SiENBE07-618_C Service Manual Inverter Pair Duct Connected Type C-Series [Applied Models] z Inverter Pair: Cooling only z Inverter Pair: Heat Pump SIENBE07-618_C_FRONT.pdf 2 9/02/2011 9:25:03
SiENBE07-618_C Introduction v 1. Introduction 1.1 Safety Cautions Cautions and Warnings Be sure to read the following safety cautions before conducting repair work. The caution items are classified into “ Warning ” and “ Caution ”. The “ Warning ” items are especially important since they can le...
SiENBE07-618_C Introduction ix 1.2 Used Icons Icons are used to attract the attention of the reader to specific information. The meaning of each icon is described in the table below: Be sure to measure the insulation resistance after the repair, and make sure that the resistance is 1 M Ω or higher. ...
SiENBE07-618_C List of Functions 1 Part 1 List of Functions 1. Functions.................................................................................................2 SIENBE07-618_C_FRONT.pdf 13 9/02/2011 9:25:04
SiENBE07-618_C Specifications 5 Part 2 Specifications 1. Specifications ..........................................................................................6 1.1 Cooling Only .............................................................................................6 1.2 Heat Pump .............
Specifications SiENBE07-618_C 6 Specifications 1. Specifications 1.1 Cooling Only 50 Hz, 230 V Models Indoor Units FDKS50CVMB FDKS60CVMB Outdoor Units RKS50E2(3)V1B RKS60E2(3)V1B Capacity Rated (Min. ~ Max.) kW 5.0 (2.0 ~ 5.3) 6.0 (2.0 ~ 6.5) Btu/h 17,100 (6,800 ~ 18,100) 20,500 (6,800 ~ 22,200) kca...
SiENBE07-618_C Specifications Specifications 9 1.2 Heat Pump 50 Hz, 230 V Models Indoor Units FDXS50CVMB FDXS60CVMB Outdoor Units RXS50E2(3)V1B RXS60E2(3)V1B Cooling Heating Cooling Heating Capacity Rated (Min. ~ Max.) kW 5.0 (2.0 ~ 5.3) 5.8 (2.0 ~ 6.0) 6.0 (2.0 ~ 6.5) 7.0 (2.0 ~ 8.0) Btu/h 17,100 (...
SiENBE07-618_C 12 Printed Circuit Board Connector Wiring Diagram Part 3 Printed Circuit Board Connector Wiring Diagram 1. Printed Circuit Board Connector Wiring Diagram..................................13 1.1 Indoor Unit ..................................................................................
SiENBE07-618_C Printed Circuit Board Connector Wiring Diagram Printed Circuit Board Connector Wiring Diagram 13 1. Printed Circuit Board Connector Wiring Diagram 1.1 Indoor Unit Connectors and Other Parts PCB(1): Control PCB PCB(2): Display PCB 1) S1 Connector for AC fan motor 2) S7 Connector for AC...
SiENBE07-618_C Printed Circuit Board Connector Wiring Diagram Printed Circuit Board Connector Wiring Diagram 15 1.2 Outdoor Unit Connectors and Other Parts PCB (1): Main PCB PCB (2): Service Monitor PCB 1) S10 Connector for terminal board (indoor - outdoor transmission) 2) S20 Connector for electron...
SiENBE07-618_C Function and Control 17 Part 4 Function and Control 1. Main Functions ......................................................................................18 1.1 Temperature Control ..............................................................................18 1.2 Frequency Princip...
Main Functions SiENBE07-618_C 18 Function and Control 1. Main Functions 1.1 Temperature Control Definitions of Temperatures The definitions of temperatures are classified as following. Room temperature: temperature of lower part of the room Set temperature: temperature set by remote control Ro...
Main Functions SiENBE07-618_C 20 Function and Control 1.3 Fan Speed Control for Indoor Units Outline Phase control and fan speed control contains 9 steps: LLL, LL, SL, L, ML, M, MH, H, and HH.The airflow rate can be automatically controlled depending on the difference between the room thermistor tem...
