Page 2 - technical data; air conditioning systems
RZQ200-250C7Y1B EEDEN08-100 technical data air conditioning systems Split Sky Air
Page 3 - TABLE OF CONTENTS
• Split Sky Air • Outdoor Units 1 • Outdoor Units • R-410A • RZQ200-250C7Y1B TABLE OF CONTENTS RZQ200-250C7Y1B 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2 Specifications . . . . . . . . . . . . . . . . . . ....
Page 4 - Features
• Outdoor Units • R-410A • RZQ200-250C7Y1B 1 1 • Split Sky Air • Outdoor Units 2 1 Features Ou td oo r Un i S p l i t S k y RZ Q2 00 -2 50 C7 Y R- 41 0A • Outdoor units for pair, twin, triple, double twin application • The Sky Air Inverter is developed for use in shops, restaurants and small offices...
Page 5 - Specifications; -1 Nominal Capacity and Nominal Input
3 1 2 • Split Sky Air • Outdoor Units 3 • Outdoor Units • R-410A • RZQ200-250C7Y1B 2 Specifications 2-1 Nominal Capacity and Nominal Input RZQ200C7Y1B RZQ250C7Y1B For combination indoor units + outdoor units Indoor Units FDQ200B8V3B FDQ250B8V3B Cooling capacity Standard kW 20.0 24.1 Heating capacity...
Page 6 - -3 Electrical Specifications
• Outdoor Units • R-410A • RZQ200-250C7Y1B 1 2 • Split Sky Air • Outdoor Units 4 2 Specifications Refrigerant Type R-410A Charge kg 8.3 9.3 Control Expansion valve (electronic type) Nr of Circuits 1 1 Refrigerant Oil Type Synthetic (ether) oil Charged Volume l 0,3 Piping connections Liquid (OD) Quan...
Page 7 - Electrical data
3 1 3 • Split Sky Air • Outdoor Units 5 • Outdoor Units • R-410A • RZQ200-250C7Y1B 3 Electrical data RZQ200-250C Unit combination Minimum Ssc value [kVA] 4TW29041-2 NOTES -In accordance with EN/IEC 61000-3-12*, it may be necessary to consult thedistribution network operator to ensure that the equipm...
Page 8 - Options
• Outdoor Units • R-410A • RZQ200-250C7Y1B 1 4 • Split Sky Air • Outdoor Units 6 4 Options Available options for RZQ200,250C Name of option Kit name RZQ200C7Y1B RZQ250C7Y1B Central drain pan kit KWC26B280 Refrigerant branch piping Twin KHRQ22M20TA Triple KHRQ250H7 Double twin KHRQ22M20TA (3x) Demand...
Page 9 - Capacity tables; - 1 Combination table
3 1 5 • Split Sky Air • Outdoor Units 7 • Outdoor Units • R-410A • RZQ200-250C7Y1B 5 Capacity tables 5 - 1 Combination table Possible indoor combination Simultaneous operation Outdoor models Twin Triple Double twin RZQ200C7Y1B 100-100 (KHRQ22M20TA) 60-60-6071-71-71 (KHRQ250H) 50-50-50-50 (3x KHRQ22M...
Page 10 - - 2 Cooling capacity tables
• Outdoor Units • R-410A • RZQ200-250C7Y1B 1 5 • Split Sky Air • Outdoor Units 8 5 Capacity tables 5 - 2 Cooling capacity tables RZQ200C (Pair + Twin / triple / double twin) Cooling Cooling capacity 400V [50Hz] Indoor Outdoor temp. (°CDB) 25 30 35 40 °CWB TC (kW) SHC (kW) CPI (-) TC (kW) SHC (kW) CP...
Page 13 - - 3 Heating capacity tables
3 1 5 • Split Sky Air • Outdoor Units 11 • Outdoor Units • R-410A • RZQ200-250C7Y1B 5 Capacity tables 5 - 3 Heating capacity tables RZQ200C (Pair + Twin / triple / double twin) Heating Heating capacity 230V [50Hz] Indoor Outdoor temp. (°CWB) − 15 − 10 − 5 0 6 10 TC (kW) CPI (-) TC (kW) CPI (-) TC (k...
