Daikin MT 180- Manuals
Daikin MT 180– Installation Manual in PDF format online.
Manuals:
Installation Manual Daikin MT 180
Summary
2 IM 1152 Table of Contents Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Operating Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Receiving and Storage . . . . ...
IM 1152 3 Introduction Daikin Thinline ™ Horizontal Fan Coils are intended for use in single zone applications. They are available in sizes from 200 to 1200 cfm. Figure 2 describes the main features of these units and can be referred to for component placement. These units are available in two-pipe ...
4 IM 1152 Introduction Safety Follow all safety codes. Wear safety glasses and work gloves. Use a quenching cloth for brazing operations. Have a fi re extinguisher available. Follow all warnings and cautions in these instructions and attached to the unit. Consult applicable local building codes and ...
IM 1152 5 Introduction Pre-Installation Notes Installation and maintenance are to be performed only by qualifi ed personnel who are familiar with and in compliance with state, local and national codes and regulations, and experienced with this type of equipment. Before beginning installation, please...
6 IM 1152 Installation Installation Uncrating and Inspecting the Unit 1. Carefully remove the packaging, remaining alert to any signs of shipping damage. Be careful not to discardcomponents that may be included with the packaging. 2. If the unit is damaged, fi le a claim with the carrier. Notify the...
IM 1152 7 Installation Recommended Maintenance Clearance Cabinet units have removable bottom and side panels for easy access to components for service and maintenance. The fan assembly and main drain pan are easily removable from the bottom for cleaning. See Accessing/Removing the Main Fan Deck and ...
8 IM 1152 Installation Piping Connection Recommendations General Guidelines • Piping can be steel, copper or PVC, but must comply with local codes. • Proper ventilation is required for soldering. When soldering, use a quenching cloth to protect fan coil components from overheating damage—melting ins...
IM 1152 9 Installation Drain Piping • Condensate piping can be steel, copper, or PVC. A means of disconnection must be furnished to facilitate fan deck removal. • No point of the drain system may be above the drain pan of any unit. • Pipe insulation is recommended to avoid condensation. • Suggested ...
10 IM 1152 Installation If the unit does not have a factory-installed valve & piping package, the changeover switch or sensor can be ordered for fi eld installation. The installer should attach the sensor or auto changeover switch parallel to and in direct contact with the supply water pipe. NOT...
IM 1152 11 Installation Two-pipe systems with electric heat The electric heating coil is designed to be the total source of heat for the unit. If used for auxiliary intermediate season heating, additional control is required. A second changeover switch is required. For units ordered with intermediat...
12 IM 1152 Installation Electrical Data The wiring diagram for the unit is attached to the exterior of the blower housing. See Figure 10 . Be sure the available power is the same voltage and phase as that shown on the unit data plate. See Figure 3, for the location of the data plate. See page 40 thr...
IM 1152 13 Accessories Condensate Overfl ow Detection Device The condensate overfl ow detection device is a factory-installed option on fan coils. This device has a condensate overfl ow fl oater with dry contacts and is connected to the LV interface or MicroTech board. See Figure 12 . If you suspect...
14 IM 1152 Initial Start Up Initial Start Up Cleaning & Flushing the Water System • Prior to fi rst operation of any unit, clean and fl ush the water circulating system of all construction dirt anddebris. • If units are equipped with water shutoff valves, either electric or pressure operated, co...
IM 1152 15 Initial Start Up Equipment Start Up Check List Receiving and Inspection □ Unit received undamaged □ Unit received complete as ordered □ Parts for fi eld installation received as ordered □ Unit arrangement/hand correct □ Unit structural support complete and correct Handling and Installatio...
16 IM 1152 Initial Start Up General Maintenance Normal maintenance on all units is generally limited to fi lter changes and cleaning the condensate drain pans. Units are provided with permanently lubricated motors and require no oiling even though oil caps may be provided. Record performance measure...
IM 1152 17 Initial Start Up Electric Resistance Heater Assembly Electric resistance heaters typically require no periodic maintenance when the unit’s air fi lters are changed properly. Other conditions and equipment in the system may affect the operation and service life of the heaters. The most imp...
18 IM 1152 Maintenance Blower Dirt and dust should not be allowed to accumulate on the blower wheels or housing (see typical, Figure 21) . Excessive debris can result in an unbalanced blower wheel condition which can damage the wheel and/or motor. The wheel and housing should be cleaned periodically...