SiENBE07-618_C Main Functions Function and Control 21 1.4 Program Dry Operation Outline Program dry operation removes humidity while preventing the room temperature from lowering.Since the microcomputer controls both the temperature and airflow rate, the temperature adjustment and fan adjustment but...
Main Functions SiENBE07-618_C 22 Function and Control 1.5 Automatic Operation Outline Automatic Cooling / Heating Function When the AUTO mode is selected with the remote control, the microcomputer automatically determines the operation mode as cooling or heating according to the room temperature and...
SiENBE07-618_C Main Functions Function and Control 23 1.6 Thermostat Control Thermostat control is based on the difference between the room thermistor temperature and the target temperature. Thermostat OFF Condition The temperature difference is in the zone A. Thermostat ON Condition The tempera...
Main Functions SiENBE07-618_C 24 Function and Control 1.7 NIGHT SET Mode Outline When the OFF timer is set, the NIGHT SET Mode is automatically activated. The NIGHT SET Mode keeps the airflow rate setting. Detail The NIGHT SET Mode continues operation at the target temperature for the first one hour...
SiENBE07-618_C Main Functions Function and Control 25 1.8 HOME LEAVE Operation Outline HOME LEAVE operation is a function that allows you to record your favorite set temperature and airflow rate. You can start your favorite operation mode simply by pressing the [HOME LEAVE] button on the remote cont...
Main Functions SiENBE07-618_C 26 Function and Control 1.9 Inverter POWERFUL Operation Outline In order to exploit the cooling and heating capacity to full extent, operate the air conditioner by increasing the indoor fan rotating speed and the compressor frequency. Detail When POWERFUL button is pres...
Function of Thermistor SiENBE07-618_C 28 Function and Control 2. Function of Thermistor A Outdoor Heat Exchanger Thermistor 1. The outdoor heat exchanger thermistor is used for controlling target discharge pipe temperature. The system sets the target discharge pipe temperature according to the outdo...
SiENBE07-618_C Control Specification Function and Control 29 3. Control Specification 3.1 Mode Hierarchy Outline There are two modes; the one is the normal operation mode and the other is the forced operation mode for installation and providing service. Detail For Cooling Only Model There are follow...
Control Specification SiENBE07-618_C 30 Function and Control 3.2 Frequency Control Outline Frequency is determined according to the difference between the room thermistor temperature and the target temperature. The function is explained as follows.1. How to determine frequency2. Frequency command fr...
Control Specification SiENBE07-618_C 32 Function and Control 3.3 Controls at Mode Changing / Start-up 3.3.1 Preheating Operation Outline The inverter operation in open phase starts with the conditions of the outdoor temperature, the discharge pipe temperature, and the radiation fin temperature (inte...
SiENBE07-618_C Control Specification Function and Control 33 3.3.4 3-minute Standby Turning on the compressor is prohibited for 3 minutes after turning it off.(Except when defrosting.) 3.3.5 Compressor Protection Function When turning the compressor from OFF to ON, the upper limit of frequency is se...
Control Specification SiENBE07-618_C 34 Function and Control 3.5 Input Current Control Outline The microcomputer calculates the input current during the compressor is running, and sets the frequency upper limit from the input current.In case of heat pump model, this control which is the upper limit ...
SiENBE07-618_C Control Specification Function and Control 35 3.6 Freeze-up Protection Control Outline During cooling operation, the signal sent from the indoor unit controls the operating frequency limitation and prevents freezing of the indoor heat exchanger. (The signal from the indoor unit is div...
Control Specification SiENBE07-618_C 36 Function and Control 3.8 Outdoor Fan Control 1. Fan OFF delay when stopped The outdoor fan is turned OFF 60 seconds after the compressor stops. 2. Fan ON control to cool down the electrical box The outdoor fan is turned ON when the electrical box temperature i...
