Page 3 - figure 8
[5] [6] [7] [8] L L L L H H H H A A A 20 or more 20 or more 20 or more 4 or more 40 or more 40 or more 60 or more 40 or more 40 or more L > H (in.) figure 8 [1] [2] Z Z 40 or more 12 or more 4 4 (in.) [1] [2] 40 or more 80 or more 8 or more 4 or more 60 or more 24 or more 120 or more H A L (in.) ...
Page 5 - Installation manual; English; CONTENTS
RXYMQ36PVJURXYMQ48PVJU VRV III -S System air conditioner Installation manual 1 English CONTENTS 1. SAFETY CONSIDERATIONS .................................................. 12. INTRODUCTION...................................................................... 2 2-1. Combination .........................
Page 6 - INTRODUCTION
English 2 • Securely fasten the outside unit terminal cover (panel). If the terminal cover/panel is not installed properly, dust or water may enter the outside unit causing fire or electric shock. • When installing or relocating the system, keep the refrigerant circuit free from substances other tha...
Page 7 - -2 Standard operation limit; BEFORE INSTALLATION
3 English 2-1 Combination The indoor units can be installed in the following range. • Be sure to connect a dedicated indoor unit. See the catalog for indoor unit models which can be connected. • Total capacity/quantity of indoor units 〈 Outdoor unit 〉 〈 Total capacity of indoor units 〉 〈 Total quant...
Page 8 - SELECTING INSTALLATION SITE
English 4 4. SELECTING INSTALLATION SITE (1) Select an installation site where the following conditions are satisfied and that meets with your customer’s approval. • Places which are well-ventilated.• Places where the unit does not bother next-door neighbors.• A locations where small animals will no...
Page 9 - When nothing is obstructing the top; PRECAUTIONS ON INSTALLATION
5 English 2. Series installation (up to two units) (Refer to figure 8-[4]) Relation of dimensions of H, A, and L are shown in the table below. (in.) Note) 1. Get the lower part of the frame sealed so that air from the outlet does not bypass. 2. Only two units at most can be installed in series. Patt...
Page 10 - FIELD WIRING; -1 Wiring connection example for whole system; Ground wire
English 6 6. FIELD WIRING CAUTION To the electrician • Do not operate until refrigerant piping work is completed. (If operated before complete the piping work, the compressor may be broken down.) • Be sure to install a ground fault circuit interrupter. (This unit uses an inverter, so install the gro...
Page 11 - -3 How to connect the power supply wiring; PRECAUTIONS ON REFRIGERANT PIPING; -1 Installation tools; Insulating sleeve
7 English <Precautions when laying power wiring> • Wiring of different thicknesses cannot be connected to the power ter- minal block. (Slack in the power wiring may cause abnormal heat.) • Use sleeve-insulated round pressure terminals for connections to the power terminal block. When none are ...
Page 12 - -2 Selecting piping material
English 8 Vacuum pump • Use extreme caution to prevent pump oil from flowing backwards through the system when the pump is stopped. • Use a vacuum pump which can evacuate to –14.6PSI. 7-2 Selecting piping material • Use pipes that have no contaminants adhered to their inner surfaces (such as sulfur,...
Page 13 - Precautions for connecting pipes; -6 Heat insulation of piping; CAUTION
9 English • If a torque wrench is not available, there is a place where the tight- ening torque will suddenly increase if a normal wrench is used to tighten the flare nut.From that position, further tighten the flare nut the angle shown below. • After all the piping has been connected, use nitrogen ...
Page 14 - -7 Example of connection; Example of connection; (Connection of 8 indoor units; Branch with refnet joint
English 10 7-7 Example of connection Example of connection (Connection of 8 indoor units Heat pump system) Branch with refnet joint Branch with refnet joint and refnet header Branch with refnet header ab c d e f g hi j k l m n 12 34 56 7 8 H2 H1 p Outdoor unit REFNET joint (A-G) Indoor units (1-8) H...
Page 15 - -8 Air tight test and vacuum drying
11 English 7-8 Air tight test and vacuum drying After doing the piping, perform the following inspections. Be sure to use nitrogen gas. (See the figure (“Shutoff valve operation procedure”) for the location of the service port.) [Procedure]Pressurize from the liquid pipes and gas pipes to 550PSI (an...
Page 16 - ADDITIONAL REFRIGERANT CHARGE; -1 Before adding refrigerant; Tank with siphon pipe; Filling after calculating the amount of refrigerant to add
English 12 8. ADDITIONAL REFRIGERANT CHARGE WARNING • When leaving the unit with the power on, be sure to switch with another person doing the installation or close the front panel. 8-1 Before adding refrigerant • Make sure the following work and inspection is complete, in accor- dance with the inst...
Page 17 - 0-1 Power On–Check Operation; 0-2 Temperature control operation checklist;
13 English • During the operation, monitor the outdoor unit operation status and check for any incorrect wiring. <Precautions During Check Operation> • If operation is performed within 12 minutes of the indoor and outdoor units being turned on, H2P will light up, and the com-pressor will not r...
Page 18 - CAUTION FOR REFRIGERANT LEAKS; Direction of the refrigerant flow
English 14 [Remote controller displays malfunction code](Check on a remote controller connected to the indoor unit.) • When using a central controller, see the installation manual or ser- vice manual which came with the central controller. [If nothing is displayed on the remote controller] • There m...
Page 19 - NOTES; Opening between rooms
15 English B. Where there is a room division but there is an opening between the rooms sufficiently large to permit a free flow of airback and forth. (Where there is an opening without a door or where there are open-ings above and below the door which are each equivalent in size to0.15% or more of t...