Page 3 - OUTLINE AND DIMENSIONS
i OUTLINE AND DIMENSIONS UAT(Y)(P)180AMY1 1020 10 60 150 150 150 150 150 60 150 36 170 36 170 10 49 1020 60 60 150 150 150 150 150 150 10 49 10 15 15 100 100 Supply air duct flange (1342) 25 1342 25 25 15 25 265 1000 265 A 46 1300 1392 46 107 1020 173 1300 51 51 50 31 230 192 412 135 1000 CondenserA...
Page 4 - ii
ii OUTLINE AND DIMENSIONS UAT(Y)(P)240,280,320AMY1 - Down flow 200 1990 5 1 51 123 1744 123 B 235 235 2082 25 46 2032 1990 25 46 (2032) 25 15 25 1200 428 51 428 169 124 77 A 50 483 Control box 72 200 200 200 200 200 200 72 200 10 34 34 1 2 0 120 120 49 10 Supply air & Return air Duct flange 428 ...
Page 5 - iii
iii OUTLINE AND DIMENSIONS UAT(Y)(P)450,560AMY1- Down flow RT-A 1200 RT-AR 1670 1800 1330 A B 1200 77 A 483 8 8 C Drain R 1 Supply air Return air Control box Wiring hole Condenser Air iinlet 25 Detail B Condenser Air inlet Condenser Air inlet Hanger (4 places) 1990 51 51 B 235 235 2082 25 46 2032 19...
Page 6 - iv
iv OUTLINE AND DIMENSIONS UAT(Y)(P)C10,C12AMY1 3148
Page 7 - ELECTRICAL WIRING DIAGRAM
Page 9 - vii
vii ELECTRICAL WIRING DIAGRAM MODEL:UAT(P)240,280,320AMY1
Page 10 - viii
viii ELECTRICAL WIRING DIAGRAM MODEL: UATY240,280AMY1
Page 11 - ix
ix ELECTRICAL WIRING DIAGRAM MODEL: UATYP240,280AMY1,UATY(P)320AMY1
Page 13 - xi
xi ELECTRICAL WIRING DIAGRAM MODEL: UATY450,560AMY1
Page 14 - xii
xii ELECTRICAL WIRING DIAGRAM MODEL: UATYP450,560AMY1
Page 15 - xiii
xiii ELECTRICAL WIRING DIAGRAM MODEL: UAT(P)700,850AMY1
Page 16 - xiv
xiv ELECTRICAL WIRING DIAGRAM MODEL: UATY(P)700,850AMY1
Page 17 - xv
xv ELECTRICAL WIRING DIAGRAM MODEL: UAT(P)C10,12AMY1
Page 18 - xvi
xvi ELECTRICAL WIRING DIAGRAM MODEL: UATY(P)C10,12AMY1
Page 19 - English; Caution
1 English 1.1 Location For Installation • Install the unit in such way that air distributed by the unit cannot be drawn in again (as in the case of short circuitof discharge air). Allow sufficient space for maintenance around the unit. • When two or more units are installed in a location, they must ...
Page 21 - Condenser outlet
3 English INSTALLATION OF THE UNIT 1.6 Space required around units (unit ; mm)All space value ; minimum clearance UAT 180~320 Condenserinlet 300 300 700 1000 1500 Evaporator coil,air filter service Electrical controlcircuit & compressorservice Condenseroutlet Condenser outlet Evaporator coil,air...
Page 22 - INSTALLATION OF THE UNIT; piece; Remove
4 INSTALLATION OF THE UNIT 1.7 Unit conversion Please check for accessory parts as below. (Packed in the unit, and available for convertible unit only) In the case of converting to down flow unit, change according to the following steps. 1. Side inlet cover 1 piece 2. Casing leg 2 pieces UAT(Y)(P)24...
Page 24 - ELECTRICAL DATA
6 ELECTRICAL DATA COOLING ONLY (R22) MODEL UAT180AMY1 UAT240AMY1 UAT280AMY1 UAT320AMY1 UAT450AMY1 POWER SUPPLY V/ph/Hz 400 / 3 / 50 VOLTAGE RANGE V 380 ~ 415 MAX CONTINUOUS CURRENT (COMP) A 14.0 23.0 26.9 27.5 23.0 x 2 FULL LOAD CURRENT (FLA, COMP) A 12.1 15.6 16.9 22.3 15.6 x 2 LOCKED ROTOR CURRENT...
Page 25 - Wiring connection to unit
7 English WIRE CONNECTION • All electrical work must be carried out by qualified electrician and accordance with local supply requirementand associated regulation. Method for connecting electric wire Before connecting the wire, consult the electric power company of jurisdiction. 1. The entire wiring...
Page 26 - WIRE CONNECTION; Arrangement of terminal block for controller are shown below.
8 WIRE CONNECTION 5 N 2 3 TB2&3 4 OUT FAN 2 OUT FAN 3 OUT FAN 1 TR A N SF O RM ER NEU TRA L DS1 DS2 DS3 DS4 RO OM ID4 ID3 ID2 ID1 HP 4 HP 3 HP 2 HP 1 ON /O FF GND A 5V CO M P1 CO M P2 CO M P3 CO M P4 IN FA N HE AT ER1 HE AT ER2 4W V1 4W V2 4W V3 4W V4 OU TF AN 4 LI VE B TB1 N L3 L2 L1 1 52C1 51C...
Page 27 - Wiring Example and Selection of Circuit Breaker
9 English WIRE CONNECTION Wiring Example and Selection of Circuit Breaker Values of breaker and wire size are recommended as in table below. 380~415V, 50Hz, 3ø UAT(Y)(P)180AMY1 8.4 32 32 8.4 UAT(Y)(P)240AMY1 8.4 32 32 8.4 UAT(Y)(P)280AMY1 13.3 50 50 13.3 UAT(Y)(P)320AMY1 13.3 50 50 13.3 UAT(Y)(P)450...
Page 28 - OPERATING RANGE; Ensure the operating temperature is in allowable range.; Outdoor
10 OPERATING RANGE Ensure the operating temperature is in allowable range. -10 -5 0 10 20 30 40 5 0 10 15 20 25 30 5 4 24 -10 -5 0 10 20 30 40 5 0 10 15 20 25 30 46 24 -15 -10 -5 0 10 15 20 25 30 5 10 15 27 20 Cooling (R22) Cooling Only Unit & Cooling Mode For Heat Pump Unit Cooling (R407C) Cool...
Page 29 - Warning; SERVICE OF THE FILTER
11 English REFRIGERANT & SPECIAL PRECAUTIONS WHEN DEALING WITH R407C UNIT • All units are pre-charged with R407C refrigerant. • R407C is a zeotropic refrigerant mixture which has zero ozone depletion potential and thus conformed to Montreal Protocol regulation. It requires Polyester oil (POE) oi...
Page 30 - MAINTENANCE; in lukewarm water (below 40°C) and a neutral detergent solution.; TROUBLESHOOTING
12 MAINTENANCE Maintenance Procedures 1. Clean any dirt or dust on the grille or panel by wiping it with a soft cloth soaked in lukewarm water (below 40°C) and a neutral detergent solution. 2. Do not use gasoline, volatile substances or chemicals to clean the indoor unit. 1. If the unit is used for ...