Control Specification SiENBE07-618_C 38 Function and Control 3.11 Electronic Expansion Valve Control Outline The following items are included in the electronic expansion valve control. Electronic expansion valve is fully closed 1. Electronic expansion valve is fully closed when turning on the power....
Control Specification SiENBE07-618_C 40 Function and Control 3.11.6 Disconnection of the Discharge Pipe Thermistor Outline The disconnection of the discharge pipe thermistor is detected by comparing the discharge pipe temperature with the condensation temperature. If the discharge pipe thermistor is...
SiENBE07-618_C Control Specification Function and Control 41 3.12 Malfunctions 3.12.1 Sensor Malfunction Detection Sensor malfunction may occur in the thermistor. Relating to Thermistor Malfunction 1. Outdoor heat exchanger thermistor2. Discharge pipe thermistor3. Radiation fin thermistor4. Outdoor ...
Control Specification SiENBE07-618_C 42 Function and Control 3.13 Forced Operation Mode Outline Forced operation mode includes only forced cooling. Detail Item Forced Cooling Conditions 1) The outdoor unit is not abnormal and not in the 3-minute standby mode. 2) The outdoor unit is not operating. Th...
SiENBE07-618_C Operation Manual 43 Part 5 Operation Manual 1. System Configuration ............................................................................442. Operation Manual..................................................................................45 2.1 Remote Control ...................
System Configuration SiENBE07-618_C 44 System Configuration 1. System Configuration After the installation and test operation of the room air conditioner have been completed, it should be operated and handled as described below. Every user would like to know the correct method of operation of the ro...
SiENBE07-618_C Operation Manual System Configuration 45 2. Operation Manual 2.1 Remote Control Remote control 1 2 5 6 9 13 15 14 10 12 11 < ARC433B69, B76 > 3 4 7 8 1. Signal transmitter: • It sends signals to the indoor unit. 2. Display: • It displays the current settings. (In this illustra...
Operation Manual SiENBE07-618_C 46 System Configuration 2.2 Auto Dry Cool Heat Fan Operation The air conditioner operates with the operation mode of your choice. From the next time on, the air conditioner will operate with the same operation mode. To start operation 1. Press “MODE selector button”...
SiENBE07-618_C Operation Manual System Configuration 47 To change the air flow rate setting 5. Press “FAN setting button”. • Indoor unit quiet operation When the air flow is set to “ ” , the noise from the indoor unit will become quieter. Use this when making the noise quieter. The unit might lose...
Operation Manual SiENBE07-618_C 48 System Configuration 2.3 POWERFUL Operation NOTE POWERFUL operation quickly maximizes the cooling (heating) effect in any operation mode. You can get the maximum capacity To start POWERFUL operation 1. Press “POWERFUL button”. • POWERFUL operation ends in 20 minu...
SiENBE07-618_C Operation Manual System Configuration 49 2.4 OUTDOOR UNIT QUIET Operation NOTE OUTDOOR UNIT QUIET operation lowers the noise level of the outdoor unit by changing the frequency and fan speed on the outdoor unit. This function is convenient during night. To start OUTDOOR UNIT QUIET o...
Operation Manual SiENBE07-618_C 50 System Configuration 2.5 HOME LEAVE Operation Before using HOME LEAVE operation HOME LEAVE operation is a function which allows you to record your preferred temperature and air flow rate settings. To start HOME LEAVE operation 1. Press “HOME LEAVE button”. • “ ” ...
SiENBE07-618_C Operation Manual System Configuration 51 What’s the HOME LEAVE operation Is there a set temperature and air flow rate which is most comfortable, a set temperature and air flow rate which you use the most? HOME LEAVE operation is a function that allows you to record your favorite set...
Operation Manual SiENBE07-618_C 52 System Configuration 2.6 TIMER Operation NOTE Timer functions are useful for automatically switching the air conditioner on or off at night or in the morning. You can also use OFF TIMER and ON TIMER in combination. To use OFF TIMER operation • Check that the cloc...
