Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 1 Contents System Overview ............................................................................ 4 1. About the iTM (intelligent Touch Manager) ...................................................... 4 1-1 System Configuration ....
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 4 1. About the iTM (intelligent Touch Manager) 1-1 System Configuration iTM iTM plus adaptor iTM plus adaptor iTM plus adaptor iTM plus adaptor iTM plus adaptor iTM plus adaptor USB memory Di/Pi port RS485 (Expansion adapter port) Di/...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 5 2. Engineering 2-1 Engineering Workflow Various engineering works are necessary for using the iTM. Engineering works can be roughly divided into those carried out at the office in advance and those carried out on site after installa...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 7 2-2 Logging into Service Mode To run engineering, you must log into the Service (SE) Mode from the Menu List screen. In the SE Mode, the Service Settings tab, which is normally hidden, is displayed on the Menu List. Also, special bu...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 8 Furthermore, if the screen is locked, entering the service password instead of the administrator password after carrying out the special operation indicated below, allows you to unlock the screen and log into the SE Mode. (1) (4) (2...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 9 3. Detailed Screen Description 3-1 Setup Screen Structure Service Settings Tab A/C Auto Regist Mgmt. Point Data Regist Other Setting DIII-NET Engineering Time Zone Changeover Option History Mgmt. (Delete) Pre-engineering Upgrade Bac...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 10 3-2 Service Settings Tab (1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12) (13) The button of an optional function is hidden unless the option is enabled. NOTE (1) A/C Auto Regist Automatically registers as management points those...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 11 (4) Dealer Option Enables/Disables dealer options. (5) Time Zone Sets up the difference between the Universal Time Coordinated (UTC) and local time. (6) History Mgmt. (Delete) Deletes history records of a specified period from the ...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 12 3-3 System Settings Tab (2) (1) (3) (1) Network Sets up the network IP addresses as well as the Web Servers. (2) Web Access Users Sets up Web users for Web Remote Management. (3) Backup Allows you to export the system file and setu...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 14 The following describes the operating procedure. Registering a management point with the iTM unit 1. Automatically recognizing air conditioners Automatically recognize air conditioners. The iTM unit will search for any D3 units tha...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 15 For management points whose Detailed Type is unknown, you can select the management point and display the Management Point Types screen by touching the Detailed Type button (4) . (5) Using the radio buttons (5) , select the managem...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 16 Touch the OK button to register the management point (8) and return to the main Mgmt. Point Data Register screen. The Add and Add ALL buttons are grayed out when the upper limit of registration has been reached and thus no more man...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 17 Select the management point type to register from Indoor, Outdoor, Ventilator, Di, and Pi. To select another type, select the Others radio button and touch the Select button. The Management Point Types screen for other types appear...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 18 When finished with all the tabs, touch the OK button to save the settings and return to the main Mgmt. Point Data Register screen. 4. Deleting/Editing/Copying a management point (13) (10) (11) (12) Touching the Delete button (10) d...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 19 5. Checking the setting results Touching the Check button (13) checks the content of the current settings data and displays the check results on the Information check screen. If an error is found, discards the edited content retain...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 20 6. Restarting iTM Restart iTM to reflect the settings. (14) When finished, touch the OK button (14) . A settings data check is carr ied out and the Information check screen displayed if errors are found. If no problems are found, t...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 21 Detailed Mgmt. Point Attributes screen and button descriptions The following describes the Mng. Point Attributes screen in detail. Tabs and items displayed on the Mng. Point Attributes screen vary depending on the selected manageme...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 22 <Internal Pi> (15) (16) (17) (18) (19) (20) (15) Port No. text field, Address combo box Sets up the port number and address to which the management point belongs. For the port number, touch the Modify button and enter it in t...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 23 The range of values you can enter/set is as indicated in the table below. Detailed Type Port number Address View Minimum/Maximum value (Default value) View Minimum/Maximum value (Default value) Non-differentiated Di/Pi 1 to 8 (1)* ...