Page 6 - English; III; CONTENTS; Safety Precaution; WARNING
1 English RWEYQ8PY1RWEYQ10PY1RWEYQ16PY1 RWEYQ18PY1RWEYQ20PY1RWEYQ24PY1 RWEYQ26PY1RWEYQ28PY1RWEYQ30PY1 VRVW III System air conditioner Installation manual CONTENTS 1. SAFETY PRECAUTIONS ....................................................... 12. INTRODUCTION..............................................
Page 7 - CAUTION; INTRODUCTION
English 2 • Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qualified personnel according to local laws and regulations and this installation manual.An insufficient power supply capacity or improper electrical con-struction may ...
Page 8 - -2 Standard operation limit; SELECTION OF LOCATION; THIN
3 English 2-2 Standard operation limit The figures below assume following operating conditions for indoor and outside units: Equivalent pipe length .....................................................7.5mLevel difference ..................................................................0m Cooling H...
Page 9 - Note; UNPACKING AND PLACING THE UNIT; WATER PIPING WORK; Caution; -1 When designing the equipment
English 4 3. Remote controller 4. Cool/heat selector 5. Personal computer or radio If the electric wave of AM broadcasting is particularly weak, keep distances of 3m or more and use conduit tubes for power and transmission lines. 2. Water qualityWater containing high level of foreign materials may c...
Page 10 - -2 Before starting a test run
5 English 5. Carry out complete cooling/thermal insulation of water piping and outdoor dehumidification. If complete cooling or thermal insula-tion has not been carried out, any damage may be caused during severe winter due to freezing, in addition to thermal loss. 6. When you stop operation during ...
Page 11 - FIELD WIRING; -2 Power circuit and cable requirements
English 6 2. Because the plate type heat exchanger has a structure which does not permit disassembling and cleaning, follow the following procedures for cleaning: 1) For maintenance purposes it is required to provide for a con- nection port on the water inlet and on the water outlet. You must connec...
Page 12 - How to the centralized interlock wiring
7 English 8-4 Examples System example (Refer to figure 8) 1. Field power supply 2. Main switch 3. Earth leak detector 4. Fuse 5. Cool/heat selector 6. Remote controller 7. Outside unit 8. BS unit 9. Indoor unit power supply wiring (sheathed cable) transmission wiring (sheathed cable) Caution • Use a...
Page 13 - -5 In case of a local setting
English 8 • The wiring to the indoor units must be connected to the F1/F2 (To IN/D UNIT) terminals on the PC board in the outside unit. Field line connection: Power supply wiring and transmission wiring Make sure to connect the power wire to the power terminal block and fix it using attached clamp a...
Page 14 - REFRIGERANT PIPING; -1 Selection of piping material; pipe size
9 English 9. REFRIGERANT PIPING Caution After completing installation, be sure to open the valve. (See 9-9 Additional refrigerant charge for details) (Operating the unit with the valve shut will break the compressor.)Use R410A to add refrigerant. All field piping must be installed by a licensed refr...
Page 15 - -4 Connecting the refrigerant piping; No trap has been installed in the gas piping.
English 10 Not recommendable but in case of emergency You must use a torque wrench but if you are obliged to install the unit without a torque wrench, you may follow the installation method men-tioned below. After the work is finished, make sure to check that there is no gas leak. When you keep on t...
Page 16 - -5 Example of connection
11 English 9-5 Example of connection ∗ Below table is mentioned about the case of heat recovery sytem (3-piping: suction gas, HP/LP gas and liquid pipes). In case of heat pump system (2-piping: gas and liquid pipes), select the pipe size from suction gas pipe for gas pipes and from liquid gas pipe f...
Page 17 - Outside unit
English 12 Required Conditions Example Dr a wings 1. It is necessar y to increase the liquid and suction gas pipe siz e betw een the first br anch kit and the final br anch kit. (Reducers m ust be procured on site) Ho w ev e r, the pipes that are same pipe siz e with main pipe m ust not be increased...
Page 18 - -6 Air tight test and vacuum drying; Charge with the tank upright.
13 English 9-6 Air tight test and vacuum drying The units were checked for leaks by the manufacturer.Confirm that the valves are firmly closed before Air tight test or vac-uum drying.To prevent entry of any impurities and insure sufficient pressure resistance, always use the special tools dedicated ...
Page 19 - -10 Shutoff valve operation procedure; CHECKS AFTER INSTALLATION; 1-2 Before turn on the power supply
English 14 Additional refrigerant charge procedure (2)-by Additional refrig-erant charge operation About the system settings for additional refrigerant charge operation, refer to the [Service Precaution] label attached on the electric box cover in the outside unit. 1. Fully open all shutoff valves (...
Page 20 - Cautions for check operation; 1-4 Check of normal operation
15 English (Refer to figure 27) 1. Electrical box 2. Cover of electrical box 3. Cover for servicing 4. Inspection cover 5. Points to be noted when providing services 〈 Cautions for check operation 〉 • If operated within about 12 minutes after power supply has been applied to the indoor unit and outs...
Page 21 - CAUTION FOR REFRIGERANT LEAKS; (Points to note in connection with refrigerant leaks)
English 16 12. CAUTION FOR REFRIGERANT LEAKS (Points to note in connection with refrigerant leaks) Introduction The installer and system specialist shall secure safety against leakage according to local regulations or standards. The follow-ing standards may be applicable if local regulations are not...