SiENBE07-618_C Operation Manual System Configuration 53 ATTENTION To use ON TIMER operation • Check that the clock is correct. If not, set the clock to the present time. 1. Press “ON TIMER button”. • 6:00 is displayed. • “ ”blinks. 2. Press “TIMER Setting button” until the time setting reaches the...
SiENBE07-618_C 54 Service Diagnosis Part 6 Service Diagnosis 1. Caution for Diagnosis ............................................................................55 1.1 Troubleshooting with LED ......................................................................55 2. Problem Symptoms and Measures ...
SiENBE07-618_C Caution for Diagnosis Service Diagnosis 55 1. Caution for Diagnosis 1.1 Troubleshooting with LED Indoor Unit The operation lamp blinks when any of the following errors is detected.1. When a protection device of the indoor unit or the outdoor unit is activated, or when the thermistor m...
Problem Symptoms and Measures SiENBE07-618_C 56 Service Diagnosis 2. Problem Symptoms and Measures Symptom Check Item Details of Measure Reference Page The units does not operate. Check the power supply. Check to make sure that the rated voltage is supplied. — Check the type of the indoor units. Che...
SiENBE07-618_C Service Check Function Service Diagnosis 57 3. Service Check Function Check Method 1 1. When the timer cancel button is held down for 5 seconds, “ 00 ” indication appears on the temperature display section. 2. Press the timer cancel button repeatedly until a long beep sounds. The co...
Troubleshooting SiENBE07-618_C 60 Service Diagnosis 4. Troubleshooting 4.1 Error Codes and Description H : Displayed only when system-down occurs. Error Codes Description Reference Page System 00 Normal — U0 H Refrigerant shortage 90 U2 Low-voltage detection or over-voltage detection 92 U4 Signal tr...
SiENBE07-618_C Troubleshooting Service Diagnosis 61 4.2 Indoor Unit PCB Abnormality Remote Control Display A1 Method of Malfunction Detection Evaluation of zero-cross detection of power supply by the indoor unit PCB. Malfunction Decision Conditions There is no zero-cross detection in approximately 1...
Troubleshooting SiENBE07-618_C 64 Service Diagnosis 4.4 Fan Motor (AC motor) or Related Abnormality Remote Control Display A6 Method of Malfunction Detection The rotation speed is detected by the Hall IC while the fan motor is operating. The rotation speed determines the error. Malfunction Decision ...
SiENBE07-618_C Troubleshooting Service Diagnosis 65 4.5 Thermistor or Related Abnormality (Indoor Unit) Remote Control Display C4 , C9 Method of Malfunction Detection The temperatures detected by the thermistors determine thermistor errors. Malfunction Decision Conditions The thermistor input is mor...
Troubleshooting SiENBE07-618_C 68 Service Diagnosis 4.8 Outdoor Unit PCB Abnormality Remote Control Display E1 Method of Malfunction Detection Detection within the program of the microcomputer Malfunction Decision Conditions The program of the microcomputer is in abnormal running order. Supposed...
Troubleshooting SiENBE07-618_C 72 Service Diagnosis 4.12 Input Overcurrent Detection Remote Control Display E8 Method of Malfunction Detection An input overcurrent is detected by checking the input current value being detected by CT with the compressor running. Malfunction Decision Conditions The ...
SiENBE07-618_C Troubleshooting Service Diagnosis 73 4.13 Four Way Valve Abnormality Remote Control Display EA Method of Malfunction Detection The room temperature thermistor, the indoor heat exchanger thermistor, the outdoor temperature thermistor, and the outdoor heat exchanger thermistor are check...
SiENBE07-618_C Troubleshooting Service Diagnosis 75 4.14 Discharge Pipe Temperature Control Remote Control Display F3 Method of Malfunction Detection An error is determined with the temperature detected by the discharge pipe thermistor. Malfunction Decision Conditions If the temperature detected b...
