OHUS08-1FCU_b Indoor Units 1 OHUS08-1FCU_b Options Handbook Indoor Units 1. FXFQ - 3’x3’ Ceiling Mounted Cassette Type (Multi Flow) - .......................................3 1.1 BYC125K-W19 — Decoration Panel ................................................................... 31.2 KDBP55H160WA — Pa...
Page 4 - OHUS08-1FCU_b FXFQ - 3’x 3’ Ceiling Mounted Cassette Type (Multi Flow) -
OHUS08-1FCU_b FXFQ - 3’x 3’ Ceiling Mounted Cassette Type (Multi Flow) - Indoor Units 3 1.FXFQ - 3’x 3’ Ceiling Mounted Cassette Type (Multi Flow) - 1.1 BYC125K-W19 — Decoration Panel . Never place the panel facin g down, leanin g a g ainst a wall, or upon a projectin g object. Never touch or put pr...
Page 8 - Dimensions
OHUS08-1FCU_b FXFQ - 3’x 3’ Ceiling Mounted Cassette Type (Multi Flow) - Indoor Units 7 1.2 KDBP55H160WA — Panel Spacer Dimensions Unit:in 5-23/32~5-29/32 in in 4-29/32~5-1/8 4-1/8~11/32 3-11/32~3-17/32 9 9 Never place the panel face down, against the wall, or on a projecting object as it may cause ...
Page 10 - Caution
OHUS08-1FCU_b FXFQ - 3’x 3’ Ceiling Mounted Cassette Type (Multi Flow) - Indoor Units 9 1.3 KDDP55D160(K) — Fresh Air Intake Kit Dimensions Unit: in Unit: in 2 8 -1/2 19-1/3 33-1/2 2 8 -1/2 3-1/2 36 6-1/2 φ 6 Connecting cham b er (left) Connecting cham b er (right) Indoor u nit Decoration panel Insp...
Page 13 - ·Field setting; Dimensions Unit: in; le ASHRAE 52.2 MERV ratings, refer to the follo
FXFQ - 3’x 3’ Ceiling Mounted Cassette Type (Multi Flow) - OHUS08-1FCU_b 12 Indoor Units 1.4 KAFP556D80·160, KAFP557D80·160 — High Efficiency Filter Kit (including filter chamber) KAFP556D 8 0 Caution ·Field setting b y remote controller is necessary w hen the high efficiency filter is installed. Di...
Page 18 - Installation of the High Efficiency Filter unit
OHUS08-1FCU_b FXFQ - 3’x 3’ Ceiling Mounted Cassette Type (Multi Flow) - Indoor Units 17 3K011145A FXFQ12·18·24M V JU Applicable Indoor Units Applicable Indoor Units FXFQ30-36M V JU / FCQ24-42M V JU KAFP556D160 o r KAFP557D160 KAFP556D 8 0 o r KAFP557D 8 0 When you install the High Efficiency Filter...
Page 20 - Cannot
OHUS08-1FCU_b FXFQ - 3’x 3’ Ceiling Mounted Cassette Type (Multi Flow) - Indoor Units 19 1.5 KAFP552H80·160, KAFP553H80·160 — Replacement High Efficiency Filter · Cannot b e w ater- w ashed for re u se. · The Filter Cham b er (KDDFP55D160) is req u ired w hen the high efficiency filter is installed....
Page 21 - KAFP55D160 — Ultra Long Life Filter Kit (including filter chamber)
FXFQ - 3’x 3’ Ceiling Mounted Cassette Type (Multi Flow) - OHUS08-1FCU_b 20 Indoor Units 1.6 KAFP55D160 — Ultra Long Life Filter Kit (including filter chamber) 3K011147 Dimensions Unit:in 12 33 33 2 (dimensions w hen attached) Caution · In order to mo u nt a u ltra long life filter u nit, setting of...
