floor standing unit (HC0250) Electrical wiring 1. First, wire between the indoor and outdoor units, then to the s...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 26 7 Product Specification 7 - 2 Optional accessories 7-2-3 KRP2A51, KRP2A61: Wiring adapter for electrical appendices 1. For zone control Wiring to indoor units (Wiring specifications)Wiring .... Sheathed wire (2-wire)Gauge .... 0.75 ~ 1.25 mm...
• Ventilation • Heat Reclaim Ventilation 27 • HRV • VAM-FA 7 Product Specification 7 - 2 Optional accessories 7-2-3 KRP2A51, KRP2A61: Wiring adapter for electrical appendices 1. Remote control input (operation control) Wire as described below. Wiring differs depending on whether using a voltage or n...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 30 7 Product Specification 7 - 2 Optional accessories 7-2-3 KRP2A51, KRP2A61: Wiring adapter for electrical appendices 3. Temperature setting input Temperature setting corresponds to resistance values in the range of 0 to 135 Ω . Their relation...
• Ventilation • Heat Reclaim Ventilation 31 • HRV • VAM-FA 7 Product Specification 7 - 2 Optional accessories 7-2-3 KRP2A51, KRP2A61: Wiring adapter for electrical appendices 4. Cancelling display signals Operation output terminals (W1 and W2) and malfunction output terminals (W3 and W4) are non-vol...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 32 7 Product Specification 7 - 2 Optional accessories 7-2-4 KRP1B61: Interlock adapter of VRV Names of parts X 1 Accessories Check if the following accessories are included in the kit. Notes • Kits vary according to applicable models. • A speci...
• Ventilation • Heat Reclaim Ventilation 33 • HRV • VAM-FA 7 Product Specification 7 - 2 Optional accessories 7-2-4 KRP1B61: Interlock adapter of VRV Electric Wiring • Refer to the WIRING DIAGRAM attached to the indoor unit before attempting to wire. [Make sure wires to units do not pass over the PC...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 36 7 Product Specification 7 - 2 Optional accessories 7-2-5 KRP1B2: Interlock adapter of VRV Contents of kit Prior to installation check whether you have the complete kit of parts as shown below including the installation manual. Notes: • Be ca...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 38 7 Product Specification 7 - 2 Optional accessories 7-2-6 KRP1B3: Interlock adapter of VRV Contents of kit Prior to installation check whether you have the complete kit of parts as shown below including the installation manual. Name of parts ...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 40 7 Product Specification 7 - 2 Optional accessories 7-2-7 DCS302C51: Centralized control BEFORE USE: GENERAL DESCRIPTION OF SYSTEM • When using 1 central remote control • When using 2 central remote controls For a maximum of 64 groups of indo...
• Ventilation • Heat Reclaim Ventilation 41 • HRV • VAM-FA 7 Product Specification 7 - 2 Optional accessories 7-2-7 DCS302C51: Centralized control CAUTIONS DURING USE • Do not tamper with the inner machanism. Do not remove the front panel. Tampering with the inner mechanism is dangerous and may dama...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 46 7 Product Specification 7 - 2 Optional accessories 7-2-7 DCS302C51: Centralized control FEATURES AND FUNCTIONS • Utilizing one of the PC board adapters (optional accessories) will enable you to combine this unit with the split. A/C units and...
• Ventilation • Heat Reclaim Ventilation 47 • HRV • VAM-FA 7 Product Specification 7 - 2 Optional accessories 7-2-7 DCS302C51: Centralized control NAMES AND FUNCTIONS OF THE OPERATING SECTION (Fig. 1,2) UNIFIED OPERATION BUTTON “ No. ” DISPLAY (TIME NO.) Press to operate all indoor units. Displays t...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 48 7 Product Specification 7 - 2 Optional accessories 7-2-7 DCS302C51: Centralized control “ ” “ ” DISPLAY (TIME TO CLEAN AIR CLEANER ELEMENT/TIME TO CLEAN AIR FILTER) TEMPERATURE SETTING BUTTON Displayed to notify the user it is time to clean ...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 50 7 Product Specification 7 - 2 Optional accessories 7-2-7 DCS302C51: Centralized control OPERATION OPERATION BY ZONE (Fig. 4) Press the ZONE/GROUP CHANGEOVER BUTTON, to call up the display of zoning. Press the ADVANCE/ BACKWARD BUTTON, to sel...