Troubleshooting SiENBE07-618_C 76 Service Diagnosis 4.15 High Pressure Control in Cooling Remote Control Display F6 Method of Malfunction Detection High-pressure control (operation half, frequency drop, etc.) is activated in cooling mode if the temperature sensed by the outdoor heat exchanger thermi...
SiENBE07-618_C Troubleshooting Service Diagnosis 77 4.16 Compressor System Sensor Abnormality Remote Control Display H0 Method of Malfunction Detection The system checks the supply voltage and the DC voltage before the compressor starts. The system checks the compressor current right after the c...
Troubleshooting SiENBE07-618_C 78 Service Diagnosis 4.17 Position Sensor Abnormality Remote Control Display H6 Method of Malfunction Detection A compressor start-up failure is detected by checking the compressor running condition through the position detection circuit. Malfunction Decision Condition...
Troubleshooting SiENBE07-618_C 80 Service Diagnosis 4.18 CT or Related Abnormality Remote Control Display H8 Method of Malfunction Detection A CT or related error is detected by checking the compressor running frequency and CT-detected input current. Malfunction Decision Conditions The compressor ...
Troubleshooting SiENBE07-618_C 84 Service Diagnosis 4.20 Electrical Box Temperature Rise Remote Control Display L3 Method of Malfunction Detection An electrical box temperature rise is detected by checking the radiation fin thermistor with the compressor off. Malfunction Decision Conditions With t...
Troubleshooting SiENBE07-618_C 86 Service Diagnosis 4.21 Radiation Fin Temperature Rise Remote Control Display L4 Method of Malfunction Detection A radiation fin temperature rise is detected by checking the radiation fin temperature with the compressor on. Malfunction Decision Conditions The radia...
Troubleshooting SiENBE07-618_C 88 Service Diagnosis 4.22 Output Overcurrent Detection Remote Control Display L5 Method of Malfunction Detection An output overcurrent is detected by checking the current that flows in the inverter DC section. Malfunction Decision Conditions A position signal error o...
Troubleshooting SiENBE07-618_C 90 Service Diagnosis 4.23 Refrigerant Shortage Remote Control Display U0 Method of Malfunction Detection Refrigerant shortage detection I: Refrigerant shortage is detected by checking the input current value and the compressor output frequency. If the refrigerant is sh...
Check SiENBE07-618_C 94 Service Diagnosis 5. Check 5.1 How to Check 5.1.1 Electronic Expansion Valve Check Check No.04 Conduct the followings to check the electronic expansion valve (EV).1. Check to see if the EV connector is correctly connected to the PCB.2. Turn the power off and on again, and che...
Check SiENBE07-618_C 98 Service Diagnosis 5.1.6 Outdoor Fan System Check Check No.09 DC motor 5.1.7 Power Supply Waveforms Check Check No.10 Measure the power supply waveform between No.1 and No.2 on the terminal board, and check the waveform disturbance. Check to see if the power supply waveform ...
Check SiENBE07-618_C 100 Service Diagnosis 5.1.11 Rotation Pulse Input on the Outdoor Unit PCB Check Check No.15 <Outdoor fan motor>Make sure that the voltage of 320 ± 30 V is applied.1. Set operation off and power off. Disconnect the connector S70.2. Check that the voltage between the pins 4 ...
SiENBE07-618_C Removal Procedure 101 Part 7 Removal Procedure 1. Outdoor Unit ........................................................................................102 1.1 Removal of Outer Panels .....................................................................102 1.2 Removal of Outdoor Fan / ...
Outdoor Unit SiENBE07-618_C 102 Removal Procedure 1. Outdoor Unit 1.1 Removal of Outer Panels Procedure Warning Be sure to wait for 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points 1. Remove the panels. Take care not to cut your finger by the...