Page 23 - — Replacement UltraLong-Life Filter Unit; Can
FXFQ - 3’x 3’ Ceiling Mounted Cassette Type (Multi Flow) - OHUS08-1FCU_b 22 Indoor Units 1.7 KAFJ55K160H — Replacement UltraLong-Life Filter Unit Can b e w ater- w ashed. Can b e re u sed. Dimensions Unit:in Model Item KAFJ55K160H A v erage efficiency (%) 50 (Gra v ity method) Initial press u re los...
Page 24 - Dimensions Unit:in
OHUS08-1FCU_b FXFQ - 3’x 3’ Ceiling Mounted Cassette Type (Multi Flow) - Indoor Units 23 1.8 KDDFP55D160 — Filter Chamber Dimensions Unit:in 33-7/32 33-7/32 1-31/32 (dimensions w hen attached) Model Item KDDFP55D160 Optional filter High-efficiencyfilter 65 (colorimetric method) KAFP552H 8 0 KAFP552H...
Page 26 - KAFJ551K160 — Replacement Long Life Filter; Has the same specifications as the standard
OHUS08-1FCU_b FXFQ - 3’x 3’ Ceiling Mounted Cassette Type (Multi Flow) - Indoor Units 25 1.9 KAFJ551K160 — Replacement Long Life Filter KAFJ551K160 Dimensions Unit:in 22-1/16 1-3/32 21-11/32 >PS< · Has the same specifications as the standard eq u ipment. · Can b e w ater w ashed. Can b e re u ...
Page 27 - KDBHJ55K160 — Sealing Member of Air Discharge Kit; manual for the optional kit or the catalogue.; Contents of Kit; Prior to installation make sure you have the complete kit of parts.; Make s
FXFQ - 3’x 3’ Ceiling Mounted Cassette Type (Multi Flow) - OHUS08-1FCU_b 26 Indoor Units 1.10 KDBHJ55K160 — Sealing Member of Air Discharge Kit Caution z Refer to the installation manual for both indoor unit and the decoration panel. z When you install other optional kit, it may not be possible to s...
Page 28 - Installation of the insulation
OHUS08-1FCU_b FXFQ - 3’x 3’ Ceiling Mounted Cassette Type (Multi Flow) - Indoor Units 27 The 3 different kinds of settings, Mode number , Settin g switch number , and Settin g of the direction of air dischar g e , sho u ld also b e set w ith the remote controller. Refer to Local setting on the Opera...
Page 30 - OHUS08-1FCU_b FXZQ - 2’x 2’ Ceiling Mounted Cassette Type (Multi Flow) -; BYFQ60B8W1U — Decoration Panel; BEFORE INSTALLATION; NOTE T O INSTALLER; PREPARATION OF DECORATION PANEL; HANDLING OF DECORATION PANELS; uv
OHUS08-1FCU_b FXZQ - 2’x 2’ Ceiling Mounted Cassette Type (Multi Flow) - Indoor Units 29 2. FXZQ - 2’x 2’ Ceiling Mounted Cassette Type (Multi Flow) - 2.1 BYFQ60B8W1U — Decoration Panel 1. BEFORE INSTALLATION 1. PRECAUTIONS • Refer also to the installation man u al attached to the indoor u nit. 2. A...
Page 31 - INSTALLATION OF THE DECORATION PANEL T O THE INDOOR UNIT BODY
FXZQ - 2’x 2’ Ceiling Mounted Cassette Type (Multi Flow) - OHUS08-1FCU_b 30 Indoor Units 3. INSTALLATION OF THE DECORATION PANEL T O THE INDOOR UNIT BODY Refer to the installation man u al attached to the indoor u nit for the installation of the indoor u nit. (1) Match the “PIPI N G SIDE” and “DRAI ...
Page 32 - INSTALLATION OF THE SUCTION GRILL; PREPARATION OF DECORATION PANE
OHUS08-1FCU_b FXZQ - 2’x 2’ Ceiling Mounted Cassette Type (Multi Flow) - Indoor Units 31 [ PRECAUTIONS ] (3) W iring of the decoration panel (Refer to Fi g . 8 ) 6. Remo v e the control b ox lid after making s u re the po w er to the u nit is off. 7. Connect the connectors for the lo uv er motor lea...