• Ventilation • Heat Reclaim Ventilation 51 • HRV • VAM-FA 7 Product Specification 7 - 2 Optional accessories 7-2-7 DCS302C51: Centralized control Press the TEMPERATURE SETTING BUTTON. Each time you press the “ ”, the temperature rises by 1°C. Each time you press the “ ”, the temperature falls by 1°...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 52 7 Product Specification 7 - 2 Optional accessories 7-2-7 DCS302C51: Centralized control OPERATION MODE The following five operation control modes can be selected along with the temperature setting and operation mode by remote control, for a ...
• Ventilation • Heat Reclaim Ventilation 53 • HRV • VAM-FA 7 Product Specification 7 - 2 Optional accessories 7-2-7 DCS302C51: Centralized control Note: Do not select the timer operation possible without the remote control. In this case, timer operation is disabled. Operation schedule is possible on...
• Ventilation • Heat Reclaim Ventilation 55 • HRV • VAM-FA 7 Product Specification 7 - 2 Optional accessories 7-2-7 DCS302C51: Centralized control SETTING OPERATION MODE (Fig. 5) • The Zone consists of the following two cases. See page 121 if the display “ ” is flashing. Press the OPERATION MODE SEL...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 56 7 Product Specification 7 - 2 Optional accessories 7-2-7 DCS302C51: Centralized control TEMPERATURE SETTING (Fig. 6) Press the TEMPERATURE SETTING BUTTON. Each time you press the “ ”, the temperature rises by 1°C. Each time you press the “ ”...
• Ventilation • Heat Reclaim Ventilation 57 • HRV • VAM-FA 7 Product Specification 7 - 2 Optional accessories 7-2-7 DCS302C51: Centralized control ERROR DIAGNOSING FUNCTION (Fig. 8) This central remote control is provided with a diagnosing function, for when an indoor unit stops due to malfunction. ...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 58 7 Product Specification 7 - 2 Optional accessories 7-2-7 DCS302C51: Centralized control FUNCTION OF REFRIGERANT SYSTEM DISPLAY (Fig. 10) The following information becomes available by utilizing this function. • Indoor group connected with th...
• Ventilation • Heat Reclaim Ventilation 59 • HRV • VAM-FA 7 Product Specification 7 - 2 Optional accessories 7-2-7 DCS302C51: Centralized control UNIFIED OPERATION (Fig. 12) Use this function when executing operation and stop of all the connected indoor units. Unified operation Press the UNIFIED OP...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 60 7 Product Specification 7 - 2 Optional accessories 7-2-7 DCS302C51: Centralized control OPTIONAL ACCESSORIES DOUBLE CENTRAL REMOTE CONTROLS Note: • For control alignment and settings for double central remote control, contact your DAIKIN dea...
• Ventilation • Heat Reclaim Ventilation 61 • HRV • VAM-FA 7 Product Specification 7 - 2 Optional accessories 7-2-7 DCS302C51: Centralized control SPECIFICATIONS Specifications Outline drawings Power supply Single phase, 50 / 60 Hz, 220 – 240 V / 220 V Power consumption Max. 4.5 W Forced ON / OFF in...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 64 7 Product Specification 7 - 2 Optional accessories 7-2-9 DST301B61: Schedule timer CAUTIONS DURING USE • Do not tamper with the inner mechanism. Do not remove the front panel. Tampering with the inner mechanism is dangerous and may damage eq...
• Ventilation • Heat Reclaim Ventilation 65 • HRV • VAM-FA 7 Product Specification 7 - 2 Optional accessories 7-2-9 DST301B61: Schedule timer Fig.1 Fig.2 SCHEDULE TIMER OK OK MIN. MIN. (1 ~ ~ 6 0) PROGRAM PROGRAM NO. NO. NO. NO. HR. HR. (1 ~ ~ 12 ) DAY DAY COPY COPY DAY DAY CLOCK CLOCK (1 ~ ~ 7) DAY...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 68 7 Product Specification 7 - 2 Optional accessories 7-2-9 DST301B61: Schedule timer OPERATION SETTING PRESENT TIME (Fig. 3) Press the CLOCK ADJUSTING BUTTON. The present time display flashes. Note:The present time needs adjusting in case of t...
