Daikin RXYSQ6M7V3B- Manuals
Daikin RXYSQ6M7V3B– User Manual in PDF format online.
Manuals:
User Manual Daikin RXYSQ6M7V3B
Summary
E E D E N 1 2 - 2 0 0 Air Conditioners V R V ® A i r - c o o l e d S e l e c t i o n P r o c e d u r e Technical Data
• VRV ® Systems • Air-cooled selection procedure 1 • Air-cooled selection procedure 1 Selection procedure VRV ® system based on cooling load . . . . 2 Flowchart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Step by step . ...
• Air-cooled selection procedure • VRV ® Systems • Air cooled selection procedure 2 2 1 1 Selection procedure VRV ® system based on cooling load 1 - 1 Flowchart CONDITIONS SELECTION OF INDOOR UNITS CONDITIONS FOR OUTDOOR UNIT SELECTION SELECTION OF OUTDOOR UNITS OPTIONAL ª ª ª Indoor & outdoor d...
• Air-cooled selection procedure • VRV ® Systems • Air cooled selection procedure 4 2 1 1 Selection procedure VRV ® system based on cooling load 1 - 2 Step by step 1 - 2 - 5 Define cooling capacity to be given by outdoor unit system: Step 1: Define Total cooling load to be absorbed by connected indo...
• VRV ® Systems • Air cooled selection procedure 5 • Air-cooled selection procedure 2 1 1 Selection procedure VRV ® system based on cooling load 1 - 3 Example 1 - 3 - 1 Design conditions • Determine indoor / outdoor design temperature Indoor: 20° CWB / 28° CDB Ambient: 33° CDB • Determine room peak ...
• Air-cooled selection procedure • VRV ® Systems • Air cooled selection procedure 6 2 1 1 Selection procedure VRV ® system based on cooling load 1 - 3 Example 1 - 3 - 5 Define cooling capacity to be given by outdoor unit system: Total cooling load • Sum of peak loads = 27.2 kW • System peak load = 2...
• VRV ® Systems • Air cooled selection procedure 7 • Air-cooled selection procedure 2 1 1 Selection procedure VRV ® system based on cooling load 1 - 3 Example 1 - 3 - 6 Selection of outdoor unit • select outdoor unit type RXYQ8P outdoor unit Indoor unit combination total capacity index table • Deter...
• Air-cooled selection procedure • VRV ® Systems • Air cooled selection procedure 8 2 2 2 Selection in heating mode 2 - 1 Flowchart CONDITIONS SELECTION OF INDOOR UNITS CONDITIONS FOR OUTDOOR UNIT SELECTION SELECTION OF OUTDOOR UNITS ª ª ª Indoor dry bulb temp & outdoor wet bulb temp. heat loads...
• VRV ® Systems • Air cooled selection procedure 9 • Air-cooled selection procedure 2 2 2 Selection in heating mode 2 - 2 Step by step 2 - 2 - 1 Design conditions: To start designing a VRV system in heating mode, following information is needed: • Indoor conditions: Dry bulb temperature (°CDB) • Hea...
• Air-cooled selection procedure • VRV ® Systems • Air cooled selection procedure 10 2 2 2 Selection in heating mode 2 - 2 Step by step 2 - 2 - 7 Selection of outdoor unit • Provisionally select outdoor unit size & type based on outdoor temperature (°CDB), indoor temperature (°CDB) & connect...
• VRV ® Systems • Air cooled selection procedure 11 • Air-cooled selection procedure 2 2 2 Selection in heating mode 2 - 3 Example 2 - 3 - 1 Design conditions • Determine indoor / outdoor design temperature Indoor: 18° CDB Ambient: 2.2° CWB / 3° CDB • Determine room peak loads (and if possible, syst...
• Air-cooled selection procedure • VRV ® Systems • Air cooled selection procedure 12 2 2 2 Selection in heating mode 2 - 3 Example 2 - 3 - 6 Define heating capacity to be given by outdoor unit system: Total heating load • Sum of peak loads = 28.6 kW • System peak load = 24.9 kW Correct total heat lo...
• Air-cooled selection procedure • VRV ® Systems • Air cooled selection procedure 14 2 3 3 Capacity correction ratio 3 - 1 VRV ® III heat recovery with connection to heating only hydrobox 1. Rate of change in heating capacity 2. Rate of change in cooling capacity 3TW60652-2A NOTES [Capacity correcti...
• Air-cooled selection procedure • VRV ® Systems • Air cooled selection procedure 18 2 3 3 Capacity correction ratio 3 - 2 VRV ® III heat recovery small footprint combination REYQ8P9, REYQ22P8 • Rate of change in cooling capacity • Rate of change in heating capacity 3D057931B NOTES 1 These figures i...
• Air-cooled selection procedure • VRV ® Systems • Air cooled selection procedure 22 2 3 3 Capacity correction ratio 3 - 2 VRV ® III heat recovery small footprint combination REYQ16P8 • Rate of change in cooling capacity • Rate of change in heating capacity 3D058183A NOTES 1 These figures illustrate...
• Air-cooled selection procedure • VRV ® Systems • Air cooled selection procedure 28 2 3 3 Capacity correction ratio 3 - 3 VRV ® III heat recovery high COP combination REYHQ16P • Rate of change in cooling capacity • Rate of change in heating capacity 3D058183A NOTES 1 These figures illustrate the ra...
• Air-cooled selection procedure • VRV ® Systems • Air cooled selection procedure 32 2 3 3 Capacity correction ratio 3 - 4 VRV ® III heat pump small footprint combination RXYQ5P Correction ratio for cooling capacity Correction ratio for heating capacity 3TW31472-1A NOTES 1 These figures illustrate t...