IM 1152 19 Maintenance Replacement Parts Factory replacement parts should be used wherever possible to maintain the unit’s performance, service life, operating characteristics and testing agency listings. Replacement parts may be purchased through a local Daikin sales representative. Contact your lo...
20 IM 1152 Controls and Thermostats Controls and Thermostats Controls A wide variety of control options are available for Daikin ThinLine Horizontal Fan Coils, both unit-mounted and remote-mounted. This section provides a brief overview of these options and their operation. For more complete informa...
IM 1152 21 Controls and Thermostats MT155 Thermostat For more details refer to page 50. The MT155 series thermostat provides on-off control for low-voltage or line-voltage valves and fan motors. This thermostat is designed as a remote-mount with connection to the LV interface board mounted on the fa...
22 IM 1152 Controls and Thermostats Digital Thermostats Daikin offers a broad range of remote, wall-mounted digital thermostats with the capability to control On-Off, 3-wire and proportional modulating valves and Normally-Closed or Normally-Open actuator valves. For more information, refer to Daikin...
IM 1152 23 Controls and Thermostats T180 Programmable Thermostat Daikin offers two different 7-Day Programmable Digital Heating/Cooling Thermostat with constant fan or Fan cycled, On/Off Valve Control depending on the fan speed control. The thermostat interface contains buttons for use in navigation...
24 IM 1152 Controls and Thermostats Sensors Room Temperature Sensor with Setpoint Adjustable Module and Fan Speed Control The Digitally Adjustable sensor provides the ultimate of temperature control and display, simple user interface, alarm annunciation, and alarm reset. The easy to ready LCD clearl...
IM 1152 25 Controls and Thermostats 8. Connect stripped, labeled wires to matching terminals on the temperature sensor. Refer to Figure 29 for wiring details. 9. Tighten screws on terminal connections. Gently tug wire to check for secure connections. Confi rm that eachwire is connected to the proper...
26 IM 1152 Physical Data Unit Data Table 1: Physical Data: Coils, Fans, Motors and Filters Shipping Weights Table 2: Approximate Shipping Weights - lbs (kg)* Unit Type Unit Size S02 S03 S04 S06 S08 S10 S12 FCHC/FCHR 125 (57) 127 (58) 142 (64) 160 (73) 174 (79) 210 (95) 225 (102) FCHH 30 (14) 33 (15)...
IM 1152 27 Physical Data Unit Dimensions Figure 31: Dimensions – Hideaway Fan Coil, Front Discharge – Free Return Dimension S02 S03 S04 S06 S08 S10 S12 inch (mm) inch (mm) inch (mm) inch (mm) inch (mm) inch (mm) inch (mm) Overall Unit Width A 28.48 (723) 28.48 (723) 33.98 (863) 44.98 (1142) 50.48 (1...
34 IM 1152 Physical Data Figure 38: Dimensions – Recessed Cabinet Fan Coil with Ceiling Plate Figure 39: Dimensions – Trim Flange Mount Unit Cabinet Unit Cabinet 39.34 30.34 4.5 7.0 7.0 2.0 typ. 2.0 typ. Y X 3.0 Floating Ceiling Panel 14.5" min. 16.0" max. Bottom View Side View Detail A Plat...
IM 1152 35 Valve and Piping Packages Factory-Installed Valve and Piping Packages Factory valve and piping packages are available for both two-pipe and four-pipe systems with either right or left hand connections. Four-pipe systems can be confi gured with the heating and cooling connections on the sa...
36 IM 1152 Valve and Piping Packages Enhanced Packages Enhanced valve and piping packages add a strainer to the Basic package supply water pipe. The strainer is attached to the supply water pipe at the coil connections. The strainer body is cast brass construction with a stainless steel mesh that is...
IM 1152 37 Valve and Piping Packages Control Valve Options Except for Shut-off Only packages, all valve and piping packages include control valves for controlling water fl ow. All Daikin control valves are factory assembled and mounted in the supply water pipe downstream of the coil. Several options...
38 IM 1152 Valve and Piping Packages Figure 47: Factory-installed Valve & Piping Packages (right-hand shown) REFERENCE POINT ○ × ○ × REFERENCE POINT B A 4.43 5.5 3.42 5.38 Primary Return Primary Return Primary Supply Primary Supply 20.25 7.0 0.50 ‡ 1.5 † 10.42 10.8 10.58 † † Overflow Connection ...