• Ventilation • Heat Reclaim Ventilation 69 • HRV • VAM-FA 7 Product Specification 7 - 2 Optional accessories 7-2-9 DST301B61: Schedule timer SETTING NO. OF PROGRAMMED TIME (Fig. 4) Press the PROGRAMMING START BUTTON. Programming is available. The display “PROGRAM START” appears, and the display of ...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 70 7 Product Specification 7 - 2 Optional accessories 7-2-9 DST301B61: Schedule timer Press the PROGRAMMING START BUTTON, and finish the program setting. Notes:• Unless the button is pressed within 20 minutes, the display will automatically rev...
• Ventilation • Heat Reclaim Ventilation 71 • HRV • VAM-FA 7 Product Specification 7 - 2 Optional accessories 7-2-9 DST301B61: Schedule timer A. Change/cancel partially Press OK button if you do not want to change the timer on. The display of the next programmed time flashes. Each time you press it,...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 72 7 Product Specification 7 - 2 Optional accessories 7-2-9 DST301B61: Schedule timer MANUAL OPERATION (Fig. 6) This schedule timer enables the operation/stop by pressing the UNIFIED OPERATION/STOP BUTTON in addition to the operation controlled...
• Ventilation • Heat Reclaim Ventilation 73 • HRV • VAM-FA 7 Product Specification 7 - 2 Optional accessories 7-2-9 DST301B61: Schedule timer SPECIFICATION SPECIFICATIONS OUTLINE DRAWINGS Display of time 12-hour digital display Clock cycle type Quartz clock type Clock accuracy Within ± 30 sec. / mon...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 74 7 Product Specification 7 - 2 Optional accessories 7-2-10 K-DGL100A, K-DGL150A, K-DGL200A, K-DGL250A: Air suction / discharge grill Applications and features • The grille can be installed at any location, using a duct. • The grille effective...
• Ventilation • Heat Reclaim Ventilation 75 • HRV • VAM-FA 7 Product Specification 7 - 2 Optional accessories 7-2-10 K-DGL100A, K-DGL150A, K-DGL200A, K-DGL250A: Air suction / discharge grill Dimensions K-DGL100A K-DGL150A K-DGL200A K-DGL250A 165330 261 74 97 200 12 284 180 180 284 300 27 169 125 1...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 76 7 Product Specification 7 - 2 Optional accessories 7-2-10 K-DGL100A, K-DGL150A, K-DGL200A, K-DGL250A: Air suction / discharge grill Installation procedure Before starting installation, attach the supplied packing to the adapter provided in t...
• Ventilation • Heat Reclaim Ventilation 77 • HRV • VAM-FA 7 Product Specification 7 - 2 Optional accessories 7-2-10 K-DGL100A, K-DGL150A, K-DGL200A, K-DGL250A: Air suction / discharge grill Common works Duct connection and ceiling board installation 1. Put the duct into the adapter and fix them by ...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 78 7 Product Specification 7 - 2 Optional accessories 7-2-11 KDDM24A50, KDDM24A100: Silencer Applications and features • The silencer effectively reduces the noise of the HRV units.• Air flow rate should be lower than 600 m 3 / h for the model ...
• Ventilation • Heat Reclaim Ventilation 79 • HRV • VAM-FA 7 Product Specification 7 - 2 Optional accessories 7-2-12 YAFF323F15, YAFF323F25, YAFF323F35,YAFF323F50, YAFF323F65, YAFF323F100: Air filter replacement Specification Dimension Part No. Applicable model Q’ty YAFF323F15 VAM150FA 2 YAFF323F25 ...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 80 7 Product Specification 7 - 2 Optional accessories 7-2-13 K-FDS101C, K-FDS151C, K-FDS201C, K-FDS251C, K-FDS102C, K-FDS152C, K-FDS202C, K- FDS252C: Flexible Duct Applications and features • Flexible duct is used for the outdoor supply air / e...
• Ventilation • Heat Reclaim Ventilation 81 • HRV • VAM-FA 7 Product Specification 7 - 2 Optional accessories 7-2-15 BRP4A50: Heater control kit Operation range of the HRV is “ –10°C to 50°CDB 80% RH or below.” When operating the HRV units at or below –10°C of the outdoor air temperature, use prehea...
