Page 2 - Za n d vo o rd e s t ra a t 3 0 0 , B - 8 4 0 0 O o s t e n d e; DAIKIN PRODUCTS ARE DISTRIBUTED BY :; Specifications are subject to change without prior notice
Split Sky Air Za n d vo o rd e s t ra a t 3 0 0 , B - 8 4 0 0 O o s t e n d e I n t e r n e t h t t p : / / w w w. d a i k i n . b e Daikin units comply with the European regulations that guarantee the safety of the product. Daikin Europe NV is participating in the EUROVENT Certification Programme. ...
Page 3 - TABLE OF CONTENTS; Nominal capacity, capacity steps and nominal input
TABLE OF CONTENTS FH(Y)-GZ/BZ/FHYP-B 1 Features ...................................................................................................... 2 2 Specifications ........................................................................................ 3 Nominal capacity, capacity steps and no...
Page 4 - Features
1 Features + Leaves maximum floor and wall space for furniture,decoration and fittings + New and even more compact casing (only 960 mm width) + Extremely quiet in operation both indoors and outdoors + Automatic air flow director ensures uniform airflow andtemperature distribution (FHY-only) + Air fl...
Page 5 - Specifications; NOMINAL CAPACITY and NOMINAL INPUT; TECHNICAL SPECIFICATIONS
2 Specifications NOMINAL CAPACITY and NOMINAL INPUT For indoor units only:INDOOR UNITS FH35BZV1 FH45BZV1 FH60BZV1 NOMINAL INPUT Cooling kW 0.111 0.111 0.115 For combination indoor units + outdoor units:INDOOR UNITS FH35BZV1 FH45BZV1 FH60BZV1 OUTDOOR UNITS R35GZ7V11 R45GZ7V11/W11 R60GZ7W1 NOMINAL CAP...
Page 7 - NOTES
ELECTRICAL SPECIFICATIONS For indoor units only: FH35BZV1 FH45BZV1 FH60BZV1 CURRENT Nominal runningcurrent cooling A - - - For combination indoor units + outdoor units: FH35BZV1 FH45BZV1 FH60BZV1 R35GZ7V11 R45GZ7V11/W11 R60GZ7W1 CURRENT Nominal runningcurrent cooling A 6.4 10.8/3.98 5.6/6.35 Maximum...
Page 11 - Dimensional drawings
3 Dimensional drawings Model A FH35GZ 12.70 FHY35GZ FH45GZ 15.90 FHY45GZ 1 Air discharge grille 2 Air suction grille 3 Air filter 4 Gas pipe connection φ A Flare connection 5 Liquid pipe connection J 6.35 Flare connection 6 Drain pipe connection V.P.20 7 Grounding terminal M4 8 Suspension bracket 9 ...
Page 15 - Piping diagrams
4 Piping diagrams O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe Indoor heat exchanger Field piping 4D024085A FH35 ∼ 60BZ FHYP35 ∼ 125B Field piping Refrigerant pipe connection port diameters Model A B FHYP35-45BV1FH35BZV1 6.4 12.7 FH45-60BZV1 6...
Page 16 - Wiring diagrams
5 Wiring diagrams 3D027501-1 FH35 ∼ 60BZ 1-RED, 2-WHITE, 3-BLACK33A Limit switch (swing flap) A1P Printed circuit board A2P Printed circuit board(Transformer 220-240V/16V) C1R Capacitor (M1F) F1U Fuse (250V,5A) HAP Light emitting diode (service monitor green) M1A Motor (swing flap) M1F Motor (indoor...
Page 18 - Sound level; Sound level data
6 Sound level 6-1 Sound level data Model Sound pressure level Sound power level (H) (cooling) 230V Measuring location 50Hz Cooling only H L FH35BZ 37 32 53 FH45BZ 38 33 54 FH60BZ 38 33 54 FHYP71B 39 35 55 FHYP100B 42 37 58 FHYP125B 44 39 60 Model Sound pressure level Sound power level (H) (cooling/h...
Page 19 - Sound pressure spectrum; Cooling only
6 Sound level 6-2 Sound pressure spectrum FH35BZV1/FHYP35BV1 FH60BZV1/FHYP60BV1 Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band sound pressure level Octave band sound pressure level Cooling only Octave band sound pressure level FH45BZV1/FHYP45BV1 Octave band center fr...
Page 21 - Accessories; Standard accessories
7 Accessories 7-1 Standard accessories Other: installation manual, operation manual Name j 1 Drain hose j 2 Clamp j 3 Washer for hanging bracket j 4 Clamp j 5 Washer fixing plate Quantity 1 pc. 1 pc. 8 pcs. 6 pcs. 1 pc. Shape Name Insulation for fitting Sealing pad (Other) + Installation manual + Op...
Page 22 - Optional accessories
7 Accessories 7-2 Optional accessories Name of option Remark: FHY-GZ 35 45 Drain pump kit KDUJ5F50 Replacement long-life filter Resin net KAFJ501F56 L-type piping kit (for upward direction) for FHY KHFJ5F50 Remote control (wired type) for FHY BRC1B517 Central remote control DCS302B51 unified ON/OFF ...
Page 23 - Control systems; Wired remote control
8 Control systems 8-1 Wired remote control BRC1B517 FH(Y)-GZ BRC1B517 Remote control Fig. 1 BRC1B517 • Ceiling Suspended Unit • R-407C • FH(Y)-GZ/BZ/FHYP-B 10 8 8-1 21 • Split - Sky Air • Indoor Units
Page 25 - Operation procedure wired remote control; Field settings
8 Control systems 8-2 Operation procedure wired remote control 1 Remote control BRC1C517 BRC1C517 Field settings a. Unit NOb. First code NOc. Second code NOd. Mode NOe. Field set mode Procedure 1. When in the normal mode, press the ’’ u ’’ button for a minimum of four seconds, and the FIELD SET MODE...