Page 3 - TD
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi, Kita-ku, Osaka, 530-8323 J apan D AIKIN INDUSTRIES, L TD . EN60335-2-40, 3P104327-1F Shinr i Sada Manager Quality Control Depar tment 1st of Apr il 2009 Lo w V oltage 2006/95/EC Machiner y Saf ety 98/37/EC Electromagnetic Compatibility 2004/108/EC ( I ) FH...
Page 4 - English; CONTENTS; WARNING
1 English CONTENTS 1. SAFETY PRECAUTIONS ............................................ 12. BEFORE INSTALLATION ............................................ 23. SELECTING INSTALLATION SITE AND AIR FLOW DIRECTION ...................................... 3 4. PREPARATIONS BEFORE INSTALLATION ................
Page 5 - BEFORE INSTALLATION; -3 OPTIONAL ACCESSORIES; Table 1
English 2 3. Where there is a machine that generates electromagnetic wave and where voltage fluctuation often occurs such as a factory.Control system may malfunction and as a result the unit may not properly operate. 4. Where flammable gas may leak, where carbon fibre or ignitable dust is suspending...
Page 6 - or installation
3 English 2. Items to be checked at time of delivery ∗ Also review the “SAFETY PRECAUTIONS” Points for explanation about operations 2-4 NOTE TO THE INSTALLER Be sure to instruct customers how to properly operate the unit (especially cleaning filters, operating different functions, and adjusting the ...
Page 7 - Make holes for suspension bolts, refrigerant and drain
English 4 4. PREPARATIONS BEFORE INSTALLATION 4-1 FOR 4-WAY AIR DISCHARGE 1. Relation of holes for indoor unit, suspension bolt posi- tion, piping and wiring. (Refer to Fig. 2) (Illustrations seen from ceiling) ∗ Dimensions in ( ) for 100 and 125 models ∗∗∗ Suspension bolt pitch 2. Make holes for su...
Page 8 - CAUTION
5 English Fig. 7 CAUTION Be careful not to touch the heat exchanger fins. [CEILING HEIGHT] The indoor unit may be installed on ceilings up to 3.5m in height. However, it becomes necessary to make field settings by remote controller when installing the unit at a height over 2.7m.Refer to the section ...
Page 10 - INDOOR UNIT INSTALLATION; -1 Fit the top nuts and washers over the; • Use the washer fixing plate (5) to keep the washer from; -3 Check whether the unit is horizontally level; • The indoor unit is equipped with a built-in drain pump and
7 English 3-way air discharge (Refer to Fig. 16) Fig. 16 [CEILING HEIGHT] The indoor unit may be installed on ceilings up to 3.5 m in height. However, it becomes necessary to make field settings by remote controller when installing the unit at a height over 2.7m.Refer to the section entitled “FIELD ...
Page 11 - REFRIGERANT PIPING WORK; -1 Refrigerant pipes can be run in 3 directions; Coat here with ester or ether oil.
English 8 6. REFRIGERANT PIPING WORK 〈 For refrigerant piping of outdoor units, see the installa- tion manual attached to the outdoor unit. 〉 〈 Execute heat insulation work completely on both sides of the gas piping and the liquid piping. Otherwise, a water leakage can result sometimes. 〉 ( When usi...
Page 12 - -2 For upward and rightward running pipes; DRAIN PIPING WORK; GOOD
9 English CAUTION For local insulation, be sure to insulate all the way to the pipe connections inside the machine.Exposed piping may cause leaking or burns on contact. 6-2 For upward and rightward running pipes • Upward and rightward running pipes are easily rigged with the optional connecting elbo...
Page 13 - Method of adding water
English 10 CAUTION • Do not twist or bend the drain hose (1), so that exces- sive force is not applied to it, as this could cause leaks. PRECAUTIONS FOR UPWARD DRAIN RAISING PIPING • Install the drain raising pipes at a height of less than 500mm. • Install the drain raising pipes at a right angle to...
Page 14 - ELECTRIC WIRING WORK; • Specifications for field wire; Electric wire
11 English 8. ELECTRIC WIRING WORK • All field supplied parts and materials and electric works must conform to local codes. • Use copper wire only.• For electric wiring work, refer also to “WIRING DIAGRAM” attached to the unit body. • For remote controller wiring details, refer to the installation m...
Page 15 - WIRING EXAMPLE; 0-1 Setting ceiling height; Pair type; remote controller control
English 12 9. WIRING EXAMPLE For the wiring of outdoor units, refer to the installation manual attached to the outdoor units. Confirm the system type. • Pair type: 1 remote controller controls 1 indoor unit (stan- dard system). • Simultaneous operation system: 1 remote controller con-trols 2 indoor ...
Page 16 - Table 7
13 English Table 7 10-4 Setting air filter sign • Remote controllers are equiped with liquid crystal dis- play air filer signs to display the time to clean air filters. • Change the SECOND CODE NO. according to Table 8 depending on the amount of dirt or dust in the room.(SECOND CODE NO. is factory s...
Page 17 - INSTALLATION OF CORNER COVER; 2-1 HOW TO TEST OPERATION; PRECAUTIONS; 2-2 HOW TO DIAGNOSE FOR PROBLEMS; NOTE; For rear running pipes
English 14 11. INSTALLATION OF CORNER COVER AND AIR INTAKE GRILLE • Attach the corner covers to the unit and lock in place by screw. (The screws are taped to the corner covers.) • For upward or rightward running pipes, cut the corner covers as shown at Fig. 36 before attaching them. (Refer to Fig. 3...
Page 18 - AF
15 English 2 Keep down the ON/OFF button for 5 seconds or longer in the inspection mode and the above trouble history dis-appears, after the trouble code goes on and off twice, followed by the code “00”(normal). The display changes from the inspection mode to the normal mode. 3 Depending on the mode...
Page 19 - UC; To test run Contractors
English 16 NOTE 1 Depending on the model or the conditions, it may carry out an emergency shut-down. CAUTION • Refer to “2. Items to be checked at time of delivery” on page 3 upon completion of the test run and make sure that all the items are checked. • If the customer’s interior work has not been ...
Page 20 - WIRING DIA
17 English Fig. 38 FUY71 • 100 • 125FJV1 FUYP71 • 100 • 125BV1 33A 33S 33H A1P A2P C1R HAP HBP M1A M1F M2F M1P M3P Q1F R1T R2T RyA RyP SS1 X1M X2M PC RC TC LIMIT SWITCH (SWING FLAP) FLOAT SWITCH PRINTED CIRCUIT BOARD PRINTED CIRCUIT BOARD (TRANSFORMER 230V/16V ) CAPACITOR (M1F/M2F) LIGHT EMITTING DI...