• Ventilation • Heat Reclaim Ventilation 83 • HRV • VAM-FA 7 Product Specification 7 - 2 Optional accessories 7-2-15 BRP4A50: Heater control kit Heater control kit Installation Switch box Accessories See the right for component. Fixing Screw 2 pcs. Clamp 2 pcs. Install the Heater control kit to the ...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 84 7 Product Specification 7 - 3 The correction ratio of exchange efficiency <Example of correction> VAM500 (50Hz): Air flow rate at strong notch 500 m 3 /h (Cooling) Enthalpy exchanging efficiency 58% Supply air and exhaust air flow rate...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 90 7 Product Specification 7 - 5 Wiring diagram VAM150-1000FA 2TW24836-1C Before obtaining access to terminal devices, all power supply circuits must be interrupted. Clean the heat exchange elements once every two years or more often and the ai...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 92 7 Product Specification 7 - 6 Sound level data 7-6-1 Overall sound pressure levels Ventilation Mode 220V / 50Hz 230V / 50Hz Total Heat Exchange mode Bypass mode Total Heat Exchange mode Bypass mode Fan Speed U-H H L U-H H L U-H H L U-H H L M...
• Ventilation • Heat Reclaim Ventilation 93 • HRV • VAM-FA 7 Product Specification 7 - 6 Sound level data 7-6-2 Sound power spectrum VAM150FA VAM250FA VAM350FA VAM500FA VAM650FA Measuring placeNotes: 1. Operation sound is measured in an anechoic chamber.2. The operating sound level may become greate...
• Ventilation • Heat Reclaim Ventilation 95 • HRV • VAM-FA 7 Product Specification 7 - 6 Sound level data 7-6-3 Sound pressure spectrum VAM150FA VAM250FA VAM350FA 50Hz 220V 50 Hz 230 V 50Hz 240V 60Hz 2 20V Octave band sound pressure level dB (OdB = 0.0002 μbar) Approximate threshold hearing for cont...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 98 7 Product Specification 7 - 7 Fan performance VAM150FA VAM250FA VAM350FA VAM500FA VAM650FA Temperatur e ex change efficienc y Enthalp y ex change efficienc y (heating) Enthalp y ex change efficienc y (c ooling) Ultra-High High Low Ex te rnal...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 100 7 Product Specification 7 - 8 Installation method VAM150FA VAM250FA 3D036781 MAINTENANCE SPACE OA(FRESH AIR FROMOUTDOORS) ROUND SHAPE HOOD(FIELD SUPPLY) EA(EXHAUST AIR TO OUTDOORS) A GRADIENT OF MORE THAN ONE IN FIFTY INSPECTION HOLE (FIELD...
• Ventilation • Heat Reclaim Ventilation 105 • HRV • VAM-FA 8 Operation 8 - 1 Method of operation 8-1-1 Operation with the remote control exclusively for Air conditioning operation HRV units. (BRC301B61) For non-independent systems, starting / stopping operation and timer operation may not be possib...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 106 8 Operation 8 - 1 Method of operation 8-1-2 Operating the HRV unit using the remote control of the VRV- system air conditioner When the VRV-system air conditioner is connected with the HRV unit with a direct duct, the remote control of the ...
• Ventilation • Heat Reclaim Ventilation 107 • HRV • VAM-FA 8 Operation 8 - 2 Cautions in use WARNING Never inspect or service the unit by yourself.Ask a qualified service person to perform this work.(The qualified service person) WARNING Before obtaining access to terminal devices( ), all power sup...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 108 8 Operation 8 - 3 Maintenance CAUTION 1. Do not wash the air filter in hot water.2. Do not dry the air filter over a fire.3. Do not subject the air filter to direct sunlight.4. Do not use organic solvent such as gasoline and thinner on the ...
• Ventilation • Heat Reclaim Ventilation 109 • HRV • VAM-FA 9 Control System 9 - 1 Introduction of control system The control systems introduced here is for the HRV unit adopting the high speed and high performance transmission system (D III -NET), the same as the VRV systems and SkyAir series, Desc...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 110 9 Control System 9 - 2 Basic patterns 9-2-1 List of control system Control system Purposes and applications Description of system Optional accessories required Independ ent system O peration by mai n switc h • Basic method to operate HRV un...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 114 9 Control System 9 - 2 Basic patterns 9-2-2 Independent system Operation by main switch Purposes and functions • Basic method to operate HRV unit The remote control for HRV unit is installed on each HRV unit for its operation. [When you use...