IM 1152 39 Valve and Piping Packages REFERENCE POINT ○ × ○ × REFERENCE POINT ○ × REFERENCE POINT B A 4.4 5.5 3.42 Primary Return Primary Supply 5.38 Primary Return Primary Supply C D X 7.9 K Secondary Supply SecondaryReturn Secondary Supply SecondaryReturn 7.7 10.35 20.25 7.0 0.50 ‡ 1.5 † 10.8 † Ove...
40 IM 1152 Wiring Diagram Figure 48: Fan Coil Wiring Diagram – Typical Low Voltage Interface Board and ECM
IM 1152 45 Model Number Description Model Number Description: Fields 1—21 Field 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 Code FC HC 1 02 A A G M Y YY W 3 12 R F T YY 12 Y Y N 1. Unit Type • FC = fan coil • FH = cabinet unit heater 2. Product Identifi er • HC = horizontal, exposed • HH =...
46 IM 1152 Model Number Description Table 3: Model Number Description: Fields 22—41 Field 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 Code YY W1 12 R F T Y 000 Y P PSC S 3 Q Y MR Y D Y R 22. Not currently used • YY = none 23. Reheat Coil Type • W1 = water standard capacity • W2 = wat...
IM 1152 47 Model Number Description Table 4: Model Number Description: Fields 42—56 Field 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 Code Y Y Y RL MOR Y 3MOU YYYY 3MOU Y Y C Y Y Y 42. Network Communication Card • Y = none 43. Changeover Type • Y = none • A = auto • M = manual • U = user selectable...
48 IM 1152 Model Number Description Table 5: Model Number Description: Fields 57—72 Field 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 Code Y Y Y Y S 18 P I 00 S 00 00 30F TA FR 1 57. Filter Status Sensor • Y = none • X = special 58. Fan Status Sensor • Y = none • X = special 59. Future Control F...
IM 1152 49 Model Number Description Table 6: Model Number Description: Fields 73—78 Figure 51: Model Number Detail — Valve Package Fields 48—50 Field 73 74 75 76 77 78 Code YYY Y A S Y 1 73. Special Options • YYY = none 74. Reserved for future use • Y = none 75. Agency Listing • A = ETL, CETL, ARI •...
IM 1014 / Page 1 of 2 © 2009 Daikin 800-432-1342 www.DaikinApplied.com Installation 1 Install the thermostat with the two furnished mounting screws to a standard 2" x 4" electrical box, 4-11/16" x 2-1/8" square device box with a 2" x 4" adapter ring or to a 4" x 4" bo...
Addendum IM 1152 — MT155 © 2009 Daikin 800-432-1342 www.DaikinApplied.com IM 1014 / Page 2 of 2 for fan continuous operation or is dependant upon connection to the fan supply input . When internally wired for fan continuous operation, the fan will be off when the system switch is off. When dependant...
Addendum IM 1152 — MT155 IM 1089 / Page 1 of 3 © 2010 Daikin 800-432-1342 www.DaikinApplied.com General InstallationPlease refer to Fig. 1, 2, 3 and 4 Two-pipe system (Cooling or Heating) To field wire a T*155 thermostat (either as wall-mounted or unit-mounted) and field-install valve package for a ...
Addendum IM 1152 — MT155 © 2010 Daikin 800-432-1342 www.DaikinApplied.com IM 1089 / Page 2 of 3 Figure 2: Low Voltage Interface Board shown with all additional support options Figure 3: Factory-installed and wired Low Voltage Interface Board (Wiring Diagram) Pipe sensor or ACO switch Condensate over...
Addendum IM 1152 — MT155 IM 1089 / Page 3 of 3 © 2010 Daikin 800-432-1342 www.DaikinApplied.com Figure 4: Thermostat TB155 autochangeover to be used with On-Off 24V valve packages, SPDT ACO and unit-mounted Low Voltage Interface Board Figure 5: Automatic changeover switch (SPDT ACO Kit P/N 039398600...
Addendum IM 1152 — MT158 IM 1015 / Page 1 of 3 © 2009 Daikin 800-432-1342 www.DaikinApplied.com Installation 1 Install the thermostat with the two furnished mounting screws to a standard 4-11/16" x 2-1/8" square device box with a 2" x 4" adapter ring. 2 For wall installations, mount ...