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 24 • Common 2 Tab Sets up common items 2 for a management point. Displayed items vary depending on the management point type. <Outdoor> <Indoor> (22) (22) (21) <Internal Pi> <D3Chiller, D3Dio, External Dio> (22...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 25 • Monitoring Tab Sets up the monitoring item. Select either of the communication error monitoring levels: Monitor or Monitor + History by using the radio button. • Ventilator Tab Sets up the Ventilator. (23) (24) (25) (23) Ventilat...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 27 (31) Post-Priority radio button Select whether to allow Start/Stop from the equipment from Enable and Disable. (32) Error output holding radio button Select whether to block the control signal when an error is detected from Enable ...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 28 (38) Power Ratio text field Sets up the power ratio. Touch the Modify button and enter the value in the Numerical Input dialog that appears. You can enter a value in the 0.01 to 99999.99 range, in increments of 0.01. For the Intern...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 29 • Analog Tab Sets up the analog value. Displayed items vary depending on the management point type. <External Ai> Analog 1 Analog 2 Analog 1 Analog 2 <External Ai> <Internal Ai> <Internal Ai> (41) (42) (43) ...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 30 (44) Upper Limit field Sets up the upper limit and monitoring status for upper limit error monitoring. For the upper limit, touch the Modify button and enter it in the Numerical Input dialog that appears. For the monitoring status,...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 31 Acceptable range for each numeric value Detailed Type Classification Item For Celsius For Fahrenheit For analog value Minimum/ Maximum value (Default value) Increment Minimum/ Maximum value (Default value) Increment Minimum/ Maximu...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 32 • Analog Point Selection Screen Sets up the reference for the Internal Ai. Touch the Ref.. button on the Analog2 tab to display the Analog Point Selection screen. (49) (50) (49) is the list of management points with analog value. (...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 33 Registering management points using a CSV file 1. Outputting a CSV file The current settings data can be output to a CSV file for editing the management point data using a computer software or the Pre-engineering tool. The CSV file...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 34 2. Loading a CSV file Load the edited CSV file. The edited data does not overwrite everything, it only merges the difference to the current settings data. Log into SE Mode from the Menu List screen and display the Service Settings ...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 35 If the setting data has been loaded without any problem, the merge results appear. The Display Merge Results screen consists of the tabs: Add, Modify, Modification Failed, and No change. After checking the list on each tab, touch t...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 36 3. CSV file format The format of the CSV file output from the iTM is as shown below. A CSV file output when no management point data is registered can be used as a template for new implementations since only the area used by the sy...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 38 • Symbols (decimal point, digit group separator, etc) used in Windows may vary depending on the locale. Be sure to check before editing a file. • Pi pulse value at the time of saving the CSV file is output with an invalid, out of t...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 39 3. Enable/Disable dry operation mode in Dry Operation Mode (2) . When enabled, allows you to set Dry mode from the touch panel, or the Schedule or Interlocking function. Touch the OK button to commit and close the screen. 4-3 DIII-...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 40 4. (3) is a list of Connector Plugs for each iTM port. (4) is a list of central units recognized on the port selected in (3) , where its name is displayed along with its Main/Sub setting. Central units that can be installed togethe...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 41 4-4 Time Zone Sets up the difference between the Universal Time Coordinated (UTC) and local time. 1. Log into SE Mode from the Menu List screen and display the Service Settings tab (see page 7). Touch the Time Zone button on the Se...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 42 2. (1) is an air conditioner list displaying all Group Addresses. When no management points are registered, columns other than Group Addr. are displayed blank. The displayed contents are as indicated in the table below. Column Disp...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 43 4-6 History Mgmt. (Delete) Deletes history records. 1. Log into SE Mode from the Menu List screen and display the Service Settings tab (see page 7). Touch the History Mgmt. button on the Service Settings tab to display the History ...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 44 4-7 Pre-engineering Pre-engineering is carried out to lessen the work to be carried out on site, such as when installing iTM in a large new property, modifying settings due to a large-scale equipment renovation, or making extensive...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 45 Relationship between the assumed scenario and functions Function Scenario Pre-engineering tool (2) Property data selection (3) Property data edit (4) Property data output (3)-1 Data edit (3)-2 Layout View edit Restore data output L...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 46 Download the pre-engineering tool from the Distributor’s Page. To use the pre-engineering tool, a separate PC is necessary. The requirements for the PC are as indicated in the table below. PC requirement for running the pre-enginee...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 47 (1) 2. On the login screen that appears, enter the password and click the Login button (1) . The iTM Pre-engineering tool main screen appears if the correct password has been provided. Main screen