• Ventilation • Heat Reclaim Ventilation 115 • HRV • VAM-FA 9 Control System 9 - 2 Basic patterns 9-2-2 Independent system Control with two remote controls Group control Purpose and functions • For control of one HRV unit (Also one group control is possible) Sophisticated operation and indication ou...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 116 9 Control System 9 - 2 Basic patterns 9-2-3 The interlocked operation system Single-group interlocked operation (Basic pattern) Single-group interlocked operation (Direct duct connection) Purposes and functions • The remote control for indo...
• Ventilation • Heat Reclaim Ventilation 117 • HRV • VAM-FA 9 Control System 9 - 2 Basic patterns 9-2-3 The interlocked operation system Interlocked operation with 2 or more group of VRV system Purposes and functions • When the HRV unit is interlocked to 2 or more group of indoor units, the HRV unit...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 118 9 Control System 9 - 2 Basic patterns 9-2-4 Centralized control system Collective / individual control [Unified On / Off control DCS301B61] Purposes and functions • One control can controll the operation of “ON / OFF” of 16 groups of the un...
• Ventilation • Heat Reclaim Ventilation 119 • HRV • VAM-FA 9 Control System 9 - 2 Basic patterns 9-2-4 Centralized control system Zone control system (Central remote control DCS302B61) Purposes and functions • A maximum of 64 groups can be controlled On / Off individually by one control. And also t...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 120 9 Control System 9 - 3 Applicable patterns 9-3-1 Additional functions Operation by power supply [HRV unit] Monitor of operation (KRP50-2) [HRV unit → operating pilot lamp (local supply)] Purposes and functions • The HRV unit is operated by ...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 122 9 Control System 9 - 3 Applicable patterns 9-3-1 Additional functions Precool / preheat operation Remote control operation by input from outside Purposes and functions • The operation of HRV unit is delayed when the air conditioner begins o...
• Ventilation • Heat Reclaim Ventilation 123 • HRV • VAM-FA 9 Control System 9 - 3 Applicable patterns 9-3-2 To connect the remote control to the HRV unit (Part 1) single-group interlocked operation (Part 2) Centralized control operation Purposes and functions When the HRV unit is interlocked to the...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 124 9 Control System 9 - 3 Applicable patterns 9-3-3 Central control system (DCS302B61) Collective / individual operation (Central remote control) Purposes and functions It is possible to have collective On / Off or individual On / Off without ...
• Ventilation • Heat Reclaim Ventilation 125 • HRV • VAM-FA 9 Control System 9 - 3 Applicable patterns 9-3-3 Central control system (DCS302B61) Collective operation (Schedule timer DST301B61) Purposes and functions • A maximum of 128 units can be controlled the collective operation / stop by weekly ...
• Ventilation • Heat Reclaim Ventilation 127 • HRV • VAM-FA 9 Control System 9 - 3 Applicable patterns 9-3-3 Central control system (DCS302B61) Multi function central control + Unified On / Off Control *1. Independent operation for ventilation is possible, if collective zone interlock setting is “ON...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 128 9 Control System 9 - 3 Applicable patterns 9-3-4 Examples of mistakes in wiring and system designing It is necessary to install the remote control for the transmission line. The centralized transmission line should be connected to the indoo...
• Ventilation • Heat Reclaim Ventilation 129 • HRV • VAM-FA 9 Control System 9 - 3 Applicable patterns 9-3-4 Examples of mistakes in wiring and system designing Setting of Remote Control for HRV unit List of Settings Caution 1. The setting positions are set at “01” at the factory. The ventilation ai...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 130 9 Control System 9 - 4 Functions of Printed Circuit Board 9-4-1 Layout of switches on Printed Circuit Board 9-4-2 Function of main connection terminal Terminal No. Contents of function P ow er supply Single phase 220 - 240 V Power supply an...
• Ventilation • Heat Reclaim Ventilation 131 • HRV • VAM-FA 9 Control System 9 - 5 Fan operation setting 9 - 6 Pre -Operation flowchart Interlock ed operation sy stem W ith r emote control for indoor unit Initial setting by the remote control for indoor unit Fan operation Ventilation air flow settin...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 132 9 Control System 9 - 7 Operation mode change over 1. In case of cooling operation 1 zone: Free cooling (cooling by outdoor air) in bypass mode.* 2 zone: Room temperature to be achieved to set temperature by heat exchange mode. 3 zone: Room ...