Page 33 - KDBHQ44B60 — Sealing Member of Air Discharge Outlet; Component
FXZQ - 2’x 2’ Ceiling Mounted Cassette Type (Multi Flow) - OHUS08-1FCU_b 32 Indoor Units 2.2 KDBHQ44B60 — Sealing Member of Air Discharge Outlet 1P109292B Component 4” x 7” 4” x 14-1/2” 4” x 60-1/2” 1” x 14-1/5” 1/3” x 17-3/4” 2” x 4/5” 1/3”(10mm) 1/3”(10mm)
Page 36 - Dimensions Installation; Using the panel spacer in areas of the ceiling
OHUS08-1FCU_b FXZQ - 2’x 2’ Ceiling Mounted Cassette Type (Multi Flow) - Indoor Units 35 2.3 KDBQ44B60A — Panel Spacer Dimensions Installation Unit:in · Using the panel spacer in areas of the ceiling w ith limited space makes it possi b le to install the air conditioner.. · Hides the gap b et w een ...
Page 37 - Adj
FXZQ - 2’x 2’ Ceiling Mounted Cassette Type (Multi Flow) - OHUS08-1FCU_b 36 Indoor Units 1P107764C Adj u st the height of the indoor u nit, making s u re that the piping does not come into contact w ith the ceiling joist. 7 ”(1 8 0mm) 11-1/5”(2 8 5mm) 5-1/2”(140mm) 9-2/3”(245mm) 10”(255mm) or mor e
Page 39 - KAFQ441B60 — Replacement Long-Life Filter
FXZQ - 2’x 2’ Ceiling Mounted Cassette Type (Multi Flow) - OHUS08-1FCU_b 38 Indoor Units 2.4 KAFQ441B60 — Replacement Long-Life Filter 2P100214B 5/81/8 Dimensions: inches 1/3 1/12 1/3 9/10 2/3 8-1/2 14-1/ 3 13-1/10 1/3 5-1/10 1/6 1/6 12-2/ 5 12-2/ 5 1/2 1/10 1/5 1/6 12-1/2 13-2/5 1/6 1/6 x P50 = 7-9...
Page 40 - KDDQ44X60 — Fresh Air Intake Kit (Direct Installation Type)
OHUS08-1FCU_b FXZQ - 2’x 2’ Ceiling Mounted Cassette Type (Multi Flow) - Indoor Units 39 2.5 KDDQ44X60 — Fresh Air Intake Kit (Direct Installation Type) 2P108307A 1. This kit can be installed to the Ceiling-mounted Cassette type (Multi-flow).2. When installing this kit, duct (nominal diameter of 4” ...
Page 42 - OHUS08-1FCU_b FXDQ - Slim Ceiling Mounted Duct Type -
OHUS08-1FCU_b FXDQ - Slim Ceiling Mounted Duct Type - Indoor Units 41 3. FXDQ - Slim Ceiling Mounted Duct Type - 3.1 KDT25N32·50·63 — Installation Kit for High Humidity in in 14-31/32 14-31/32 9-7/16 9-7/16 8-5/328- 5/ 32 8-5/328- 5/ 32 27-9/16 27-9/1635-7/16 35-7/1643-5/16 43-5/16 in in in in 16-17...
Page 43 - FXSQ - Ceiling Mounted Built-In Type -
FXSQ - Ceiling Mounted Built-In Type - OHUS08-1FCU_b 42 Indoor Units 4. FXSQ - Ceiling Mounted Built-In Type - 4.1 BYBS32·45·71·125DJW1 — Decoration panel . Slide the le v er, then p u ll u p and u nhook the inner frame assem b ly. PanelUnit BYBS32DJ W 1 BYBS45DJ W 1 BYBS71DJ W 1 BYBS125DJ W 1 FXSQ0...