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 48 Scenario 1: Installation to new property Set up data for the new property in advance. (2) Main screen 1. Click the New button (2) to display the Create New Folder dialog. (3) (4) (5) Create New Folder dialog 2. Select the location ...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 49 Clicking the OK button on the confirmation dialog box deletes all folders and files within the folder. NOTE (6) Main screen 3. Click the Edit Data button (6) to start up the iTM demo version for PC. (7) Screen of demo version for P...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 52 Scenario 2: Maintenance of existing property (When carrying out pre-engineering using the current setting) When extensively modifying an existing property due to equipment renovation and the like, the current settings for the exist...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 53 4. Click the Edit Data button (13) to start up the iTM demo version for PC. The steps from editing using the demo version for PC to restore data output to USB and iTM restore are the same as steps 3 to 5 of the procedure for Scenar...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 54 Scenario 3: Restore with existing property’s backup data When iTM in an existing proper ty is replaced due to malfunction and the like, the system is recovered by restoring the backup data (folder name: Backup_MAC address_year mont...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 55 Scenario 4: Implementation of new functions due to existing property’s upgrade When implementing new functions to an existing property, the upgraded Pre-engineering tool is used to create the functions’ settings data. 1. Back up th...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 56 4-9 Backup When modifying settings data due to equipment renovation in an existing property or upgrade, the iTM unit data must be backed up to a USB memory as history and settings data reference for troubleshooting and the like. Da...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 57 2. Inser t a USB memor y into iTM. Touching the Backup button (1) displays a backup star t confirmation dialog. 3. Touch the Yes button. A USB memory content deletion confirmation dialog appears. 4. Touching the Yes button displays...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 58 4-10 Installation Data installation to the iTM unit includes installation of upgrade data and pre-engineered data (See 4-7 Pre-engineering). The installation procedure is the same in all cases. The following describes the operating...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 60 If there is no flaw in the information, touching the OK button on the installation tool screen starts the installation. When installation is complete, an information dialog appears. Remove the USB memory and touch the Close button ...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 62 4-12 Setting outdoor unit Set the type of the outdoor unit registered as a Mgmt. point. 1. Log into SE Mode from the Menu List screen and display the Service Settings tab (see page 7). Touch the Outdoor Setup button on the Service ...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 63 Precautions when using DIII-NET EXPANDER ADAPTER In the application using the DIII-NET EXPANDER ADAPTER, if you monitor the outdoor units or use Internal Pi or such other functions processed based on information from the outdoor un...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 69 4-13 Leakage Check Leakage Check is a function available in VRV III or later outdoor units. It checks refrigeration systems for leakage. Leakage Check can be carried our centrally for multiple refrigeration systems installed in a p...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 70 Leakage Check functions Category Function Description Usage scene As Web function Reference page Schedule Manual Setup Registration of Indoor Unit Registers applicable indoor units to place them under maintenance when the outdoor u...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 71 Touch the Outdoor Setup button on the Service Settings tab to display the Outdoor Setup screen (see page 10). (1) (2) 2. (1) is a list of outdoor units registered in iTM. The Charge item displays the current Refrigerant Charging Op...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 72 4. (3) is the Registered Indoor Unit list. (4) is the Unregistered Indoor Unit list. Select the indoor unit you want to register and touch the Add button to register. To unregister, select the indoor unit from (3) and touch the Rem...