• Ventilation • Heat Reclaim Ventilation 133 • HRV • VAM-FA 10 Installation 10 - 1 Reducing operating sound 10-1-1 Points for reducing operating sound 1. Operating sound heard from the air discharge outlet can be reduced just by applying sound-insulating material to the SA (indoor air supply) duct. ...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 134 10 Installation 10 - 1 Reducing operating sound 10-1-4 Effect of remedy for sound Caution 1. Be sure to connect a flexible duct (2 m) to an outlet of the main body in the indoor air supply side. 2. Do not connect a spiral duct and an almini...
• Ventilation • Heat Reclaim Ventilation 135 • HRV • VAM-FA 10 Installation 10 - 2 Centralized piping Because the air flow shown in Fig.1 is generated when centralized OA and EA pipings for two or more HRV units normal air flow cannot be maintained. If a back flow prevention damper is installed in t...
• Ventilation • Heat Reclaim Ventilation 137 • HRV • VAM-FA 10 Installation 10 - 3 Cautions 1) Operation in highly humid areas (in cooling mode) To prevent dew formation, use the unit under the condition that the indoor discharge air is 95% RH or less on the psychrometric chart. Fig.1 shows the limi...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 138 10 Installation 10 - 4 Cautions in installation Do not use a HRV or an air suction / discharge grille in the following places. • Place such as machinery plant and chemical plant where gas, which contains noxious gas or corrosive components ...
• Ventilation • Heat Reclaim Ventilation 139 • HRV • VAM-FA 10 Installation 10 - 6 Duct Work 10-6-1 Caution • Do not install ducts as shown below. 1. To prevent air leakage, wind aluminum tape round the section after the duct connecting flange and the duct are connected. 2. Install the opening of th...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 140 10 Installation 10 - 7 Electrical wiring procedure Before obtaining access to terminal devices, all power supply circuits must be interrupted. Connection of Wiring • Connect the wires in accordance with the diagram of each system.• All wiri...
• Ventilation • Heat Reclaim Ventilation 141 • HRV • VAM-FA 10 Installation 10 - 7 Electrical wiring procedure PRECAUTIONS 1. Do not connect wires of different gauge to the same power supply terminal. Looseness in the connection may cause overheating. When connecting more than one wire to the power ...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 142 10 Installation 10 - 7 Electrical wiring procedure 10-7-1 Opening the switch box Before opening the cover, be sure to turn off the power switches of the main units and other devices connected with the main units. • Remove the screw securing...
• Ventilation • Heat Reclaim Ventilation 143 • HRV • VAM-FA 10 Installation 10 - 8 Initial setting 10-8-1 Initial setting by the remote control for indoor unit Note: When you make several field settings to one (or one group of) indoor unit(s), the item to of the above setting procedure should be rep...
• HRV • VAM-FA • Ventilation • Heat Reclaim Ventilation 144 10 Installation 10 - 8 Initial setting 10-8-2 Setting procedure of group no. for centralized control The following shows the procedure how to set the group number for the centralized control by the remote control for indoor unit Notes: Do n...
• Ventilation • Heat Reclaim Ventilation 145 • HRV • VAM-FA 10 Installation 10 - 8 Initial setting 10-8-3 Initial setting for “Central zone control” When HRV unit is connected to the central transmission line (terminal connector no. (F1) and (F2)), it is necessary to make a initial setting of “colle...
Daikin Manuals
-
Daikin 3MXS68G2V1B
Installation Manual
-
Daikin 3P207257-3
Installation Manual
-
Daikin 4MKS75F2V1B
User Manual
-
Daikin 2AMX50G3V1B
Installation Manual
-
Daikin ACEF 3AV1-(C)(H)
User Manual
-
Daikin ACEF 3AVE
User Manual
-
Daikin ACEF 4AV1-(C)(H)
User Manual
-
Daikin 4MXS68F2V1B
User Manual
-
Daikin AGZ 130D
Installation Manual
-
Daikin AGZ 140D
User Manual
-
Daikin AH123E35AX
User Manual
-
Daikin AGZ030EH
Installation Manual
-
Daikin AGZ 040D
Installation Manual
-
Daikin Altherma HT
Installation Manual
-
Daikin AKZJ8Series
User Manual
-
Daikin Altherma Large Monobloc
User Manual
-
Daikin ARC423A17
User Manual
-
Daikin ARC433B46
User Manual
-
Daikin ARC433B47
User Manual
-
Daikin Altherma LT
User Manual