Page 15 - Dimensional drawing & centre of gravity; - 1 Dimensional drawing
3 1 6 • Split Sky Air • Outdoor Units 13 • Outdoor Units • R-410A • RZQ200-250C7Y1B 6 Dimensional drawing & centre of gravity 6 - 1 Dimensional drawing 3TW29044-1 1 Liquid pipe connection port see note 2.2 Gas pipe connection port see note 2.3 Grounding terminal inside of switch box (M8)4 Power ...
Page 16 - - 2 Centre of gravity
• Outdoor Units • R-410A • RZQ200-250C7Y1B 1 6 • Split Sky Air • Outdoor Units 14 6 Dimensional drawing & centre of gravity 6 - 2 Centre of gravity 4TW29049-4 RZQ200-250C Center of foundation bolt hole Center of foundation bolt hole Center of foundation bolthole (oblong hole) Center of foundatio...
Page 17 - Piping diagram
3 1 7 • Split Sky Air • Outdoor Units 15 • Outdoor Units • R-410A • RZQ200-250C7Y1B 7 Piping diagram 3TW29045-1 RZQ200-250C (Pair) Low pressure sensor Indoor heatexchanger Fan (With service port on on-sitepiping side J 7.9mm flare connection) Filter Electronic expansion valve Check valve High pressu...
Page 19 - Wiring diagram
3 1 8 • Split Sky Air • Outdoor Units 17 • Outdoor Units • R-410A • RZQ200-250C7Y1B 8 Wiring diagram 8 - 1 Wiring diagram 2TW29046-1B RZQ200-250C A1P-A6P Printed circuit board A1P Main A2P Noise filter A3P Inverter A4P Fan motor A6P QA Transmission BS1-BS5 Push button switch Mode, set, return, test,...
Page 20 - Sound data; - 1 Sound pressure spectrum
• Outdoor Units • R-410A • RZQ200-250C7Y1B 1 9 • Split Sky Air • Outdoor Units 18 9 Sound data 9 - 1 Sound pressure spectrum 3TW29047-1 Sound pressure level (dB) Octave band center frequency (Hz) RZQ200C - Cooling NOTES 1 Data is valid at free field condition (measured in asemi-anachoic room) 2 dB(A...
Page 21 - - 2 Sound power spectrum
3 1 9 • Split Sky Air • Outdoor Units 19 • Outdoor Units • R-410A • RZQ200-250C7Y1B 9 Sound data 9 - 2 Sound power spectrum 3TW29047-3 Sound power level (dB) Octave band center frequency (Hz) RZQ200C - Cooling NOTES 1 dB(A) = A-weighted sound pressure level (A-scale according to IEC) 2 Reference aco...
Page 22 - Installation; 0 - 1 Installation method
• Outdoor Units • R-410A • RZQ200-250C7Y1B 1 10 • Split Sky Air • Outdoor Units 20 10 Installation 10 - 1 Installation method 3TW29049-3 RZQ200-250C For single unit installation <Pattern 1> For installation in rows <Pattern 1> 300 or more 10 or more <Front> 500 or more 10 or more 1...
Page 23 - 0 - 2 Fixation and foundation of units
3 1 10 • Split Sky Air • Outdoor Units 21 • Outdoor Units • R-410A • RZQ200-250C7Y1B 10 Installation 10 - 2 Fixation and foundation of units 3D040102N RZQ200-250C NOTES 1 The proportions of cement: sand: gravel for the concrete shall be 1:2:4, and the reinforcement bars that their diameter are 10mm,...
Page 24 - Operation range
• Outdoor Units • R-410A • RZQ200-250C7Y1B 1 11 • Split Sky Air • Outdoor Units 22 11 Operation range 4TW26566-1 RZQ200-250C Outdoor temp. (°CDB) Operation range Allowable range of operation (pull-down) Indoor temp. (°CWB) Cooling Heating Indoor temp. (°CDB) Outdoor temp. (°CWB) Operation range Allo...