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 73 2. The management point name of the target outdoor unit appears in the Name field (7) . You may set up to four schedule programs per outdoor unit. Enable/disable the schedule program in (8) . Set up the Leakage Check start date in ...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 74 Copying a schedule program 1. You may set the same program set up in the Schedule Setup screen to another outdoor unit. (11) Touch the Schedule Copy button (11) to display the Copy screen. (12) (13) (14) 2. The name of the outdoor ...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 75 Starting Leakage Check by manual operation Start Leakage Check by manual operation. (15) (16) 1. Select the target outdoor unit from the Outdoor Unit list (15) and touch the Check Start button (16) . A confirmation dialog appears. ...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 76 Executing a Leakage Check places the outdoor unit and indoor units registered in the same refrigeration system under “Maintenance”. “Maintenance” is released upon Leakage Check completion (If the iTM is stopped when the Leakage Che...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 77 Outputting the Leakage Check results to a CSV file Output the Leakage Check results to a CSV file. (19) (20) 1. Insert a USB memory into the iTM and touch the CSV Output button (20) . A confirmation dialog appears. Touching the Yes...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 79 Conflict with other controls The following describes the operation when another control comes into conflict with the Leakage Check. : Enabled ×: Disabled Target management point Other control Leakage Check Mgmt. point status/Other ...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 80 • Inform the user that all units are forced to operate in the cooling mode during leakage check. • Caution the user not to change the time setting of iTM during leakage check. • Power consumed by the indoor unit during leakage chec...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 81 Failure mode The following describes the failure modes of the Leakage Check. Scene Failure mode Impact to users Cause Handling Notification method Recovery method When How Preparation Forget to run Refrigerant Charging Operation Ca...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 84 Optional Functions 5. Service Settings 5-1 Activation In addition to standard functions, iTM provides various optional functions suited to users’ needs. There are two types of optional functions: optional maker functions sold by Da...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 85 (1) (2) (3) 2. The MAC address of the iTM unit appears in MAC Address (1) . (2) is a list of currently enabled optional maker functions. 3. To enable a new optional maker function, touch the Add button (3) . Enter the Activation ke...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 86 5-2 Dealer Option Setup The following describes the procedure to enable dealer options. 1. Log into SE Mode from the Menu List screen and display the Service Settings tab (see page 7). Touch the Dealer Option Switch button on the S...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 87 Operating Optional Functions 6. System Settings 6-1 Network iTM allows you to operate it remotely via the Internet, or receive notification via E-mail in the case of an error. To use these functions, you must set up the network on ...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 88 2. The current settings are displayed. Touch the Modify button to modify the settings in the Input dialog that appears. For infor mation necessar y for the settings, consult your networ k administrator. (1) Controller name (2) Host...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 89 (9)(10) Select (9) to use the default port 80. Selecting (10) displays the port number 8080. Touching the Modify button allows you to modify the settings in the Numerical Input dialog that appears. Touch the OK button to save and c...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 90 6-2 Web Remote Management The iTM can be remotely operated via the Internet or local network. Ethernet (100Base-T or higher) PC (Web browser) PC (Web browser) Internet iTM Firewall For settings necessary on the iTM unit, see “6-1 N...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 91 Connecting the PC and iTM Connect the PC and iTM unit into a network using an Ethernet cable. Ethernet cables use for connecting networks come in two types: straight and cross. Connect the PC and iTM unit by referring to the connec...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 92 Checking the Web browser and Flash Player versions 1. Start up the Web browser (Internet Explorer) and select [About] from the [Help] menu. In the case of Firefox, you can check by selecting [Help] → [About Mozilla Firefox]. NOTE C...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 97 Setting up the IP address (Windows Vista Business) 1. Select [Start] → [Control Panel]. 2. Click [Network and Internet]. 3. Click [Network and Sharing Center].
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 100 8. To connect to the iTM via the Internet, ask its IP address and subnet mask to your network administrator and set them up. Set them up as follows when connecting to the iTM via local network. IP address: 192.168.0.2 Subnet mask:...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 101 Setting up the IP address (Windows 7 Professional) 1. Select [Start] → [Control Panel]. 2. Click [Network and Internet]. 3. Click [Network and Sharing Center].