Page 44 - OHUS08-1FCU_b FXSQ - Ceiling Mounted Built-In Type -
OHUS08-1FCU_b FXSQ - Ceiling Mounted Built-In Type - Indoor Units 43 Air discharge adapter (optional) (optional)
Page 47 - Ceiling joist and ceiling joist support re
FXSQ - Ceiling Mounted Built-In Type - OHUS08-1FCU_b 46 Indoor Units 4.2 KTBJ25K36·56·80·160W — Service Access Panel KTBJ25K36W Dimensions Model KTBJ25K36W A 24-21/32 30-9/16 42-3/8 58-1/8 Ceiling opening 23-27/32 × 26-25/32 29-3/4 × 26-25/32 41-9/16 × 26-25/32 57-5/16 × 26-25/32 KTBJ25K56W KTBJ25K8...
Page 51 - Specifications; The filter models for FXSQ12·18M; Characteristics of filter; Dimensions Unit:in
FXSQ - Ceiling Mounted Built-In Type - OHUS08-1FCU_b 50 Indoor Units 4.4 KAFJ251K36·56·80·160 — Replacement Long-Life Filter Specifications Note: The filter models for FXSQ12·18M V JU can be used also as Rear-suction types. Characteristics of filter Model Item KAFJ251K36 KAFJ251K56 KAFJ251K80 KAFJ25...
Page 52 - Dimensions Unit:in; • Filter replacement is easily performed.; Installation
OHUS08-1FCU_b FXSQ - Ceiling Mounted Built-In Type - Indoor Units 51 4.5 KAJ25L36·56·80·160D — Filter Chamber for Bottom Suction KAJ25L56D Dimensions Unit:in u nit:(in) Model A KAJ25L36D KAJ25L56D KAJ25L 8 0D KAJ25L160D 21-21/32 27-9/16 39-3/ 8 55-1/ 8 • Filter replacement is easily performed. Model...
Page 55 - hen maintenance of filter is carried o; hen maintenance of filter is carried o
FXSQ - Ceiling Mounted Built-In Type - OHUS08-1FCU_b 54 Indoor Units Procedure W hen maintenance of filter is carried o u t from the side: (Refer to ta b le for type of long-life filter.) Procedure W hen maintenance of filter is carried o u t from the b ottom: - - - - - - - - - - - - - (3)Install th...
Page 56 - Dimensions Unit:in
OHUS08-1FCU_b FXSQ - Ceiling Mounted Built-In Type - Indoor Units 55 4.7 KSA-25K36·56·80·160 — Canvas Duct (Air Suction Canvas) Installation KSA-25K 8 0 Dimensions Unit:in 2-15/16-10-1/32 15-9/32 D C 15-9/32 D C B A 15-15/16 14-17/32 D C Victor chain 4-M5 tap Main u nit side Panel side Sealant A 21-...
Page 57 - Dimensions Unit:in; • Screens the bottom intake vent.
FXSQ - Ceiling Mounted Built-In Type - OHUS08-1FCU_b 56 Indoor Units 4.8 KBBJ25K36·56·80·160 — Screening Door Installation KBBJ25K36 Dimensions Unit:in • Screens the bottom intake vent. Model Item KBBJ25K36 KBBJ25K56 KBBJ25K80 KBBJ25K160 Appearance Galvanized steel plate Mass (Lbs) 4 FXSQ12M V JU 5 ...
Page 58 - hen con; Example of installation
OHUS08-1FCU_b FXSQ - Ceiling Mounted Built-In Type - Indoor Units 57 4.9 KDJ2507K36·56·80·160 — Air Suction Flange (Rear Return) Dimensions Unit:in A 20-3/4 26-21/32 3 8 -15/32 54-7/32 Model KDJ2507K36 KDJ2507K56 KDJ2507K 8 0 KDJ2507K160 Model Item KDJ2507K36 KDJ2507K56 KDJ2507K 8 0 KDJ2507K160 Size...
Page 59 - hen the air-discharge adaptor is installed,
FXSQ - Ceiling Mounted Built-In Type - OHUS08-1FCU_b 58 Indoor Units 4.10 KDAJ25K36·56·71·140 — Air Discharge Adaptor KDAJ25K71 Model Item KDAJ25K36 KDAJ25K56 KDAJ25K71 KDAJ25K140 D u ct connection diameter φ 7-7/ 8 ×1 port φ 7-7/ 8 ×2 port φ 7-7/ 8 ×4 port Material Steel plate Resin Mass (L b s) 2....