Addendum IM 1152 — MT158 © 2009 Daikin 800-432-1342 www.DaikinApplied.com IM 1015 / Page 2 of 3 Thermostat Operation These thermostats are designed to control On-Off, N.O. and N.C. valves, relays and Erie® three wire floating valves. These units may include a fan switch with one or more fan speed se...
Addendum IM 1152 — MT158 IM 1015 / Page 3 of 3 © 2009 Daikin 800-432-1342 www.DaikinApplied.com Figure 3: Circuit Board Jumpers Table 3: Circuit Board Jumper Configuration Application Notes 1 When no pipe sensor is used the main output controls cooling and the secondary output controls heating. 2 Th...
Addendum IM 1152 — MT158 © 2010 Daikin 800-432-1342 www.DaikinApplied.com IM1016-1 / Page 2 of 3 2 For wall installations, mount the thermostat on an inside wall approximately 5 feet above the floor. The location should provide circulation at average room temperature. Avoid direct sunlight or source...
Addendum IM 1152 — MT158 IM 1016-1/ Page 3 of 3 © 2010 Daikin 800-432-1342 www.DaikinApplied.com Application Notes 1 When no pipe sensor is used the main output controls cooling and the secondary output controls heating. 2 The pipe sensor should be mounted on the main coil input for water system ope...
Addendum IM 1152 — MT168 © 2009 Daikin 800-432-1342 www.DaikinApplied.com IM 1017 / Page 2 of 3 5 Connecting a jumper between terminals 16 and 17 will disable the secondary output and change the main output to heat mode. 6 Connection of a 24 VAC set-back signal will force the control into unoccupied...
Addendum IM 1152 — MT168 IM 1017 / Page 3 of 3 © 2009 Daikin 800-432-1342 www.DaikinApplied.com Table 3: Dip Switch Configuration Note: * On is with the dip switch handle to the right. See diagram below. Figure 3: Circuit Board Service Menu: Access: Press UP and DOWN arrows for 5 seconds. Menu Selec...
Addendum IM 1152 — MT170 © 2006 Daikin 800-432-1342 www.DaikinApplied.com US Installation and Maintenance Manual IM-846 T170 Thermostat Group: Fan Coil Part Number: 910102993 Date: July 2006 24 VAC/120–277 VAC 3-Speed Fan Control (Continuous or Cycling) or Staged Fan Control
Addendum IM 1152 — MT170 Daikin IM 846 3 Installation Instructions Installation Instructions Thermostat Model and Part Number Daikin offers two different thermostats depending on the fan speed control used (Table 2). Table 1: Thermostat model and part numbers Note – For a list of thermostat features...
Addendum IM 1152 — MT170 4 Daikin IM 846 Installation Instructions 5 On the circuit board, set the voltage selection switch (Figure 2) to the appropriate voltage for the application • 24 V = 24 VAC • 110–277 V = 120, 240, or 277 VAC . Note: The circuit board is shipped with the voltage selection swi...
Addendum IM 1152 — MT170 Daikin IM 846 5 Operation Operation Thermostat Button Operation The thermostat interface (Figure 4) contains buttons for use in navigating to accompanying menus/screens and for performing specific operations. These buttons and operations are described below. Figure 4: Thermo...
Addendum IM 1152 — MT170 6 Daikin IM 846 Operation Thermostat Menu Functions The thermostat menu contains nine functions which can be accessed using controls on the thermostat. Accessing the menu functions and details of each function are described below. Menu Function Access 1 Press and hold the UP...
Addendum IM 1152 — MT170 Daikin IM 846 7 Operation Fan Operation The thermostat may be factory configured for standard or staged fan operation. Standard Fan Configuration (TA170-001) Units with standard fan operation (Figure 8) have a selectable fan Speed button. Figure 8: Standard fan operation Sta...
Addendum IM 1152 — MT170 8 Daikin IM 846 Operation Fancoil Operation Fancoil operation is either a 2-pipe or 4-pipe configuration which is determined by jumper selection JP4 (see “Mounting and Wiring the Thermostat” on page 3). 2-Pipe Operation In this configuration, the thermostat permanently disab...