• VRV ® Systems • Air cooled selection procedure 45 • Air-cooled selection procedure 2 3 3 Capacity correction ratio 3 - 5 VRV ® III heat pump high COP combination &RUUHFWLRQUDWLRIRUFRROLQJFDSDFLW\ &RUUHFWLRQUDWLRIRUKHDWLQJFDSDFLW\ 7:$ 127(6 7KHVH¿JXUHVLOOXVWUDWHWKHFRUUHFWLRQUDWLRIRUSLSLQJOH...
• Air-cooled selection procedure • VRV ® Systems • Air cooled selection procedure 52 2 3 3 Capacity correction ratio 3 - 7 VRV ® III heating only &RUUHFWLRQUDWLRIRUKHDWLQJFDSDFLW\ 7: 127(6 7KHVH¿JXUHVLOOXVWUDWHWKHFRUUHFWLRQUDWLRIRUSLSLQJOHQJWKLQFDSDFLW\IRUDVWDQGDUGLQGRRUXQLWV\VWHPDWPD[LPXPORDGZL...
• Air-cooled selection procedure • VRV ® Systems • Air cooled selection procedure 64 2 4 4 Integrated heating capacity coefficient REYQ-P8/P9 INTEGRATED HEATING CAPACITY COEFFICIENT The heating capacity tables do not take account of the reduction in capacity, when frost has accumulated or while the ...
• Air-cooled selection procedure • VRV ® Systems • Air cooled selection procedure 66 2 4 4 Integrated heating capacity coefficient INTEGRATED HEATING CAPACITY COEFFICIENT The heating capacity tables do not take account of the reduction in capacity, when frost has accumulated or while the defrosting ...
• VRV ® Systems • Air cooled selection procedure 69 • Air-cooled selection procedure 2 4 4 Integrated heating capacity coefficient 3TW30402 NOTES 1. The figure shows that the integrated heating capacity expresses the integrated capacity for a single cycle (from defrost operation to defrost operation)...
• Air-cooled selection procedure • VRV ® Systems • Air cooled selection procedure 72 2 5 5 Refnet pipe systems DISCHARGE GAS SIDE JUNCTION SUCTION GAS SIDE JUNCTION LIQUID SIDE JUNCTION KHRQ5 8T7 KHRQ 23M7 5T8 K H R Q 23M 64T8 KHR Q 23M 20T8 KHRQ 23M2 9T9 KFRP23M 75T8 KHRP23M64T8 KHRP 23 M33T8 KHRQ2...
• Air-cooled selection procedure • VRV ® Systems • Air cooled selection procedure 82 2 6 6 Example of Refnet piping layouts Type of fitting Sample systems Dis tri bu tio n b y REF NET j oin ts Di str ibu tion by R EF NE T he ad er Dis tri but ion by REFNE T jo ints and he ad ers Outdoor unit Outdoor...
• VRV ® Systems • Air cooled selection procedure 83 • Air-cooled selection procedure 2 7 7 Refrigerant pipe selection 7 - 1 VRV ® III heat recovery small footprint combination Example of connection (Connection of 8 indoor units) Branc h with refnet joint Branc h with refnet joint and refnet header B...
• VRV ® Systems • Air cooled selection procedure 87 • Air-cooled selection procedure 2 7 7 Refrigerant pipe selection 7 - 3 VRV ® III heat recovery with connection to heating only hydrobox REYAQ-P 4PW62582-1A ■ Size: determine the proper size referring to following table: Refnet joint Branch selecto...
• Air-cooled selection procedure • VRV ® Systems • Air cooled selection procedure 88 2 7 7 Refrigerant pipe selection 7 - 3 VRV®III heat recovery with connection to heating only hydrobox REYAQ-P 4PW62582-1A Piping length restrictions ■ For refnets joints other than the first branch (example refnetjoi...
• VRV ® Systems • Air cooled selection procedure 89 • Air-cooled selection procedure 2 7 7 Refrigerant pipe selection 7 - 4 VRV ® III heat pump small footprint combination / high COP combination/heating only RXYQ-P9, RXYHQ-P9, RXHQ-P9 4PW67902-1(1) Example of connection (Connection of 8 indoor units...
• VRV ® Systems • Air cooled selection procedure 93 • Air-cooled selection procedure 2 7 7 Refrigerant pipe selection 7 - 6 Piping thickness O annealed 1/2H half-hard For half hard pipes the maximum allowed tensile stress is 61 N/mm 2 . For this reason the 0.2% proof strength of the half hard pipe s...
Daikin Manuals
-
Daikin 3MXS68G2V1B
Installation Manual
-
Daikin 3P207257-3
Installation Manual
-
Daikin 4MKS75F2V1B
User Manual
-
Daikin 2AMX50G3V1B
Installation Manual
-
Daikin ACEF 3AV1-(C)(H)
User Manual
-
Daikin ACEF 3AVE
User Manual
-
Daikin ACEF 4AV1-(C)(H)
User Manual
-
Daikin 4MXS68F2V1B
User Manual
-
Daikin AGZ 130D
Installation Manual
-
Daikin AGZ 140D
User Manual
-
Daikin AH123E35AX
User Manual
-
Daikin AGZ030EH
Installation Manual
-
Daikin AGZ 040D
Installation Manual
-
Daikin Altherma HT
Installation Manual
-
Daikin AKZJ8Series
User Manual
-
Daikin Altherma Large Monobloc
User Manual
-
Daikin ARC423A17
User Manual
-
Daikin ARC433B46
User Manual
-
Daikin ARC433B47
User Manual
-
Daikin Altherma LT
User Manual