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 104 Set them up as follows when connecting to the iTM via local network. IP address: 192.168.0.2 Subnet mask: 255.255.255.0 For iTM settings at the time of shipment, see page 96. NOTE 8. Check that the settings are correct and click [...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 105 (1) (2) (3) (4) (5) Network Connection Check Check whether the Ethernet connection between a PC and iTM is normal. Carry out the following procedure from the PC. <Windows XP> <Windows VISTA, Windows 7>
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 106 1. From the Start menu of the PC, select “All Programs” → “Accessories” → “Command Prompt”. Alternatively, select “Run” from the Start menu of the PC, enter “cmd” in Open and click the OK button. (Windows XP)
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 108 3. If Lost=0(0% loss) is displayed, the Ethernet connection between the PC and the iTM unit is normal. If Lost=4(100% loss) is displayed, then the PC could not recognize the iTM unit. Check the settings. When a port number is set ...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 109 iTM integrator Explanation 7. iTM integrator 7-1 Basic Setup If you are sure that all connections have been made, proceed to the basic setup of the iTM integrator. Here, “basic setup” means setting up the iTM integrator in prepara...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 110 Select Basic software and enter the MAC address, Software ID, and User information of the iTM integrator you want to install. Write down the activation key that appears on the screen. 3. Powering on data backup battery To retain t...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 111 5. Setting up display language Set up the display language used throughout the iTM integrator setup screens. <Language Settings screen> 1. Touch the desired language from those listed on the screen. The radio button next to ...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 112 6. Setting up locale “Locale setup” allows to set up how you want to see items that are expressed in different ways depending on the region, such as the data/time, temperature, and decimal point, on the display. <Locale Setting...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 113 7. Setting time zone Set up the local standard time zone you want to use for the system clock. <Time Zone Settings screen> 1. On the Time Zone Settings screen, select the time zone of your region from the Time Zone combo box...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 114 7-2 iTM integrator Service Settings Set up the iTM integrator unit. iTM integrator USB port USB memory Power (100 240V) LAN port Web Remote Management Router Web Remote Management HUB 100Base-TX compliant iTM iTM iTM iTM iTM Indiv...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 115 Service Settings Tab (Menu List Screen) Displayed when you log into Service Mode from the iTM integrator Menu List screen. The procedure to log into Service Mode is the same as that for the iTM. See “2-2 Logging into Service Mode”...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 116 Controller Access Setup Set up the connection between the iTM to be controlled and the iTM integrator. 1. Display the Service Settings tab on the iTM integrator Menu List screen. (1) 2. Touch the Controller Access button (1) to di...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 119 6. When finished, touch the OK button to close the screen. If there is an iTM whose connection status is “Disconnected”, the following Confirm dialog appears. To exit setup leaving the iTM disconnected, touch the Yes button. To re...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 120 Appendix 8. Useful Information 8-1 Troubleshooting Troubleshooting table Problem Checking method Cause Measure Remote operation Cannot remotely operate iTM from the PC. When iTM and PC are connected via hub, check whether they are...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 122 9. Hardware Specifications 9-1 iTM Hardware Specification 243mm 207mm 290mm 256.6mm Power AC100 - 240 V 50/60 Hz Power consumption 23 W Emergency stop input Always “a” contact Contact current approximately 10 mA Size 290 × 243 × 5...
Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 123 Peripheral Equipment Specification Function Requirement PC for Web Remote Management PC for pre-engineering tool OS: Windows XP Professional SP3 (32 bit) Windows Vista Business SP2 (32 bit) Windows 7 Professional SP1 (32 bit, 64bi...
Daikin Manuals
-
Daikin 3MXS68G2V1B
Installation Manual
-
Daikin 3P207257-3
Installation Manual
-
Daikin 4MKS75F2V1B
User Manual
-
Daikin 2AMX50G3V1B
Installation Manual
-
Daikin ACEF 3AV1-(C)(H)
User Manual
-
Daikin ACEF 3AVE
User Manual
-
Daikin ACEF 4AV1-(C)(H)
User Manual
-
Daikin 4MXS68F2V1B
User Manual
-
Daikin AGZ 130D
Installation Manual
-
Daikin AGZ 140D
User Manual
-
Daikin AH123E35AX
User Manual
-
Daikin AGZ030EH
Installation Manual
-
Daikin AGZ 040D
Installation Manual
-
Daikin Altherma HT
Installation Manual
-
Daikin AKZJ8Series
User Manual
-
Daikin Altherma Large Monobloc
User Manual
-
Daikin ARC423A17
User Manual
-
Daikin ARC433B46
User Manual
-
Daikin ARC433B47
User Manual
-
Daikin Altherma LT
User Manual