Addendum IM 1152 — MT170 Daikin IM 846 9 Optional Occupancy Detection Equipment Operation Optional Occupancy Detection Equipment Operation The T170 thermostat can be used with optional S200 series occupancy detection equipment. Purchasing and installing this equipment to compliment the thermostat ad...
Addendum IM 1152 — MT170 10 Daikin IM 846 Optional Occupancy Detection Equipment Operation SD200-001 Occupancy Sensor The SD200-001 occupancy sensor (Figure 11) serves as a master sensor for a guest room HVAC management system. The sensor provides HVAC operation according to occupancy status, as wel...
Addendum IM 1152 — MT170 Daikin IM 846 11 Optional Occupancy Detection Equipment Operation SD200-002 Occupancy Sensor The SD200-002 occupancy sensor serves as a stand alone master sensor for a guest room HVAC management system. The sensor provides HVAC operation according to occupancy status, as wel...
Addendum IM 1152 — MT180 Installation and Maintenance Manual IM 1019 Group: Fan Coil Part Number: IM 1019 Date: October 2011 © 2011 Daikin MT 180 Programmable Thermostat
Addendum IM 1152 — MT180 Daikin IM 1019 3 Installation Instructions Installation Instructions Applications and features For 2 or 4 Pipe Fan Coil and On/Off Control Applications • 7 Day, 4 Event Programmability • System Selection: Off-Heat-Cool-Auto-Setback • 6 Outputs: 1H, 1C, Up to 3 Fan, OA Damper...
Addendum IM 1152 — MT180 4 Daikin IM 1019 Installation Instructions Thermostat Model and Part Number Optional Sensors/Kits In addition to the T180 thermostat, Daikin offers optional sensors for occupancy detection ( page 14 and page 15 ) and 10K pipe sensor page 12 ) that can be ordered and used in ...
Addendum IM 1152 — MT180 Daikin IM 1019 5 Installation Instructions 5 On the circuit board, set the voltage selection switch ( Figure 3 ) to the appropriate position prior to application of power. • 24V = 24 VAC • 110-277 V = 120, 240 or 277 VAC Note: The circuit board is shipped with the voltage se...
Addendum IM 1152 — MT180 6 Daikin IM 1019 Operation Operation Front Panel Reference The thermostat interface ( Figure 5 ) contains buttons for use in navigating to accompanying menus/screens and for performing specific operations. These buttons and operations are described below. 1 Liquid Crystal Di...
Addendum IM 1152 — MT180 Daikin IM 1019 7 Operation 6 Fan Operation Indicators 7 Program Override Commands 8 Service IndicatorThe wrench symbol is displayed when there is a tempera-ture sensor error or condensate overflow error. It indi-cates there is an open or a short connection to the sensor swit...
Addendum IM 1152 — MT180 8 Daikin IM 1019 Operation System Button Operation Pressing SYSTEM will light up the five system mode options described below. Press SYSTEM to scroll through the options. As you scroll, the current option will be blinking. To select the blinking option, wait for the five-sec...
Addendum IM 1152 — MT180 Daikin IM 1019 9 Operation Setting the Clock & Day 1 Press PROGRAM once. 2 Press Ÿ or ź to scroll until “CLOCK” is blinking. To select, press PROGRAM once. 3 Press Ÿ or ź to scroll through “24Hr”, “AM”, “PM” options. “24Hr” sets your thermostat to a 24-hour clock. “AM” a...
Addendum IM 1152 — MT180 10 Daikin IM 1019 Operation Copy Feature 1 Press PROGRAM once. 2 Press Ÿ or ź to scroll until “COPY” is blinking. To select, press PROGRAM once. 3 Press Ÿ or ź to scroll to the individual day you want to copy from. “DFLT” (the default Factory Program) is also a copy option. ...
Addendum IM 1152 — MT180 Daikin IM 1019 11 Operation System Check-out To verify thermostat operation after mounting and wiring it, perform the following: 1 Energize the system. 2 Set fan to ON. Select each fan speed (TA180 Models) to verify operation. 3 Set the System button to AUTO, or available se...
Addendum IM 1152 — MT180 12 Daikin IM 1019 Technical and Application Notes Technical and Application Notes Fan Operation The thermostat may be factory configured for standard or staged fan operation. Standard Fan Operation Single setpoint represented in Figure 9 . Programming mode includes multiple ...