Page 60 - OHUS08-1FCU_b FXMQ - Ceiling Mounted Duct Type -; — High-Efficiency Filter; Specification; The filter chamber is separately re
OHUS08-1FCU_b FXMQ - Ceiling Mounted Duct Type - Indoor Units 59 5. FXMQ - Ceiling Mounted Duct Type - 5.1 KAFP372A80·160 / KAFP373A80·160 — High-Efficiency Filter Specification Note: The filter chamber is separately re q uired when the high efficiency filter is installed. * For applicable ASHRAE 52...
Page 63 - The filter is optional and can be added later to the unit.
FXMQ - Ceiling Mounted Duct Type - OHUS08-1FCU_b 62 Indoor Units Characteristics of filter KAFP372A80, KAFP372A160, KAFP373A80, KAFP373A160 Installation Installation Meet the airflow direction and arrow mark putting on the High-efficiency filter. The filter is optional and can be added later t...
Page 64 - • Set the anchor bolts
OHUS08-1FCU_b FXMQ - Ceiling Mounted Duct Type - Indoor Units 63 5.2 KDDFP37A80·160 — Filter Chamber Characteristics of filter KDDFP37A80, KDDFP37A160 KDDFP37A 8 0 Dimensions Unit:in 12-3/ 8 5-21/32 8 -21/32 (Connection d u ct opening) D u ct side G (Connection d u ct opening) Ser v ice co v er ( ...
Page 65 - Installations; Before Installation
FXMQ - Ceiling Mounted Duct Type - OHUS08-1FCU_b 64 Indoor Units Installations A or more Air conditioner b ody Blo w off S u ction B or more (1) If direction of takin g out the filter is chan g ed, the work should be made in the followin g procedure. Example) In the case of changing the opening and ...
Page 66 - Installation of the filter chamber; In the case of High-efficiency filter; In the case of Long-life filter
OHUS08-1FCU_b FXMQ - Ceiling Mounted Duct Type - Indoor Units 65 Installation of the filter chamber <Remarks>• If scre w s are not tightened steadily, it may ca u se air leakage. • If the prod u ct is not installed horizontally, it may ca u se air leakage, or remo v al of the filter may b ecom...
Page 67 - Dimensions Unit:in
FXMQ - Ceiling Mounted Duct Type - OHUS08-1FCU_b 66 Indoor Units 5.3 KAFP371A80·160 — Long-Life Replacement Filter Specifications Characteristics of filter KAFP371A80 Dimensions Unit:in Model Item KAFP371A80 KAFP371A160 Filter Chamber for Bottom Suction KDDFP37A80 KDDFP37A160 Dimensions (W×D×T) in 1...
Page 68 - OHUS08-1FCU_b FXHQ - Ceiling Suspended Type -; • Can
OHUS08-1FCU_b FXHQ - Ceiling Suspended Type - Indoor Units 67 6. FXHQ - Ceiling Suspended Type - 6.1 KAFJ501D56·112·160 — Replacement Long-Life Filter KAFJ501D56 Dimensions Unit:in A 16-15/16 16-15/16 19-13/32 Model KAFJ501D56 KAFJ501D112 KAFJ501D160 A 7/16 10-1/32 25/32 10-1/4 • Can b e w ater w as...
Page 71 - Remote Sensor; EMBEDDED WIRING; The position of the thermistor used for sensing the; OPERATION TEST AFTER MOUNTING; Sensor box cover; Sensor box; SURFACE MOUNTING
Remote Sensor OHUS08-1FCU_b 70 Indoor Units EMBEDDED WIRING WIRING GUIDE Use the provided extension cable to connect the remote sensor to the electronic control unit (PCB) in the indoor unit. 1. Wire to the electronic control unit (main PCB) In the indoor unit by first removing the existing ther-mis...
Page 72 - VRV Systems; Option Handbook