Outdoor Unit SiENBE07-618_C 106 Removal Procedure 1.2 Removal of Outdoor Fan / Fan Motor Procedure Warning Be sure to wait for 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points 1. Remove the electrical box cover. Preparation Remove the top pan...
Outdoor Unit SiENBE07-618_C 110 Removal Procedure 1.3 Removal of Electrical Box Procedure Warning Be sure to wait for 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points 1 Remove the 2 screws of the shield plate. Preparation Remove the top panel...
SiENBE07-618_C Outdoor Unit Removal Procedure 115 1.4 Removal of PCB Procedure Warning Be sure to wait for 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points 1 Disconnect the connectors from the service monitor PCB [S52] [S102]. Preparation Rem...
Outdoor Unit SiENBE07-618_C 118 Removal Procedure 1.5 Removal of Sound Blanket / Thermistors Procedure Warning Be sure to wait for 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points 1 Remove the sound blanket (back). 2 Remove the sound blanket (o...
Outdoor Unit SiENBE07-618_C 120 Removal Procedure 1.6 Removal of Four Way Valve Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points 1 Remove the screw and remove the four way valve coil. Warning Be careful not to ...
SiENBE07-618_C Outdoor Unit Removal Procedure 121 1.7 Removal of Electronic Expansion Valve Procedure Warning Be sure to wait for 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points 1 Pull out the electronic expansion valve coil. 2 Remove the shee...
Outdoor Unit SiENBE07-618_C 122 Removal Procedure 1.8 Removal of Compressor Procedure Warning Be sure to wait for 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points 1 Remove the terminal cover. 2 Disconnect the lead wires of the compressor. Termi...
SiENBE07-618_C Trial Operation and Field Settings 125 Part 8 Trial Operation and Field Settings 1. Trial Operation ....................................................................................1262. Field Settings ...................................................................................
SiENBE07-618_C Field Settings Trial Operation and Field Settings 127 2. Field Settings 2.1 When 2 Units are Installed in 1 Room When 2 indoor units are installed in 1 room, 1 of the 2 pairs of indoor unit and infrared remote control can be set for different addresses.Both the indoor unit PCB and the...
Field Settings SiENBE07-618_C 128 Trial Operation and Field Settings 2.2 Facility Setting Switch (cooling at low outdoor temperature) Outline For Cooling Only Model This function is limited only for facilities (the target of air conditioning is equipment (such as computer)). Never use it in a reside...
SiENBE07-618_C Application of Silicon Grease to a Power Transistor and a Diode Bridge Trial Operation and Field Settings 129 3. Application of Silicon Grease to a Power Transistor and a Diode Bridge Applicable Models All outdoor units using inverter type compressor for room air conditioner. When the...
SiENBE07-618_C 130 Appendix Part 9 Appendix 1. Piping Diagrams ..................................................................................131 1.1 Indoor Unit ............................................................................................131 1.2 Outdoor Unit .........................
Daikin Manuals
-
Daikin 3MXS68G2V1B
Installation Manual
-
Daikin 3P207257-3
Installation Manual
-
Daikin 4MKS75F2V1B
User Manual
-
Daikin 2AMX50G3V1B
Installation Manual
-
Daikin ACEF 3AV1-(C)(H)
User Manual
-
Daikin ACEF 3AVE
User Manual
-
Daikin ACEF 4AV1-(C)(H)
User Manual
-
Daikin 4MXS68F2V1B
User Manual
-
Daikin AGZ 130D
Installation Manual
-
Daikin AGZ 140D
User Manual
-
Daikin AH123E35AX
User Manual
-
Daikin AGZ030EH
Installation Manual
-
Daikin AGZ 040D
Installation Manual
-
Daikin Altherma HT
Installation Manual
-
Daikin AKZJ8Series
User Manual
-
Daikin Altherma Large Monobloc
User Manual
-
Daikin ARC423A17
User Manual
-
Daikin ARC433B46
User Manual
-
Daikin ARC433B47
User Manual
-
Daikin Altherma LT
User Manual