Addendum IM 1152 — MT180 Daikin IM 1019 13 Technical and Application Notes Time-Based Purge (Default) 1 The time-based purge cycle will start a 3-min purge cycle and enable the Main Output if any of the following conditions occur: transition from OFF to AUTO mode, Reset event, power cycle, and/or 1-...
Addendum IM 1152 — MT180 14 Daikin IM 1019 Optional Occupancy Detection Equipment Operation Optional Occupancy Detection Equipment Operation The T180 thermostat can be used with optional S200 series occupancy detection equipment. Purchasing and installing this equipment to compliment the thermostat ...
Addendum IM 1152 — MT180 Daikin IM 1019 15 Optional Occupancy Detection Equipment Operation SD200-001 Occupancy Sensor The SD200-001 occupancy sensor ( Figure 12 ) serves as a master sensor for a guest room HVAC management system. The sensor provides HVAC operation according to occupancy status, as ...
Addendum IM 1152 — MT180 16 Daikin IM 1019 Annex I Annex I Table 18: Custom Program Worksheet Day Time Period Start Time Heat Setpoint Temperature Cool Setpoint Temperature Monday Wake Day Evening Sleep Tuesday Wake Day Evening Sleep Wednesday Wake Day Evening Sleep Thursday Wake Day Evening Sleep F...
Addendum IM 1152 — MT180 Daikin IM 1019 17 Annex II Annex II Table 19: Service Menu Table Menu Feature Range Description / Comments 1 F° or C° 0- Celsius 1- Fahrenheit (Default) Determines temperature displays in Fahrenheit or Celsius 3 Fan Off Delay 0-99 Seconds (0- Default) The amount of time (in ...
Addendum IM 1152 — Digitally Adjustable Display Sensor Installation & Maintenance Data Group: WSHP/FCU Part Number: 910139264 Date: November 2012 IM 1171-2 Daikin ZZZ DaikinApplied FRP Digitally Adjustable Display Sensor Used With: :DWHU6RXUFH+HDW3XPSV:6+36HQVRU3DUW1R SmartSource ™ Units - M...
Addendum IM 1152 — Digitally Adjustable Display Sensor 3DJHRI,0 Overview The display sensor is used in conjunction with the MicroTech III equipped units as described in the Application Section below. The same sensor is used for Water Source Heat Pump (WSHP) and for Fan Coil Units (FCU) with just a h...
Addendum IM 1152 — Digitally Adjustable Display Sensor ,03DJHRI Digitally Adjustable Sensor Applications The display sensor can be used on the products shown in Table 1 . Table 1: Product usage guide Units Product Models Controls Used with Digitally Adjustable Sensor with Temperature and Humidity Di...
Addendum IM 1152 — Digitally Adjustable Display Sensor 3DJHRI,0 Sensor Dimensions Figure 2: Sensor dimensions Termination 'DLNLQ0F4XD\UHFRPPHQGVXVLQJDWZLVWHGVKLHOGHGSDLURI at least 22AWG for the power wire connections. The shield should be earth grounded only at the power source. Larger gauge wire m...
Addendum IM 1152 — Digitally Adjustable Display Sensor ,03DJHRI Mounting Location Avoid mounting on outside walls or in direct sunlight. Junction Box, (J-Box) 1. Pull the wire through the wall and out of the junction box, leaving about six inches free. 2. Pull the wire through the hole in the base p...
Addendum IM 1152 — Digitally Adjustable Display Sensor 3DJHRI,0 Setpoint Analog Range Tolerance Table 3: Setpoint analog range tolerance Setpoint Analog Tolerance 55° to 95°F Scale -5° to +5°F Scale Terminal 3 Analog Output # ° )PLQ # ° )PLQ WRYGF # ° F # ° F WRYGF # ° F @0 ° F WRYGF # ° F # ° F WRY...
Addendum IM 1152 — Digitally Adjustable Display Sensor ,03DJHRI Display Descriptions Fan Status & Speed Indicators: The Fan Shape, 4 Wavy Lines and “Auto” word indicate Fan and Speed status. “Fan & No Wavy Lines” indicate the fan is Off. “ Fan & 2 Wavy Lines ” indicate Low. “ Fan & 3...
Addendum IM 1152 — Digitally Adjustable Display Sensor 3DJHRI,0 System Mode Indication (FCU Only) “Heat/Cool/Auto/Off” The “Heat/Cool/Auto/Off” Mode Indicators on the bottom of the display show the mode status of the sensor and are changed by pushing the System Mode button. “Cool” on the display m...
Addendum IM 1152 — Digitally Adjustable Display Sensor ,03DJHRI Front Panel Button Operation the new occupancy condition remains; otherwise the “U” ter-minal will return to the original state and the “Occupied” Icon ZLOOÀDVKWKHGHVLUHGRFFXSDQF\VWDWHHYHU\VHFRQGV Up & Down Setpoint Buttons (Temp Or...
Addendum IM 1152 — Digitally Adjustable Display Sensor 3DJHRI,0 Optional Technician Adjustments P2 Temperature Offset (Factory set to zero). ³83´WRLQFUHDVHRIIVHWXSWR ³'2:1´WRGHFUHDVHRIIVHWGRZQWR P3 Humidity Offset (Factory set to zero). ³83´WRLQFUHDVHRIIVHWXSWR ³'2:1´WRGHFUHDVHRIIVHWGRZQWR P4 ...
Addendum IM 1152 — Digitally Adjustable Display Sensor ,03DJHRI Optional Technician Adjustments 7HPSHUDWXUH9DOXH +XPLGLW\9DOXH Humidity Setpoint. +XPLGLW\9DOXH 7HPSHUDWXUH6HWSRLQW Humidity Setpoint. 7HPSHUDWXUH9DOXH 7HPSHUDWXUH6HWSRLQW +XPLGLW\9DOXH +XPLGLW\6HWSRLQW:6+3 'HIDXOW 3 6HWSRLQW%XWWRQ/RFNR...
Addendum IM 1152 — Digitally Adjustable Display Sensor Daikin ZZZ DaikinApplied FRP ,03DJHRI Diagnostics Problem & Possible Solution (Continued) FAN key does not change Fan Mode &KHFNWRYHULI\)$1LVQRWORFNHGRXWLQ3URJUDPPLQJ 0RGH0HQX3DJH3 MODE key does not change System Mode &KHFNWR...
Addendum IM 1152 — Thermostat Conversion Kit 3. Remove the cover from the thermostat by gently pryingbehind the left hand edge of the cover with a smallscrewdriver, then pulling it off as shown inFigures 1 and 2. Daikin ® Fan Coil Unit Thermostat Conversion Kit – to Eliminate 3-speed Switch Capabili...
Addendum IM 1152 — Thermostat Conversion Kit © 2006 Daikin (800) 432-1342 www.DaikinApplied.com IM 831 Page 2 of 2 Daikin reserves the right to change design and specifications without notice in support of our policy of continuous product and data improvement. 4. Adjust the dip switch and jumpers to...
Addendum IM 1152 — Automatic Changeover Switch Installation and maintenance are to be performed only by qualified personnel who are familiar with and in compliance withstate, local and national codes and regulations, and experienced with this type of equipment. Caution: Sharp edges and coil surfaces...
Daikin Training and Development Now that you have made an investment in modern, efficient Daikin equipment, its care should be a high priority. For training information on all Daikin HVAC products, please visit us at www.Daikin Applied .com and click on training, or call 540-248-9646 and ask for the...
Daikin Manuals
-
Daikin 3MXS68G2V1B
Installation Manual
-
Daikin 3P207257-3
Installation Manual
-
Daikin 4MKS75F2V1B
User Manual
-
Daikin 2AMX50G3V1B
Installation Manual
-
Daikin ACEF 3AV1-(C)(H)
User Manual
-
Daikin ACEF 3AVE
User Manual
-
Daikin ACEF 4AV1-(C)(H)
User Manual
-
Daikin 4MXS68F2V1B
User Manual
-
Daikin AGZ 130D
Installation Manual
-
Daikin AGZ 140D
User Manual
-
Daikin AH123E35AX
User Manual
-
Daikin AGZ030EH
Installation Manual
-
Daikin AGZ 040D
Installation Manual
-
Daikin Altherma HT
Installation Manual
-
Daikin AKZJ8Series
User Manual
-
Daikin Altherma Large Monobloc
User Manual
-
Daikin ARC423A17
User Manual
-
Daikin ARC433B46
User Manual
-
Daikin ARC433B47
User Manual
-
Daikin Altherma LT
User Manual